<chapter heading="Chapter 22. Fire Safety Code - Regulations">
  <section heading="COMCOR 22.00.01 Hazardous Materials Use Permit">
    <regulation heading="COMCOR 22.00.01 Hazardous Materials Use Permit">
      <subsection heading="22.00.01.01 Statement of Purpose">
        <paragraph indent="2">These regulations augment existing state and federal Community Right-to Know reporting and emergency planning requirements set out in Sec 6-501, et. seq., and Sec. 7-101, et seq., of the Environment Article of the Annotated Code of Maryland (1987 volume as amended), and Subtitle 5, Sec. 22-501, et. seq., of the Health-General Volume of the Annotated Code of Maryland (1990 Replacement volume as amended), and Sections 301-304, 311 and 312 of the federal Superfund Amendments and Reauthorization Act of 1986, also known as the Emergency Planning and Community Right-to-Know Act of 1986 (EPCRA). Pub. L. 99-499, 100 Stat. 1613 (1986). These regulations require all facilities using, processing, transferring, storing, or manufacturing hazardous substances that exceed a minimum threshold level to report these substances and their locations, develop contingency plans in the event of accidental release, and provide these plans to the Office of Emergency Management and Homeland Security on behalf of the Local Emergency Planning Council. Revisions to this Regulation may be made using Method 2, in accordance with Chapter 22 of the Montgomery County Fire Code.</paragraph>
      </subsection>
      <subsection heading="22.00.01.02 Definitions">
        <paragraph indent="2">(a)   Corporate responsible officer. 1   The term “corporate responsible officer” means that individual of a regulated facility who is responsible for ensuring compliance with the applicable federal, state, and local hazardous or toxic substance control laws and regulations including reporting requirements.</paragraph>
        <paragraph indent="2">(b)   EPCRA. Title III of the Superfund Amendments and Reauthorization Act of 1986, also known as the Emergency Planning and Community Right-to-Know Act of 1986.</paragraph>
        <paragraph indent="2">(c)   Extremely Hazardous Substances.  The term “extremely hazardous substance” means any substance listed in Appendices A and B of Title 40 of the Code of Federal Regulations, Part 355 (40 CFR 355), Emergency Planning and Notification, as published in the U.S. Environmental Protection Agency "Title III List of Lists, Consolidated List of Chemicals Subject to Reporting Under the Emergency Planning and Community Right-to-Know Act, as amended.</paragraph>
        <paragraph indent="2">(d)   Facility. 2   The term “facility” includes, but is not limited to:</paragraph>
        <paragraph indent="3">(1)   Any single industrial, commercial, educational, recreational 3 , agricultural, research, or institutional occupancy;</paragraph>
        <paragraph indent="3">(2)   Located within a contiguous boundary; or</paragraph>
        <paragraph indent="3">(3)   Confined to a single detached structure.</paragraph>
        <paragraph indent="2">(e)   Facility Emergency Coordinator. The term “facility emergency coordinator” (FEC) means a designated employee of a regulated facility who is responsible for maintaining a working knowledge of the site, building, and chemicals or hazardous substances stored on site, is the primary contact for emergency services, including Fire Departments and Police, and the Office of Emergency Management and Homeland Security during emergency communications with the facility, is responsible for ensuring compliance with applicable federal, state, and local hazardous or toxic substance control laws and regulations, and is subject to in personam service of process within the State of Maryland.</paragraph>
        <paragraph indent="2">(f)   Fire Administrator.  The non-uniformed department head of the Montgomery County Fire and Rescue Service.</paragraph>
        <paragraph indent="2">(g)   General Use Facility. The term “General Use Facility” includes any facility which uses, processes, stores, transfers or manufactures one or more extremely hazardous substances or hazardous substances, in quantities set out in this regulation, as to generally pose a risk of injury to emergency responders or the surrounding community.</paragraph>
        <paragraph indent="2">(h)   Hazardous inventory. The term “hazardous inventory” means the quantity of hazardous substances or extremely hazardous substances used, processed, transferred, stored, or manufactured and present at any time in a facility.</paragraph>
        <paragraph indent="2">(i)   Hazardous substances. 4   The term “hazardous substance” means:</paragraph>
        <paragraph indent="3">(1)   Any substance that:</paragraph>
        <paragraph indent="4">(A)   conveys toxic or lethal effects, or may otherwise injure human, plant, animal, or  aquatic life, or persists in the environment.</paragraph>
        <paragraph indent="4">(B)   is capable of causing cancer (carcinogen), chromosomal alterations (mutagen), fetal abnormality (teratogen), or allergic reaction (allergen or sensitizer); or</paragraph>
        <paragraph indent="4">(C)   any matter that is designated as an explosive material; radioactive material; etiological agent 5 ; flammable gas, liquid or solid; combustible liquid or solid; compressed gas; or cryogenic 6  liquid or solid; and</paragraph>
        <paragraph indent="3">(2)   Includes any matter identified as a hazardous waste by the United States Environmental Protection Agency or Maryland State Department of the Environment (excluding waste motor oil).</paragraph>
        <paragraph indent="3">(3)   Includes any matter identified as a hazardous substance under Article 101(14) of the Comprehensive Environmental Response, Compensation, and Liability Act of 1980, as amended.</paragraph>
        <paragraph indent="3">(4)   Includes any substance defined as a toxic material in Subpart Z of the U.S. Occupational Safety and Health Administration regulations published in 29 CFR 1910, “General Industrial Standards”,1970 as amended, or by the Maryland Occupational Safety and Health Administration.</paragraph>
        <paragraph indent="2">(j)   High Use Facility. The term “High Use Facility” includes any facility which uses, processes, stores, transfers, or manufactures one or more extremely hazardous substances or hazardous substances as defined in Sec II(i), in quantities set out in this regulation, as to pose significant risk of injury to emergency responders or the surrounding community.</paragraph>
        <paragraph indent="2">(k)   LEPC. The Montgomery County Local Emergency Planning Council for Hazardous Materials.</paragraph>
        <paragraph indent="2">(1)   Light Use Facility. The term “Light Use Facility” includes any facility which uses, processes, stores, transfers or manufactures one more hazardous substances, in quantities set out in this regulation, as to pose a recognized limited risk of injury to emergency responders or the surrounding community.</paragraph>
        <paragraph indent="2">(m)   OEMHS Manager. The non-uniformed department head of the Montgomery County Office of Emergency Management and Homeland Security.</paragraph>
        <paragraph indent="2">(n)   SARA Facility. The term “SARA facility” means any facility which is subject to the emergency planning and reporting requirements of the federal Superfund Amendments and Reauthorization Act of 1986, also known as the Emergency Planning and Community Right-to-Know Act of 1986 (Title III of the Superfund Amendments and Reauthorization Act of 1986, Pub. L. 99-499).</paragraph>
        <paragraph indent="2">(o)   Threshold Planning Quantity (TPQ). The term “Threshold Planning Quantity” means that quantity of a hazardous substance which subjects the facility to the reporting requirements of the Superfund Amendments and Reauthorization Act of 1986. (Pub. L. 99-499). The extremely hazardous substances and their TPQs are listed in 40 CFR § 355, Appendices A and B.</paragraph>
      </subsection>
      <subsection heading="22.00.01.03 Registration and Exemptions">
        <paragraph indent="2">The following schedule of reporting and planning requirements is hereby adopted, pursuant to the authority contained in Chapter 22, Montgomery County Fire Safety Code, of the Montgomery County Code, 1984, as amended.</paragraph>
        <paragraph indent="2">(a)   Registration. Regardless of exemption from federal reporting requirements under the federal EPCRA, the occupant of any facility which uses, processes, transfers, stores, or manufactures one or more hazardous substances and falls within one of the facility classifications below must annually register the facility with the Office of Emergency Management and Homeland Security.</paragraph>
        <paragraph indent="3">(1)   The Corporate Responsible Officer must register a regulated facility within 30 days of:</paragraph>
        <paragraph indent="4">(A)    meeting the registration requirement, regardless of facility classification; or</paragraph>
        <paragraph indent="4">(B)   any change in hazardous inventory which upgrades facility classification.</paragraph>
        <paragraph indent="3">(2)   The Corporate Responsible officer of a regulated facility must notify the Office of Emergency Management and Homeland Security within 90 days of any significant change in hazardous inventory which downgrades a facility classification.</paragraph>
        <paragraph indent="3">(3)   Facility registration is current for one year from the date of registration with the Office of Emergency Management and Homeland Security. However, if under 22.00.01.03(e)(4), the Office of Emergency Management and Homeland Security adjusts the annual registration date, facility registration will remain current until the assigned registration date.</paragraph>
        <paragraph indent="3">(4)   New facilities must register with the Office of Emergency Management and Homeland Security within 30 days from the date of issue of their occupancy certificate.</paragraph>
        <paragraph indent="3">(5)   The certificate of registration issued by the Administrator must be conspicuously displayed at the regulated facility.</paragraph>
        <paragraph indent="2">(b)   Classification of facilities. For the purpose of this regulation, all facilities which use, process, transfer, store, or manufacture hazardous substances or extremely hazardous substances are classified according to the following criteria:</paragraph>
        <paragraph indent="3">(1)   SARA Facility. Any facility subject to the reporting and planning requirements of EPCRA.</paragraph>
        <paragraph indent="3">(2)   High Use Facility. Any facility that has a hazardous inventory at any time during the year:</paragraph>
        <paragraph indent="4">(A)   Equal to or greater than 2000 pounds or 220
									 7   gallons aggregate quantity of hazardous substances, but less than the reporting requirements of EPCRA; or</paragraph>
        <paragraph indent="4">(B)   Equal to or greater than 10 pounds, of any single extremely hazardous substance as published in 40 CFR § 355 (but less than the TPQ for reporting as a SARA facility); or</paragraph>
        <paragraph indent="4">(C)   That includes Uninterruptible Power Supply (UPS) systems equal to or greater than 10 pounds, of any single extremely hazardous substance as published in 40 CFR § 355 (but less than the TPQ for reporting as a SARA facility) which utilizes Flooded Lead Acid Batteries. See Section III(b)(3)(E) for UPS systems utilizing Valve Regulated Lead Acid (VRLA) batteries where the electrolyte is suspended in either a gel or a fiberglass mat.</paragraph>
        <paragraph indent="3">(3)   General Use Facility. Any facility that has a hazardous inventory at any time during the year:</paragraph>
        <paragraph indent="4">(A)   Less than 2000 pounds or 220 gallons aggregate quantity of hazardous substances, but equal to or greater than 500 pounds or 55 gallons aggregate; or</paragraph>
        <paragraph indent="4">(B)   Greater than 2 pounds and less than 10 pounds (but less than the TPQ for reporting as a SARA facility) of any single extremely hazardous substance as published in 40 CFR § 355; or</paragraph>
        <paragraph indent="4">(C)   That Includes Uninterruptible Power Supply systems equal to or greater than 10 pounds, of any single extremely hazardous substance as published in 40 CFR § 355 (but less than the TPQ for reporting as a SARA facility) which utilizes Valve Regulated Lead Acid (VRLA) batteries where the electrolyte must be suspended in either a gel or a fiberglass-mat. See Section III(b)(2)(C) for UPS systems utilizing Flooded Lead Acid Batteries. A General Use Facility also includes:</paragraph>
        <paragraph indent="4">(D)   Facilities dispensing fuels to the general public from underground tanks, without vehicle servicing or repair capabilities are classified as General Use. Permanent above ground storage tanks installed in accordance with NFPA 30, “Flammable and Combustible Liquids Code”, and approved by the Assistant State Fire Marshal for Montgomery County, are classified as General Use.</paragraph>
        <paragraph indent="4">(E)    Laboratories, including but not limited to medical, school, research, and commercial facilities, under the direct supervision of a technically qualified individual, regardless of inventory requirements as stated elsewhere in this regulation, are classified as General Use, where inventory of:</paragraph>
        <paragraph indent="5">(1)   any single hazardous substance is equal to or greater than 5 pounds or 1 gallon, or</paragraph>
        <paragraph indent="5">(2)   any single extremely hazardous substance, as published in 40 CFR § 355, is greater than 1 pound.</paragraph>
        <paragraph indent="2">(4)   Light Use Facility. Any facility which has a hazardous inventory at any time during the year:</paragraph>
        <paragraph indent="4">(A)   Equal to or greater than 50 pounds or 5 gallons aggregate quantity of hazardous substances but less than the reporting threshold of a General Use Facility, or</paragraph>
        <paragraph indent="4">(B)   Equal to or greater than 1 pound, and less than 2 pounds of any single extremely hazardous substance as published in 40 CFR § 355 (but less than the TPQ for reporting as a SARA facility). A Light Use Facility also includes:</paragraph>
        <paragraph indent="4">(C)   Laboratories, including but not limited to medical, school, research, and commercial facilities, under the direct supervision of a technically qualified individual, are classified as Light Use, where any single extremely hazardous substance, as published in 40 CFR § 355, does not exceed 1 pound.</paragraph>
        <paragraph indent="2">(5)   Exempt Facility: The following facilities or substances are exempt for the purposes of this regulation:</paragraph>
        <paragraph indent="4">(A)   Privately held farms as defined as follows: a tract of land, with or without associated buildings, that is devoted to agriculture, i.e.,  is, the science or art of cultivating and managing the soil, growing and harvesting crops and other plants, forestry, horticulture, hydroponics, breeding or raising livestock, poultry, fish, game, and fur-bearing animals, dairying, beekeeping, and similar activities, but does not include cooperatives, nurseries, agricultural supply houses, and like commercial establishments.</paragraph>
        <paragraph indent="4">(B)   Any facility storing any prepackaged substance to the extent it is used in routine agriculture or any fertilizer prepackaged for household use and held for sale by a retailer to the ultimate consumer.</paragraph>
        <paragraph indent="4">(C)   Private domiciles 10 .</paragraph>
        <paragraph indent="4">(D)   Any facility owned, leased, or in space within a facility controlled by the federal  government or the State of Maryland. For the safety and welfare of emergency response personnel, it is highly recommended that exempt governmental facilities be encouraged to voluntarily provide the requested information, where security is not at issue.</paragraph>
        <paragraph indent="4">(E)   Any substance that is a food, food additive, color additive, drug, or cosmetic regulated by the Food and Drug Administration (FDA). With regard to food additives, a chemical is a food additive only when in use as a food additive, and not when it is stored or used for other purposes, or is being sold to another business for use as a food additive.</paragraph>
        <paragraph indent="4">(F)   Any substance present as a solid in any manufactured item to the extent exposure to that substance does not occur under normal conditions of use.</paragraph>
        <paragraph indent="4">(G)   Any substance to the extent it is used for normal personal, family, or household purposes, or is present in the same container and concentration and is labeled as a product for distribution and use for personal, family, or household purposes.</paragraph>
        <paragraph indent="2">(c)    Information requirements. The Corporate Responsible Officer is required to provide to the Office of Emergency Management and Homeland Security, on behalf of the LEPC, the following information at the time of registration, unless otherwise specified in this regulation:</paragraph>
        <paragraph indent="3">(1)   Business or corporation name. The legal corporate title of the regulated facility, the common name of the business, the name of the owner, and the employer identification number (federal tax number).</paragraph>
        <paragraph indent="3">(2)   Facility address. The actual address at which the regulated facility is located, including street numbers, street name, nearest cross-street, city, and zip code.</paragraph>
        <paragraph indent="3">(3)   Corporate responsible officer (CRO). The CRO is the primary contact for the Office of Emergency Management and Homeland Security during non- emergency communications with the facility. A contact address, if different from the facility address, daytime telephone number, evening telephone number, and official company title must be provided. The person appointed CRO must be clearly identified. Any change in the CRO must be forwarded to the Office of Emergency Management and Homeland Security within 30 days of the change.</paragraph>
        <paragraph indent="3">(4)   Facility Emergency Coordinator (FEC). The FEC is the primary contact for the Office of Emergency Management and Homeland Security during emergency communications with the facility. A contact address within the state, if different from the facility address, daytime telephone number, evening telephone number, and official company title must be provided. The person appointed FEC must be clearly identified. Any change in the FEC must be forwarded to the Office of Emergency Management and Homeland Security within 30 days of the change.</paragraph>
        <paragraph indent="3">(5)   Twenty-four hour emergency telephone number. This emergency phone number must provide direct contact on a 24 hour basis with the Facility Emergency Coordinator or  designee with specific knowledge of the hazards present.</paragraph>
        <paragraph indent="2">(6)   Hazardous Substances Inventory 9 . The listing and designation of quantities of hazardous substances must be arranged alphabetically by product name or chemical name in accordance with the requirements of 22.00.01.03(b). Where a product name does not exist, the substance must be listed by generic name 10 .</paragraph>
        <paragraph indent="2">(7)   Hazardous substance data location. The location of Material Safety Data Sheets (MSDS) or hazardous waste manifests within the facility must be provided. MSDS and hazardous waste disposal records must be kept in a location clearly identified, and easily accessible to emergency service personnel and employees.</paragraph>
        <paragraph indent="2">(8)   Emergency notifications. The Facility Emergency Coordinator must certify that the applicant has an emergency notification plan for employees, other occupants of the building, and the adjacent community, if an accidental release or spill occurs 11 .</paragraph>
        <paragraph indent="2">(9)   SIC. The Standard Industrial Code assigned by the United States Chamber of Commerce.</paragraph>
        <paragraph indent="2">(10)   Number of Employees. Number of full-time employees for the purpose of reporting under EPCRA.</paragraph>
        <paragraph indent="1">(d)   Supplemental requirements. Only those facilities classified as General Use Facilities, High Use Facilities, or SARA Facilities are required to submit supplemental information and diagrams under this section of the regulation. Filing requirements of this section of the regulation are intended to meet the reporting requirements for EPCRA facilities under federal regulations.</paragraph>
        <paragraph indent="3">(1)   Hazardous substance location. The room or specific location within the building or on the grounds must be identified along with the quantity of hazardous substances and extremely hazardous substances.</paragraph>
        <paragraph indent="4">(A)   For the purposes of this section, the most recently submitted Tier II reporting forms are acceptable. However, for each substance listed, a notation indicating the type and size of a typical container must be provided.</paragraph>
        <paragraph indent="4">(B)   If Tier II forms are not used to fulfill the requirements of this section, then an alphabetical listing of substances by product name or chemical name must be provided and include the chemical abstract service number, physical and health hazards, inventory amount, storage location, and typical container type and size.</paragraph>
        <paragraph indent="2">(2)   Facility diagram. An accurate, clear and legible facility diagram must be provided in 8 ½  inch by 11 inch format. Where necessary to maintain clarity, the diagram may be broken out onto several pages. The scale of the diagram must be provided. The diagram must indicate, at a minimum:</paragraph>
        <paragraph indent="3">(A)   The location of substances by name or storage code;</paragraph>
        <paragraph indent="3">(B)   Access and egress points;</paragraph>
        <paragraph indent="3">(C)   Automatic fire alarm and extinguishing systems, fire protection systems, or other control system locations and control rooms;</paragraph>
        <paragraph indent="3">(D)   Unusual facility hazards; and</paragraph>
        <paragraph indent="3">(E)   Immediate facility exposures (adjacent properties).</paragraph>
        <paragraph indent="2">(3)   A facility may request a waiver of part, or all of the supplemental information  requirements. The applicant must justify the need because of special security or safety requirements. The request for a waiver must be submitted in writing to OEMHS Manager. The request must include documentation on how this information would be made available to authorized County officials and emergency response personnel in both emergency and non-emergency situations.</paragraph>
        <paragraph indent="1">(e)   Application submittal and review.</paragraph>
        <paragraph indent="2">(1)   Application with accompanying appropriate fee must be submitted to the Office of Emergency Management and Homeland Security at the time of registration. Thereafter, application and appropriate fee must be submitted:</paragraph>
        <paragraph indent="3">(A)    Annually;</paragraph>
        <paragraph indent="3">(B)   As assigned; or</paragraph>
        <paragraph indent="3">(C)   With any change in hazardous inventory which would change the facility classification.</paragraph>
        <paragraph indent="2">(2)   The Office of Emergency Management and Homeland Security must review and give timely notice to the submitting facility of application acceptance, or request revision or clarification.</paragraph>
        <paragraph indent="3">(A)    Applications which are returned to the submitting facility must be accompanied by a statement indicating revisions or clarifications needed.</paragraph>
        <paragraph indent="3">(B)   Applications returned to a facility for revision or clarification must be resubmitted to the Office of Emergency Management and Homeland Security within 30 days of receipt by the facility.</paragraph>
        <paragraph indent="2">(3)   The time period for submitting an application under this regulation may be extended for cause at the discretion of the OEMHS Manager. Requests for an extension must be:</paragraph>
        <paragraph indent="3">(A)    Made on company letterhead or, where no letterhead exists, must be notarized by a certified notary public;</paragraph>
        <paragraph indent="3">(B)   Signed by the CRO; and</paragraph>
        <paragraph indent="3">(C)   Received in the Office of Emergency Management and Homeland Security no later than 14 days prior to the time for application submittal.</paragraph>
        <paragraph indent="3">(D)    If the extension is denied, the OEMHS Manager must provide written explanation to the CRO for such denial.</paragraph>
        <paragraph indent="2">(4)   The Office of Emergency Management and Homeland Security may schedule annual application submittal dates 12 .</paragraph>
        <paragraph indent="2">(5)   Where no significant changes in inventory or facility have occurred, a facility may meet annual application submittal requirements by certifying that the existing information on the renewal application is correct and accurate and that there are no changes, signing and dating where indicated, and submitting the appropriate fee.</paragraph>
      </subsection>
      <subsection heading="22.00.01.04 Fee Schedule">
        <paragraph indent="2">The following schedule and accompanying fees is hereby adopted, pursuant to the authority contained in Chapter 22, Montgomery County Fire Safety Code, of the Montgomery County Code, 1984 as amended. Fees included are for program administration, registration, application review, and inspection(s).</paragraph>
        <paragraph indent="2">(a)   Basic fees. Fees required by this section must be paid by the Corporate Responsible Officer on behalf of the regulated facility at the time of facility registration.</paragraph>
        <paragraph indent="3">(1)   Light Use Facility.</paragraph>
        <paragraph indent="4">(A)    Initial registration fee                $   175.00</paragraph>
        <paragraph indent="4">(B)      Annual registration fee          $   100.00</paragraph>
        <paragraph indent="4">(C)      Seasonal pools annual registration      $     50.00</paragraph>
        <paragraph indent="6">(open less than 120 consecutive days)</paragraph>
        <paragraph indent="4">(D)   Pools (open 120 days or more per year)      $   100.00</paragraph>
        <paragraph indent="3">(2)   General Use Facility.</paragraph>
        <paragraph indent="4">(A)    Initial registration fee               $   400.00</paragraph>
        <paragraph indent="4">(B)      Annual registration fee         $   250.00</paragraph>
        <paragraph indent="4">(C)      Seasonal pools annual registration      $   115.00</paragraph>
        <paragraph indent="6">(open less than 120 consecutive days)</paragraph>
        <paragraph indent="4">(D)   Pools (open 120 days or more per year)      $   250.00</paragraph>
        <paragraph indent="3">(3)   High Use Facility.</paragraph>
        <paragraph indent="4">(A)    Initial registration fee               $   800.00</paragraph>
        <paragraph indent="4">(B)      Annual registration fee         $   400.00</paragraph>
        <paragraph indent="4">(C)      Seasonal pools annual registration      $   185.00</paragraph>
        <paragraph indent="6">(open less than 120 consecutive days)</paragraph>
        <paragraph indent="4">(D)   Pools (open 120 days or more per year)      $   400.00</paragraph>
        <paragraph indent="3">(4)   SARA Facility.</paragraph>
        <paragraph indent="4">(A)    Initial registration fee               $1,500.00</paragraph>
        <paragraph indent="4">(B)      Annual registration fee         $1,000.00</paragraph>
        <paragraph indent="4">(C)      Seasonal pools annual registration      $   225.00</paragraph>
        <paragraph indent="6">(open less than 120 consecutive days)</paragraph>
        <paragraph indent="4">(D)   Pools (open 120 days or more per year)      $1,000.00</paragraph>
        <paragraph indent="2">(b)   Miscellaneous fees. Fees required by this section must be paid at the time of service.</paragraph>
        <paragraph indent="3">(1)   Application review resubmittals and revision.</paragraph>
        <paragraph indent="4">(A)    First resubmittal            included in original fee.</paragraph>
        <paragraph indent="4">(B)   Each subsequent resubmittal as shown below:</paragraph>
        <paragraph indent="5">Light use facility               $     50.00</paragraph>
        <paragraph indent="5">General use facility                $   100.00</paragraph>
        <paragraph indent="5">High use facility               $   150.00</paragraph>
        <paragraph indent="5">SARA facility                   $   200.00</paragraph>
        <paragraph indent="3">(2)   Consultation Fee: The fee for an appointment with the Hazmat Permitting Program Specialist is $100 per hour. This fee will not be broken into hourly increments. The number of minutes will round up to the next highest hour for fee. For example 15 minutes will be charged a 1 hour fee ($100.00) and 1 hour and 5 minutes will be charged a 2 hour fee ($200.00).</paragraph>
        <paragraph indent="3">(3)   Extensions. The fee for a granted extension is $50.00 if submitted within 30 days of the due date.  Each additional month is an additional $25.00, up to a maximum of the initial fee, per registration year.  Fees must accompany the request. Fees for a granted extension are not refundable and are not considered as partial payment of required registration fees.</paragraph>
        <paragraph indent="3">(4)   Upgrade in facility classification. When a facility is subject to the requirement of 19A.06.01.03(a)(1)(B), the balance of the initial registration fee for the new facility classification must be paid at the time the facility is registered under the new classification. However, if the upgrade in facility classification occurs within 90 days before the annual registration date, the balance of the initial registration fee for the new classification is waived until the annual registration date.</paragraph>
        <paragraph indent="3">(5)   Late Registration. A facility that fails to register as required under Section III(a)(1) or Section III(e)(1) will be subject to a late registration fee in addition to the basic fee, which must be paid at time of registration.</paragraph>
        <paragraph indent="4">(A)   30 days after the required filing date. . .   10% of the original filing fee in addition to the basic fee.</paragraph>
        <paragraph indent="4">(B)   60 days after the required filing date. . .   20% of the original filing fee in addition to the basic fee.</paragraph>
        <paragraph indent="4">(C)   90 days after the required filing date. . .   50% of the original filing fee in addition to the basic fee.</paragraph>
        <paragraph indent="4">(D)   180 days after the required filing date . . .    100% of the original filing fee in addition to the basic fee.</paragraph>
        <paragraph indent="2">(c)   Waiver.</paragraph>
        <paragraph indent="3">(1)   The OEMHS Manager or the OEMHS Manager’s designee may waive or reduce any fee required under this regulation if:</paragraph>
        <paragraph indent="4">(A)   Payment of the fee would cause the applicant undue hardship; or</paragraph>
        <paragraph indent="4">(B)   The fee is incurred because of circumstances beyond the applicant’s control (for example, severe weather); or</paragraph>
        <paragraph indent="4">(C)   It otherwise would be in the public interest to reduce or waive the fee.</paragraph>
        <paragraph indent="3">(2)   The OEMHS Manager’s decision regarding any reduction or waiver of a fee is final.</paragraph>
      </subsection>
      <subsection heading="22.00.01.05 Enforcement">
        <paragraph indent="2">The following rights of entry and penalties are established for the purposes of ensuring community and emergency responder safety, and compliance with this regulation.</paragraph>
        <paragraph indent="2">(a)   Right of Entry. Pursuant to the authority contained in Title 40 of the Code of Federal Regulations, Part 370.25(d), and Section 22-7 of the Montgomery County Fire Safety Code, the following persons, after designation by the Fire Administrator, have right of entry to conduct facility familiarization and pre-emergency planning inspections, or compliance inspections, or both. The right of entry is concomitant with registering a facility with the Office of Emergency Management and Homeland Security.</paragraph>
        <paragraph indent="3">(1)   The officers and official representatives of the Fire and Rescue Departments.</paragraph>
        <paragraph indent="3">(2)   The officers and official representatives of the Montgomery County Hazardous Incident Response Team.</paragraph>
        <paragraph indent="3">(3)   The officers and official representatives of the Montgomery County Fire and Rescue Service and Division of Volunteer Fire and Rescue Services.</paragraph>
        <paragraph indent="3">(4)   The official representatives of the Montgomery County Department of Environmental Protection.</paragraph>
        <paragraph indent="2">(b)   Timing of inspections. A routine inspection conducted under this regulation must be made during normal business hours at the discretion of the inspecting official. However, no advance notice of the inspection is required.</paragraph>
        <paragraph indent="2">(c)   Violations and penalties. Pursuant to the authority contained in Sections 1-19 and 1-20 of the Montgomery County Code, the following penalties are established. Each day a violation continues constitutes a separate offense. Violations of this regulation are subject to criminal and/or civil penalties. Violations and penalties contained in this regulation are in addition to any other violations and penalties that may apply under county, state, or federal laws.</paragraph>
        <paragraph indent="3">(1)   Registration/Planning/Denial of Entry.  Any violation of this regulation is a Class A violation as set out in the Montgomery County Code. Repeat violations or violations of any of the following may result in revocation of the certificate of registration for a period of one year, at the discretion of the Fire Administrator.</paragraph>
        <paragraph indent="4">(A)    Failure to register a facility</paragraph>
        <paragraph indent="4">(B)   Falsely registering a facility</paragraph>
        <paragraph indent="4">(C)   Failure to provide a plan</paragraph>
        <paragraph indent="4">(D)    Misstatements or omissions in a plan or application</paragraph>
        <paragraph indent="4">(E)   Denying entry to authorized official</paragraph>
        <paragraph indent="2">(d)   Right to Hearing</paragraph>
        <paragraph indent="3">(1)   Any Corporate Responsible Officer or regulated person aggrieved by a decision of the Fire Administrator or Fire Administrator's designee made under these regulations may appeal to a separate hearing officer appointed by the Administrator, who after hearing upon notice has the authority to affirm, modify or reverse the decision made.</paragraph>
        <paragraph indent="3">(2)   A decision of the hearing officer may be appealed to the County Board of Appeals or, to a municipal Board of Appeals. The Appeals Board has the authority to affirm, modify or reverse the decision of the hearing officer.</paragraph>
        <paragraph indent="3">(3)   Any appeal from the decision of the Fire Administrator, Fire Administrator's designee or hearing officer must be made within 10 business days of receipt of official notice of the decision.</paragraph>
        <paragraph indent="3">(4)   Any decision of the County Board of Appeals or municipal Board of Appeals may be appealed to a court of competent jurisdiction.</paragraph>
      </subsection>
      <subsection heading="22.00.01.06 Severability">
        <paragraph indent="2">If a court holds that any part of this regulation is invalid, such invalidity does not affect the remaining sections of this regulation.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.00.02 Regulations Adopting and Amending Certain Standards of the National Fire Code Regarding Fire Protection Systems">
    <regulation heading="COMCOR 22.00.02 Regulations Adopting and Amending Certain Standards of the National Fire Code Regarding Fire Protection Systems">
      <subsection heading="22.00.02.01">
        <paragraph indent="2">In accordance with the procedures authorized in Chapter 22, "Fire Safety Code", of the Montgomery County Code, 1996, this Executive Regulation applies to the design, installation, and maintenance of fire protection systems in buildings or structures.  Where there are differences between this regulation and the Montgomery County Building Code, the more restrictive provision(s) will apply.</paragraph>
        <paragraph indent="2">In this regulation the term “Fire Chief” means the Fire Chief of the Montgomery County Fire and Rescue Service and includes the Fire Chief’s designees.</paragraph>
      </subsection>
      <subsection heading="22.00.02.02">
        <paragraph indent="2">All references to the National Fire Codes and standards adopted in these regulations are to those codes, standards, recommended practices, and manuals in the National Fire Codes, published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.  Unless otherwise noted, all references to those codes and standards published in the 2003 edition of National Fire Protection Association’s Uniform Fire Code (NFPA 1) are adopted in their entirety.</paragraph>
        <paragraph indent="2">The Fire Chief must review these regulations and propose amendments within six months after the date the State Fire Prevention Commission adopts new amendments to NFPA 1 and NFPA 101 into the State Fire Prevention Code.</paragraph>
      </subsection>
      <subsection heading="22.00.02.03 Fire Protection System Permit">
        <paragraph indent="1">A permit must be obtained from the Fire Chief to operate any fire protection system in any building or other structure, except one and two family dwellings.</paragraph>
        <paragraph indent="2">(a)   Fire protection system means any fire alarm device or system, or suppression device or system, which is designated and installed to:</paragraph>
        <paragraph indent="3">1.   detect, control, or extinguish a fire;</paragraph>
        <paragraph indent="3">2.   alert occupants or the fire department, or both, that a fire has occurred; or</paragraph>
        <paragraph indent="3">3.   be used by fire and rescue personnel on scene to aid in suppressing a fire.</paragraph>
        <paragraph indent="2">(b)   Fire protection systems must be inspected and approved at time of installation and annually thereafter. The Fire Chief must issue a permit upon approval of the system.</paragraph>
        <paragraph indent="2">(c)   A fire protection systems permit must be obtained prior to installation of any kitchen cooking equipment suppression system.</paragraph>
      </subsection>
      <subsection heading="22.00.02.04Fire Protection SystemLicense">
        <paragraph indent="2">A contractor or person responsible for the installation, modification, service, or third-party inspection of any fire protection system or any portion thereof in Montgomery County, must obtain and carry on their person a license from the Fire Chief subject to the following criteria:</paragraph>
        <paragraph indent="2">(a)   Qualifications required.</paragraph>
        <paragraph indent="3">(1)   Residential license (13D and 13R sprinkler systems): National Institute for Certification of Engineering Technologies (NICET) Level II Certification, Registered Professional Engineer Certification, or other nationally recognized certification as approved by the Fire Chief.</paragraph>
        <paragraph indent="3">(2)   General license (all other fire protection systems):  National Institute for Certification of Engineering Technologies (NICET) Level III Certification, Registered Professional Engineer Certification, or other nationally recognized certification as approved by the Fire Chief.</paragraph>
        <paragraph indent="2">(b)   When required by the system manufacturer for systems other than sprinkler systems, proof of training for installing or maintaining particular system types.</paragraph>
        <paragraph indent="2">(c)   Proof of financial stability.</paragraph>
        <paragraph indent="2">(d)   Demonstrated competency in Montgomery County requirements.</paragraph>
        <paragraph indent="2">(e)   Licenses will be subject to annual renewal.</paragraph>
        <paragraph indent="2">(f)   The Fire Chief may rescind these licenses for cause.</paragraph>
      </subsection>
      <subsection heading="22.00.02.05 Maintenance of Residential Sprinkler Systems">
        <paragraph indent="2">All leases must have the following provision: “Sprinkler System. In units equipped with fire sprinkler systems, no portion of the system may be changed or altered except by a licensed, certified sprinkler installer.  Sprinkler heads must not be painted, covered, obstructed, or any item hung from them.  Prior to any alteration of the sprinkler system or any changes, additions, or removal of partitions, or walls, plans must be submitted to the Department of Permitting Services”.</paragraph>
      </subsection>
      <subsection heading="22.00.02.06">
        <paragraph indent="1">Smoke Control System shop drawing submittals must include:</paragraph>
        <paragraph indent="2">(a)   Plans and specifications</paragraph>
        <paragraph indent="2">(b)   Engineering calculations and/or computer model</paragraph>
        <paragraph indent="2">(c)   Floor plans</paragraph>
        <paragraph indent="2">(d)   System diagrams and details</paragraph>
        <paragraph indent="2">(e)   Sequence of operations and control layout</paragraph>
        <paragraph indent="2">(f)   Preliminary test procedures</paragraph>
        <paragraph indent="2">(g)   Acceptance test procedures</paragraph>
        <paragraph indent="2">(h)   Pass/fail criteria</paragraph>
      </subsection>
      <subsection heading="22.00.02.07">
        <paragraph indent="2">NFPA 12A, add: Halon systems shall not be installed as required protection in accordance with the state and/or local building or fire codes due to the environmental impact of discharge testing, the lack of adequate alternative test methods, and availability of alternative agents such as carbon dioxide.</paragraph>
      </subsection>
      <subsection heading="22.00.02.08">
        <paragraph indent="2">NFPA 13, paragraph 8.1.1, add new paragraph (7) as follows:</paragraph>
        <paragraph indent="3">(7)   Sprinklers are required in attached balconies or porches unless at least 50 percent of the longest exterior side is open to the atmosphere.</paragraph>
      </subsection>
      <subsection heading="22.00.02.09">
        <paragraph indent="2">NFPA 13, paragraph 8.4.5.1, add: Listed residential sprinkler heads must be used in dwelling units except Detention and Correctional occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.02.10">
        <paragraph indent="2">NFPA 13, paragraph 8.14.7.5, add: Sprinklers are not required under noncombustible or limited exterior canopies over drive up windows.  Any canopy with the potential for extended vehicle standing or parking below shall have sprinkler protection on the underside of the canopy.</paragraph>
      </subsection>
      <subsection heading="22.00.02.11">
        <paragraph indent="2">NFPA 13, paragraph 8.14.10.3 (protection of electrical equipment rooms) is deleted.</paragraph>
      </subsection>
      <subsection heading="22.00.02.12">
        <paragraph indent="2">NFPA 13, paragraph 8.14.19.1 is amended as follows: In new installations expected to supply sprinklers below a ceiling and in any speculative areas subject to tenant changes, minimum one inch sprinkler outlets must be provided.</paragraph>
      </subsection>
      <subsection heading="22.00.02.13">
        <paragraph indent="2">NFPA 13, paragraph 8.14.19.2 is amended as follows: after the word “bushings” delete everything and replace with “for hydrostatic testing only, and must be removed prior to the occupancy of the space.”</paragraph>
      </subsection>
      <subsection heading="22.00.02.14">
        <paragraph indent="2">NFPA 13, paragraphs 8.15.1.1.1 and 8.16.1.1, add: When a sprinkler system serves more than one level, each level must be consistently and separately valved by a listed and approved control valve.  In addition, where a sprinkler system is required to activate a local building fire alarm system, the sprinkler system must have a separate and distinct water flow detecting device for each floor and zone.</paragraph>
        <paragraph indent="2">Exception 1:   In buildings not exceeding three floors and 3000 square feet per floor.</paragraph>
        <paragraph indent="2">Exception 2:   Unoccupied and unused attics may be zoned with the level below.</paragraph>
        <paragraph indent="2">Exception 3:   Mezzanines not exceeding 3000 square feet in area.</paragraph>
        <paragraph indent="2">Exception 4:     Detention and correctional facilities.</paragraph>
      </subsection>
      <subsection heading="22.00.02.15">
        <paragraph indent="2">NFPA 13, paragraph 8.16.2, add the following requirements for fire department connections:</paragraph>
        <paragraph indent="2">(a)   Must be located within 100 feet from a free standing (not wall type) hydrant, and between 18 and 48 inches from grade to the centerline of the inlets.</paragraph>
        <paragraph indent="2">(b)   Number of 2 ½  in. inlets:</paragraph>
        <paragraph indent="3">System Demand (gpm)         No. of Inlets</paragraph>
        <paragraph indent="3">up to 749                  2</paragraph>
        <paragraph indent="3">750-999                  3</paragraph>
        <paragraph indent="3">1000 and above               4</paragraph>
        <paragraph indent="2">(c)   Multiple connections for the same building shall be interconnected.</paragraph>
        <paragraph indent="2">(d)   When a section of a building is fed by a connection (i.e., partial systems), permanent all weather identification signs shall be provided on connections.</paragraph>
        <paragraph indent="2">(e)   Must be sized at least as large as the main sprinkler system riser pipe or the fire pump discharge line, whichever is larger.</paragraph>
      </subsection>
      <subsection heading="22.00.02.16">
        <paragraph indent="2">NFPA 13, paragraph 11.1, add:  Calculations for new systems or new portions of systems must meet the criteria below.</paragraph>
        <paragraph indent="2">(a)   Highest hazard and most demanding use allowed by building construction permit or property zoning.</paragraph>
        <paragraph indent="2">(b)   Storage use: Available storage height for high storage of a class 4 non-encapsulated material.</paragraph>
        <paragraph indent="2">(c)   Laboratory use: ordinary group 2 for class A, B, or C labs.</paragraph>
        <paragraph indent="2">(d)   All uses: 20% safety factor. For systems without a pump, this is based on the demand pressure only at the supply point. For systems with a pump, this is based on both the demand pressure and demand flow at the pump discharge.  All design options, except grids, must be explored.</paragraph>
        <paragraph indent="0">Exception to safety factor only: Owner occupied buildings may use a lower safety factor if a pump would be necessary to achieve the 20%.</paragraph>
      </subsection>
      <subsection heading="22.00.02.17">
        <paragraph indent="2">NFPA 13, paragraph 11.2.3.5.1, add: The number of design sprinklers shall be at least 5 under ceilings which are not flat, smooth and level unless specifically listed for a four sprinkler design area.</paragraph>
      </subsection>
      <subsection heading="22.00.02.18">
        <paragraph indent="2">NFPA 13, paragraph 15.1.2, add: Pressure and flow availability as determined by a public utility shall be used for new taps.  Pressure and flow availability for existing taps shall be determined by an interior flow test. In any case, the supply information shall be corrected for the low hydraulic gradient.  Booster pumps and pump/tank supplies shall only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.02.19">
        <paragraph indent="2">NFPA 13D, paragraph 1.1, add: This standard also applies to Day care homes containing 12 clients or less if located within converted one and two family dwellings or townhouses.</paragraph>
      </subsection>
      <subsection heading="22.00.02.20">
        <paragraph indent="2">NFPA 13D, add new paragraph:</paragraph>
        <paragraph indent="1">5.1.4   Where a dedicated sprinkler booster pump is provided the following conditions must be met:</paragraph>
        <paragraph indent="3">(1)   Pumps shall not sit directly on the floor.</paragraph>
        <paragraph indent="5">(2)   Pumps shall be powered from the house electrical service by a nominal 220-240 circuit as required by Montgomery County Electrical Code.</paragraph>
        <paragraph indent="5">(3)   Power at the pump shall be supervised passively by motor disconnect within sight that also controls a lighting circuit for other than a stair or pump room.</paragraph>
        <paragraph indent="5">(4)   Sprinkler system shall be connected to a bathroom toilet to create a passive purge system.</paragraph>
        <paragraph indent="5">(5)   Pump shall be connected to a time delay relay (run timer).</paragraph>
      </subsection>
      <subsection heading="22.00.02.21">
        <paragraph indent="2">NFPA 13D, paragraph 6.1, add: Pressure and flow availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may only be used where it is demonstrated that the public water supply is inadequate as determined by the director of the Department of Permitting Services.</paragraph>
      </subsection>
      <subsection heading="22.00.02.22">
        <paragraph indent="2">NFPA 13D, paragraph 6.2: Add section (5) Well pumps</paragraph>
        <paragraph indent="1">(5)   A well pump shall have sufficient capacity and pressure to meet the sprinkler system demand.  The stored water capacity of sections 6.1.2 and 6.1.3 shall be permitted to be a combination of the water in the well (including the refill rate) plus the water in the holding tank if such tank can supply the sprinkler system.</paragraph>
      </subsection>
      <subsection heading="22.00.02.23">
        <paragraph indent="2">NFPA 13D, add new paragraph:</paragraph>
        <paragraph indent="3">6.2.1   Where a water storage tank(s) is provided the following conditions shall be met:</paragraph>
        <paragraph indent="5">(1)   Tank shall be provided with an automatic filling valve (float valve or equivalent).</paragraph>
        <paragraph indent="5">(2)   A method of seeing the water level in the tank shall be provided without having to open the tank.</paragraph>
      </subsection>
      <subsection heading="22.00.02.24">
        <paragraph indent="2">NFPA 13D, paragraph 6.2 (4), add new sentence: “A valve must be provided for routine testing of the pump.”</paragraph>
      </subsection>
      <subsection heading="22.00.02.25">
        <paragraph indent="2">NFPA 13D, 7.1.2, delete “the” in the beginning and add “fed by a tank” after piping.</paragraph>
      </subsection>
      <subsection heading="22.00.02.26">
        <paragraph indent="2">NFPA 13D, section 7.5.5.1, add: Where possible to maintain listed coverage, sprinkler heads shall be positioned so as to eliminate the need to install sprinkler heads of a higher temperature rating.</paragraph>
      </subsection>
      <subsection heading="22.00.02.27">
        <paragraph indent="2">NFPA 13D, paragraph 7.5.5, add new paragraph 7.5.5.4:</paragraph>
        <paragraph indent="3">7.5.5.4   Dry type sprinklers shall be used in areas which are not heated to at least 40 degrees F.</paragraph>
      </subsection>
      <subsection heading="22.00.02.28">
        <paragraph indent="2">NFPA 13D, paragraph 8.1.2, add: The number of design sprinklers shall be at least three under ceilings which are not flat, smooth, and level, unless specifically listed with a two sprinkler design area.</paragraph>
      </subsection>
      <subsection heading="22.00.02.29">
        <paragraph indent="2">NFPA 13D, paragraph 8.2.4 is amended as follows:</paragraph>
        <paragraph indent="2">Obstructions:</paragraph>
        <paragraph indent="2">(a)   Sprinklers shall be positioned so that response time and discharge are not adversely affected by features such as sloped ceilings, beams, lights, and fan motors.</paragraph>
        <paragraph indent="2">(b)   Unprotected bulkheads or soffits behind the spray of sidewall sprinklers shall not exceed 8 inches in width.</paragraph>
        <paragraph indent="2">(c)   Sprinkler heads in closets shall not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.02.30">
        <paragraph indent="2">NFPA 13D, paragraph 8., add: All calculations shall include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.02.31">
        <paragraph indent="2">NFPA 13D, paragraph 8.6.4, add the following after garages: “...unless located partially or wholly beneath living space.”</paragraph>
      </subsection>
      <subsection heading="22.00.02.32">
        <paragraph indent="2">NFPA 13R, paragraph 6.5.3, add: Pressure and volume availability as determined by a public utility shall be used and shall be adjusted to the low hydraulic gradient. Booster pumps and pump/tank supplies may only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.02.33">
        <paragraph indent="2">NFPA 13R, paragraph 6.6.4.1 is replaced to read: In all apartment buildings, a single 2 ½ in. fire department connection with a feed line sized at least as large as the main system riser shall be provided when the system has 20 or more sprinklers.  The fire department connection shall be located on a street front and be 18 to 48 inches from the centerline of the inlet to finish grade.  Paragraph 6.6.4.2 is deleted.</paragraph>
      </subsection>
      <subsection heading="22.00.02.34">
        <paragraph indent="2">NFPA 13R, paragraph 6.7.1.2, add: The number of design sprinklers shall be at least five under ceilings which are not flat, smooth and level unless specifically listed with a four sprinkler design area.</paragraph>
      </subsection>
      <subsection heading="22.00.02.35">
        <paragraph indent="2">NFPA 13R, paragraph 6.7.1.5.3 is amended as follows:</paragraph>
        <paragraph indent="2">Obstructions:</paragraph>
        <paragraph indent="2">(a)   Sprinklers shall be positioned so that response time and discharge are not adversely affected by features such as sloped ceilings, beams, lights, and fan motors.</paragraph>
        <paragraph indent="2">(b)   Unprotected bulkheads or soffits behind the spray of side wall sprinklers shall not exceed 8 inches in width.</paragraph>
        <paragraph indent="2">(c)   Sprinkler heads in closets must not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.02.36">
        <paragraph indent="2">NFPA 13R, paragraph 6.7.4, add: All calculations must include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.02.37">
        <paragraph indent="2">NFPA 14, paragraph 4.7.2 is amended as follows: Each fire hose valve shall be provided with</paragraph>
        <paragraph indent="0">2 ½  in. valved hose connections, 2 ½  in. to 1 ½  in. reducers, caps, and chains.</paragraph>
      </subsection>
      <subsection heading="22.00.02.38">
        <paragraph indent="2">NFPA 14, paragraph 5.1.2, add:</paragraph>
        <paragraph indent="2">(1)   Systems shall be automatic wet type.</paragraph>
        <paragraph indent="2">(2)   Standpipe systems in unheated areas shall be automatic dry type.</paragraph>
        <paragraph indent="2">(3)   Standpipe systems in detached open parking garages may be the manual dry type, if the piping is air supervised for breaks or open valves.</paragraph>
        <paragraph indent="2">(4)   Occupant use hose is prohibited in new or existing buildings.</paragraph>
        <paragraph indent="2">(5)   New standpipe systems shall be Class 1 only.</paragraph>
      </subsection>
      <subsection heading="22.00.02.39">
        <paragraph indent="2">NFPA 14, paragraph 6.3 (Fire Department Connections), add:</paragraph>
        <paragraph indent="2">(1)   Shall be located within 100 feet from a free standing (not wall type) hydrant.</paragraph>
        <paragraph indent="2">(2)   Number of 2 ½  in. inlets:</paragraph>
        <paragraph indent="3">System Demand (gpm)      No. of Inlets</paragraph>
        <paragraph indent="3">up to 749            2</paragraph>
        <paragraph indent="3">750-999            3</paragraph>
        <paragraph indent="3">1,000 and above         4</paragraph>
        <paragraph indent="2">(3)   Multiple connections on the same building shall be interconnected.</paragraph>
        <paragraph indent="2">(4)   When a section of a building is fed by a connection (i.e., partial systems), permanent all weather identification signs shall be provided on connections.</paragraph>
      </subsection>
      <subsection heading="22.00.02.40">
        <paragraph indent="2">NFPA 14, paragraph 7.3.2.3, add:</paragraph>
        <paragraph indent="2">(1)   Measurement shall be parallel or at right angles to walls.</paragraph>
        <paragraph indent="2">(2)   Supplemental hose valves outside the stairs shall not be located within tenant spaces, unless hose reach requirements cannot be met by placement of valves in public corridors or by use of wall hydrants for spaces opening to the exterior. Hose valve locations shall be marked by the placement of signs, the striping of columns, or other approved methods.</paragraph>
      </subsection>
      <subsection heading="22.00.02.41">
        <paragraph indent="2">NFPA 14, paragraph 7.8.1.1, add exceptions:</paragraph>
        <paragraph indent="2">Exception No. 1:   In high-rise buildings, where booster pumps are necessary to produce the required residual pressures, pumps and piping systems must be sized to provide for the demand of the hydraulically most remote hose station, or the sprinkler system demand, whichever is greater. The standpipe system must also be sized to provide the required flow and pressure for all hose stations required to be flowing, when supplied by 150 psi at 1000 gpm at the fire department connection(s). Two sets of calculations will, therefore, be required under this exception.</paragraph>
        <paragraph indent="2">Exception No. 2:   Systems in buildings that are not high rise, and dry systems with no automatic water supply, may be sized to obtain the required flows and pressures, when supplied by 150 psi at 1000 gpm at the fire department connection(s).</paragraph>
        <paragraph indent="2">Exception No. 3:   In existing buildings, after shell occupancy, hose valves added to correct reach violations created by tenant modifications may be supplied by 3 inch pipe without recalculation.</paragraph>
      </subsection>
      <subsection heading="22.00.02.42">
        <paragraph indent="2">NFPA 20, paragraph 5.14.6.4, add a new sentence: Eccentric reducers must be installed with the flat side on the bottom when fed directly from above.</paragraph>
      </subsection>
      <subsection heading="22.00.02.43">
        <paragraph indent="2">NFPA 20, paragraph 5.18.1.2, add: A relief valve may be installed to reduce operating pressure below 175 psi at high gradient.</paragraph>
      </subsection>
      <subsection heading="22.00.02.44">
        <paragraph indent="2">NFPA 20, paragraph 5.18.7 is amended entirely to state: Relief valves shall not be piped back into the source of the supply.</paragraph>
      </subsection>
      <subsection heading="22.00.02.45">
        <paragraph indent="2">NFPA 72, paragraph 4.4.6.1, add the following sentence: An annunciator with the following features is required when the building is greater than one story, over 20,000 square feet in area per floor, or has more than one type of alarm initiating device.</paragraph>
        <paragraph indent="2">Exception No. 1:   Apartments protected by a 13R sprinkler system.</paragraph>
        <paragraph indent="2">Exception No. 2:   Any building not exceeding two stories above grade and 3,000 square feet per floor.</paragraph>
        <paragraph indent="2">(a)   Annunciator shall have a visible signal for each different floor, zone, and device type. Supervised computer screen or printer type annunciators may be used to meet this requirement if the zone identification is approved by the Fire Chief.</paragraph>
        <paragraph indent="2">(b)   Zones shall not exceed a single floor, 20,000 square feet, or 300 linear feet. Sprinkler systems may be zoned in accordance with the applicable sprinkler standard.</paragraph>
        <paragraph indent="2">(c)   If two or more zones per floor are required, a graphic outline on or adjacent to the annunciator shall be provided showing the building outline, zone boundaries, "you are here" notation, north compass arrow, all stairways, stairway identification numbers, all standpipe risers, elevators, and the building address.</paragraph>
        <paragraph indent="2">(d)   A lamp type annunciator shall have a lamp test switch unless the annunciator circuits are supervised.</paragraph>
        <paragraph indent="2">(e)   The annunciator shall be located at, and visible from, the main fire department entrance.</paragraph>
        <paragraph indent="2">(f)   If two or more buildings are controlled by one alarm system, an annunciator shall be installed in each building with a pilot lamp indicating the building of alarm origination.</paragraph>
      </subsection>
      <subsection heading="22.00.02.46">
        <paragraph indent="2">NFPA 72, add new paragraph 5.7.3.2.5:</paragraph>
        <paragraph indent="1">5.7.3.2.5   Detectors which activate required extinguishing systems on a cross-zoned or multiple-zone basis shall be spaced at a maximum of one-half of their allowed or listed square footage spacing.</paragraph>
      </subsection>
      <subsection heading="22.00.02.47">
        <paragraph indent="2">NFPA 72, paragraph 5.7.4.2.2, add: Activation of duct smoke detectors must sound an audible alarm in a normally occupied area or through the building fire alarm system, and must be identified as duct detector trouble.  If connected to the building alarm, the signal must be supervisory only and must not initiate the building evacuation alarm unless a confirmation or verification feature is provided to minimize unwanted alarms.</paragraph>
      </subsection>
      <subsection heading="22.00.02.48">
        <paragraph indent="2">NFPA 72, paragraph 5.7.1.7 is amended as follows: Detectors located at the top of shafts and stairs must be on a supervisory circuit only unless a confirmation or verification feature is provided to minimize unwanted alarms. The location must be identified at the annunciator or fire alarm control panel.</paragraph>
      </subsection>
      <subsection heading="22.00.02.49">
        <paragraph indent="2">NFPA 72, paragraph 5.10.2, add: Standpipe or main water flow indicators, if provided, must sound a supervisory signal only.</paragraph>
      </subsection>
      <subsection heading="22.00.02.50">
        <paragraph indent="2">NFPA 72, the second sentence under paragraph 5.12.4 is changed to read "The center of each station must be between 42 and 48 inches above the floor level." Also, this paragraph shall be amended by the addition of the following: Approved "911" instruction signs shall be permanently affixed and maintained at each manual fire alarm station, unless the fire alarm is monitored by a UL listed central station.</paragraph>
      </subsection>
      <subsection heading="22.00.02.51">
        <paragraph indent="2">NFPA 72, paragraph 6.9.9.14 is amended as follows: At least six handsets shall be provided in the fire control room.</paragraph>
      </subsection>
      <subsection heading="22.00.02.52">
        <paragraph indent="2">NFPA 72, paragraphs 11.5.1.1, 11.5.2.1, and 11.5.4.1: delete the exception for each section.</paragraph>
      </subsection>
      <subsection heading="22.00.02.53">
        <paragraph indent="2">NFPA 72, paragraph 11.5.6.1 (4) is deleted.</paragraph>
      </subsection>
      <subsection heading="22.00.02.54">
        <paragraph indent="2">NFPA 72, paragraph 11.5.8.1 (2), delete the exception.</paragraph>
      </subsection>
      <subsection heading="22.00.02.55">
        <paragraph indent="2">NFPA 72, paragraph 11.5.12.1 (2), delete the exception.</paragraph>
      </subsection>
      <subsection heading="22.00.02.56">
        <paragraph indent="2">NFPA 72, paragraph 11.8.3.5, add new paragraphs (10) and (11):</paragraph>
        <paragraph indent="2">(10)   Separate entrances to sleeping rooms shall be protected separately unless the door leads only to a bathroom or clothes/linen closet.</paragraph>
        <paragraph indent="2">(11)   Enclosed rooms such as dens, libraries, studies, or sitting rooms which could be used as a temporary sleeping area shall be treated as bedrooms.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.00.03 Schedule of Fees for Fire Safety Code Permits, Code Modifications, Inspections and Licenses">
    <regulation heading="COMCOR 22.00.03 Schedule of Fees for Fire Safety Code Permits, Code Modifications, Inspections and Licenses">
      <subsection heading="22.00.03.01 Statement of Purpose">
        <paragraph indent="0">The following fire prevention maintenance inspections, permits and license fees are adopted pursuant to the authority contained in Chapter 22, Fire Safety Code, of the Montgomery County Code as amended. Fees are for inspections, permits, licenses, and code modifications as specified in the Fire Safety Code and regulations adopted by Montgomery County, Department of Permitting Services.</paragraph>
      </subsection>
      <subsection heading="22.00.03.02 General Provisions">
        <paragraph indent="0">The following provisions apply to all types of permits, licenses and certificates:</paragraph>
        <paragraph indent="0">a.   Display.  All required permits and certificates must be readily accessible upon request when not displayed.</paragraph>
        <paragraph indent="0">b.   Fee Payment.  All fees required by this regulation must be paid before the issuance of the permit, license, certificate, or code modification.</paragraph>
        <paragraph indent="0">c.   Government Activities.  All activities of municipal, county, and state government requiring a permit, license, certificate, exception, inspection or testing must conform to the Maryland State Fire Prevention Code and Montgomery County Fire Safety Code and will be charged the applicable fees except where specifically exempted by law. Applicable fees will be charged to the permit, license, certificate, or exception holder.</paragraph>
        <paragraph indent="0">d.   Refund.  All fees are non-refundable, except in the case of an administrative error.</paragraph>
        <paragraph indent="0">e.   Transfer.  Permits and Permit fees are not transferable.</paragraph>
      </subsection>
      <subsection heading="22.00.03.03Definitions">
        <paragraph indent="0">a.   Fire Code Compliance Permit:  A permit to ensure that any business, school, multi-family residential building, health care facility, place of worship, and other commercial building complies with the applicable fire safety codes.</paragraph>
        <paragraph indent="0">b.   Operational Permit:  A Permit to ensure that each active and passive Fire Protection System complies with the applicable fire safety codes in any business, school, multi-family building, health care facility, place of worship, or other commercial building or occupancy.</paragraph>
        <paragraph indent="0">c.   General Permit:  A permit for particular operations, special events, blasting, including items listed under 22.00.03.05 of this document.</paragraph>
        <paragraph indent="0">d.   Multi-Family Residential Garden Style Apartment Building Complex means more than one building where each building:</paragraph>
        <paragraph indent="1">1.   consists of three or more dwellings;</paragraph>
        <paragraph indent="1">2.   does not exceed three stories above grade plane; and</paragraph>
        <paragraph indent="1">3.   is located on one lot, parcel, or ownership unit.</paragraph>
      </subsection>
      <subsection heading="22.00.03.04 Fire Code Compliance and Operational Permits, Terms and Fees">
        <paragraph indent="0">a.   Systems and Structures Maintenance – All code required fire protection systems and features must be operational and maintained in good working order at all times and must be inspected or tested by an authorized individual or agency in compliance with the Montgomery County Fire Safety Code and applicable NFPA standards.</paragraph>
        <paragraph indent="1">1.   The building owner or representative, occupant, or a Montgomery County licensed fire protection contractor must submit inspection, maintenance, and testing report documents and data in compliance required by the Montgomery County Fire Safety Code and NFPA code requirements to the Department of Permitting Services, Division of Fire Prevention and Code Compliance.</paragraph>
        <paragraph indent="1">2.   The building owner or occupant or both must maintain the documents and data required in paragraph 1 of this subsection for the previous two years and have the documents and data readily available on site.</paragraph>
        <paragraph indent="1">3.   Failure to submit the documents and data required under paragraph 1 of this subsection, or the failure to maintain the required records, may result in an order to conduct an annual test of the fire protection systems and features witnessed by the Montgomery County Fire Marshal.</paragraph>
        <paragraph indent="0">b.   Non-compliance. All reported or discovered deficiencies or impairments, or any failures to provide the documentation and data required under subsection a.1, may result in a Notice of Violation being issued to the responsible party.</paragraph>
        <paragraph indent="0">c.   Fire Code Compliance Permits. A Fire Code Compliance Permit must be renewed annually and in accordance with 22.00.03.04
									(f) of this document.</paragraph>
        <paragraph indent="0">d.   Operational Permits. An Operational Permit must be renewed annually and in accordance with 22.00.03.04
									(f) of this document.</paragraph>
        <paragraph indent="0">e.   Fire Code Compliance Permits and Operational Permits are valid for one calendar year from the date of issuance and must indicate an expiration date.</paragraph>
        <paragraph indent="0">f.   Fire Code Compliance Permits and Operational Permits must be renewed immediately when any of the following occur:</paragraph>
        <paragraph indent="1">1.   The Use and Occupancy for the building or tenant space issued by the Department of Permitting Services is changed,</paragraph>
        <paragraph indent="1">2.   The owner of the building or tenant changes.</paragraph>
        <paragraph indent="0">g.   Fees.</paragraph>
        <paragraph indent="0">h.   A cancellation within 24 hours before a scheduled inspection will be counted as an inspection.</paragraph>
        <paragraph indent="0">i.   Witnessed Tests of Systems or Structures   $95</paragraph>
      </subsection>
      <subsection heading="22.00.03.05General Permits, Terms, and Fees">
        <paragraph indent="0">Fees for the following items are $95 except as noted. An inspection may be required at the discretion of the Fire Marshal before a permit is issued. For additional Inspections required post event (Example Fireworks), an additional fee will be charged as a reinspection fee.</paragraph>
        <paragraph indent="1">a.   Amusement and entertainment</paragraph>
        <paragraph indent="2">1.   To conduct or operate any scary (haunted) house, crop maze, carnival, fair, exhibit, trade show, concert, or other public event that presents an unusual life safety or fire hazard. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="2">2.   To conduct or operate any fireworks shoot. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="2">3.   To use any flame effects before an audience. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="1">b.   Flammable and combustible liquids and gases</paragraph>
        <paragraph indent="2">1.   To install, remove, abandon, repair or alter a stationary tank for storing flammable or combustible liquids, dispensing devices, or associated piping. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="2">2.   To place any flammable or combustible liquid stationary tank temporarily or permanently out of service. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="2">3.   To conduct floor resurfacing and refinishing operations involving the use and application of flammable liquids or materials. Permit Term – 30 calendar days.</paragraph>
        <paragraph indent="2">4.   For spraying or dipping operations utilizing more than one gallon of flammable or combustible liquids on any working day. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">5.   For the operation of a bulk storage plant and/or for storage and dispensing of any formulation of natural gases or liquefied petroleum gases. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="1">c.   Flammable and combustible solids</paragraph>
        <paragraph indent="2">1.   To store or handle more than 100 cubic feet of combustible fibers. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">2.   To conduct or maintain any tire recapping or rebuilding plant. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">3.   To store more than 100,000 board feet of lumber. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">4.   To use explosives (for blasting permit) per month, $95. Permit Term – not to exceed 12 calendar months.</paragraph>
        <paragraph indent="2">5.   To operate any commercial rubbish-handling facility or site. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="1">d.   Hot Work</paragraph>
        <paragraph indent="2">1.   To conduct any cutting or welding operations except those activities contained in a fabrication shop. Permit Term – Site specific, 12 calendar months.</paragraph>
        <paragraph indent="2">2.   To use an open flame torch for the application of roofing materials or stripping of paint. Permit Term – Site specific, 30 calendar days.</paragraph>
        <paragraph indent="2">3.   To place and operate a tar kettle. Permit Term – Site specific, 30 calendar days.</paragraph>
        <paragraph indent="1">e.   Motor vehicles</paragraph>
        <paragraph indent="2">1.   To use any building, shed, or enclosure as a place of business for the purpose of repairing or refurbishing any motor vehicle, including aircraft. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">2.   To operate any motor vehicle wrecking yard. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="2">3.   To operate any motor vehicle refueling facility, including aircraft. Permit Term – 12 calendar months.</paragraph>
        <paragraph indent="1">f.   To review Fire Department Access and/or Fire hydrant location. Site Specific.</paragraph>
        <paragraph indent="1">g.   Miscellaneous Permits.</paragraph>
        <paragraph indent="2">1.   To operate any commercial establishment or conduct any process or activity that poses an unusual fire or life safety risk not otherwise covered in this regulation is $95. Permit Term – 12 calendar months, or until a change in ownership or use group.</paragraph>
        <paragraph indent="2">2.   The fee for any inspection associated with the issuance of a permit is included in the permit fee.</paragraph>
        <paragraph indent="2">3.   The fee for any other Permit required by the Fire Marshal, or identified in other reference documents or in NFPA 1 is $95. Permit Term – 12 calendar months, or as noted on permit.</paragraph>
      </subsection>
      <subsection heading="22.00.03.06License Fees">
        <paragraph indent="0">a.   Fire protection systems and equipment</paragraph>
        <paragraph indent="1">1.   Fire Extinguisher Corporate License – For a firm to engage in the business of servicing portable fire extinguishers. $88. License Term – 12 calendar months.</paragraph>
        <paragraph indent="1">2.   Corporate License – For a firm to engage in the business of repairing, servicing or inspecting, maintaining and testing any fixed fire protection system or structural fire protection element or feature. $88. License Term – 12 calendar months.</paragraph>
        <paragraph indent="1">3.   Individual License – To install, repair, service, inspect, maintain, or test any fixed fire protection system, structural fire protection element or feature, or portable fire extinguishers. $88. License Term – 12 calendar months.</paragraph>
        <paragraph indent="0">b.   Fire Safety Permits (Licensing Inspections)</paragraph>
        <paragraph indent="0">1. | Family or Group Day Care home. | $95
2. | Nursery or Day Care Centers. | $95
3. | Board &amp; Care (Group Home). | $95
4. | Assisted Living or Nursing Home. | $95
5. | Health Care, Detention. | $95
6. | Other Licensed Facility. | $95
7. | Private Educational Institutions. | $95</paragraph>
      </subsection>
      <subsection heading="22.00.03.07 Miscellaneous Fees">
        <paragraph indent="0">a.   Additional Inspection fees:</paragraph>
        <paragraph indent="0">1. | Initial inspection of work or event site or property required before permit issuance | $95
2. | When a post event inspection is required | $95
3. | Each re-inspection fee after two disapprovals | $95</paragraph>
      </subsection>
      <subsection heading="22.00.03.08 Indexing of Fees to Labor and Operating Cost Changes and to Manage Reserves">
        <paragraph indent="0">The Director of Permitting Services must calculate an enterprise fund stabilization factor (EFSF) each year to be applied to each fee set in or under this regulation on July 1 of each year. The EFSF is the factor by which the fee calculation is adjusted, up or down, to cover DPS labor and operating costs and to manage the DPS reserve policy under the 2002 Principles of the Fiscal Management of the Permitting Services Fund. The Director must publish the EFSF for each upcoming fiscal year not later than March 15 of the current fiscal year. For any year in which the EFSF will be less than .80 or greater than 1.20, the Department must review its fee rates and functional analysis behind the fee rates to determine if changes need to be made to the fee rates.</paragraph>
      </subsection>
      <subsection heading="22.00.03.09 Severability">
        <paragraph indent="0">The provisions of these regulations are severable. If a court of competent jurisdiction holds that a provision is invalid or inapplicable, the remainder of the regulation remains in effect.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.00.04 Regulation Adopting and Amending Certain Editions of the National Fire Codes Regarding Building Construction and Protective Features">
    <regulation heading="COMCOR 22.00.04 Regulation Adopting and Amending Certain Editions of the National Fire Codes Regarding Building Construction and Protective Features">
      <subsection heading="22.00.04.01">
        <paragraph indent="2">In accordance with the procedures authorized in Chapter 22, “Fire Safety Code,” of the Montgomery County Code, 1996, this Executive Regulation applies to the safeguarding of life, property, and the public welfare from the hazards of fire and explosion arising from the improper storage, handling, or use of substances, materials, or devices and from conditions hazardous to life, property, and the public welfare in the use or occupancy of buildings, structures, sheds, tents, lots or premises.</paragraph>
        <paragraph indent="2">In this regulation the term “Fire Chief” means the Fire Chief of the Montgomery County Fire and Rescue Service and includes the Fire Chief’s designees.</paragraph>
      </subsection>
      <subsection heading="22.00.04.02">
        <paragraph indent="2">Unless otherwise noted, all references to the National Fire Codes and Standards adopted in these regulations are to those codes, standards, recommended practices and manuals in the National Fire Codes, published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269. The references to these National Fire Codes and Standards are set forth in Section 22-14 of the Montgomery County Code, 1996.</paragraph>
      </subsection>
      <subsection heading="22.00.04.03 Standards Adopted">
        <paragraph indent="2">a.   The following standards published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269, are incorporated in these regulations except as expressly amended. The dates or editions of the individual codes and standards are as listed in this section.</paragraph>
        <paragraph indent="2">NFPA NO.      CODE OR STANDARD</paragraph>
        <paragraph indent="2">1         Uniform Fire Code 2003</paragraph>
        <paragraph indent="2">42         Code for the Storage of Pyroxylin Plastic (2002)</paragraph>
        <paragraph indent="2">NFPA NO.      CODE OR STANDARD</paragraph>
        <paragraph indent="2">50A         Standard for Gaseous Hydrogen Systems at Consumer Sites (1999)</paragraph>
        <paragraph indent="2">92A         Recommended Practice for Smoke Control Systems (2000)</paragraph>
        <paragraph indent="2">92B         Guide for Smoke Management Systems in Malls, Atria, and Large Areas (2002)</paragraph>
        <paragraph indent="2">101         Code for Safety to Life from Fire in Buildings and Structures (2003)</paragraph>
        <paragraph indent="2">105         Recommended Practice for the Installation of Smoke-Control Door Assemblies (2003)</paragraph>
        <paragraph indent="2">130         Standard for Fixed Guideway Transit Systems (2000)</paragraph>
        <paragraph indent="2">170         Standard for Fire Safety Symbols (2002)</paragraph>
        <paragraph indent="2">214         Water Cooling Towers (2000)</paragraph>
        <paragraph indent="2">720         Recommended Practices for the Installation of Household Carbon Monoxide (CO) Warning Equipment (1998)</paragraph>
        <paragraph indent="2">850         Electric Generating Plants (2000)</paragraph>
        <paragraph indent="2">b.   The Fire Chief must review this regulation and propose amendments within six months after the date the State Fire Prevention Commission adopts new amendments to NFPA 1 and NFPA 101 into the State Fire Prevention Code.</paragraph>
      </subsection>
      <subsection heading="22.00.04.04">
        <paragraph indent="2">NFPA No. 1, Section 10.12.1, add new subsection 10.12.1.1 as follows:</paragraph>
        <paragraph indent="2">10.12.1.1   All occupancies other than 1 and 2 family dwellings shall provide an approved access box.</paragraph>
        <paragraph indent="3">Exception 1:   The requirement for an access box shall not apply when the occupancy provides 24-hour on-site staffing with access to all areas in the building or complex.  At least one person must staff a fixed location proximate to the main building or complex entrance to provide ready access for the fire department.</paragraph>
        <paragraph indent="3">Exception 2:   For multiple occupancies located within a single structure, a single access box shall be permitted with approval of the Fire Chief.</paragraph>
        <paragraph indent="3">Exception 3:   For multiple structures within a residential building complex, a single access box shall be permitted with approval of the Fire Chief.</paragraph>
        <paragraph indent="3">Exception 4:   The size, contents, and location of the access box shall be determined by the Fire Chief in cooperation with the occupancy owner or management.</paragraph>
      </subsection>
      <subsection heading="22.00.04.05">
        <paragraph indent="2">NFPA 1, Section 13.3.2.22, add new subsection 13.3.2.22.2 and renumber the existing subsection as 13.3.2.33.2.  New subsection 13.3.2.22.2 reads:</paragraph>
        <paragraph indent="2">13.3.2.22.2   The requirement of 13.3.2.22.3, that existing high-rise buildings shall be protected throughout by an approved automatic sprinkler system, shall not apply until a separate specific high-rise regulation takes effect that requires protection of existing buildings through an approved, supervised, engineered life-safety system as defined by NFPA 101 Section 31.3.5.10.3 (2003 edition) and includes timetables and conditions for compliance and incentives.</paragraph>
      </subsection>
      <subsection heading="22.00.04.06">
        <paragraph indent="2">NFPA No. 30A, as referenced by NFPA 1, in subsections 7.3.6.1 and 7.3.6.3, add the following Exception:</paragraph>
        <paragraph indent="1">Exception:   In buildings protected throughout with “approved” automatic sprinkler protection, separation must consist of such assemblies having a fire resistance rating of not less than one (1) hour with all openings therein provided with approved minimum twenty (20) minute fire resistance rated opening protectives.</paragraph>
      </subsection>
      <subsection heading="22.00.04.07">
        <paragraph indent="1">NFPA No. 80, as referenced by NFPA 1, subsection 1-10.1, add the following: Release of fire doors and shutters shall not be by fusible link and shall be accomplished by one or more of the following:</paragraph>
        <paragraph indent="2">(a)   Approved local smoke detection at the doors,</paragraph>
        <paragraph indent="2">(b)   Approved area smoke detection per NFPA 72, or</paragraph>
        <paragraph indent="2">(c)   Full automatic sprinkler protection per NFPA 13 with water flow interlock.</paragraph>
      </subsection>
      <subsection heading="22.00.04.08">
        <paragraph indent="1">NFPA No. 96, as referenced by NFPA 1, subsection 1.1.1, add an Exception to read:</paragraph>
        <paragraph indent="1">Exception:   In day care and business occupancies doing food warming only, Home Economics classrooms in schools, and lodging or rooming houses or small board and care in existing structures originally built for single family residential use, protection shall consist of one of the following:</paragraph>
        <paragraph indent="4">(1)   A listed and approved recirculating residential ventilation hood with range top extinguishing system installed in accordance with the manufacturer’s instructions, or</paragraph>
        <paragraph indent="4">(2)   In a building equipped with approved full automatic sprinkler protection, the sprinkler system is considered to provide surface fire protection.  Exhaust from residential range tops shall not leave the room where the range top is located.</paragraph>
      </subsection>
      <subsection heading="22.00.04.09">
        <paragraph indent="2">NFPA 101 is amended by deleting the following reference: NFPA 5000 Building Construction and Safety Code.  Wherever NFPA 5000 is referenced, substitute the building code that is in effect in Montgomery County.</paragraph>
      </subsection>
      <subsection heading="22.00.04.10">
        <paragraph indent="2">NFPA 101 is amended by the addition of new subsection 1.4.4 to read as follows:</paragraph>
        <paragraph indent="1">The use of NFPA 101A to justify equivalency concepts is not permitted in new construction.</paragraph>
      </subsection>
      <subsection heading="22.00.04.11">
        <paragraph indent="2">NFPA 10, section 3.3 is amended as follows:</paragraph>
        <paragraph indent="3">(a)   Subsection 3.3.47, add the following new subsection and definition:</paragraph>
        <paragraph indent="4">3.3.47.3   Bulkhead Door.  A type of door assembly covering an opening in the ground providing direct access to a basement, the floor of which is not more than 8 feet below ground level.  The door consists of a single rigid leaf or two overlapping rigid leaves or covers which need to be pushed or lifted upwards in order to be opened.  A person, after opening the door, can walk up a series of steps to escape to the outside.</paragraph>
        <paragraph indent="3">(b)   Amend Subsection 3.3.110.1 to change the definition of “Day-Care Home” by deleting the phrase “...more than three, but...”</paragraph>
        <paragraph indent="3">(c)   Amend Subsection 3.3.152.4 to change the definition of “Day-Care Occupancy” by deleting the phrase “...four or more...”</paragraph>
        <paragraph indent="3">(d)   Amend Subsections 3.3.152.13 to change the definition of “Residential Board and Care Occupancy” by changing “A building or portion thereof...” to “A building or portion thereof that does not qualify as a one- and two-family dwelling...”</paragraph>
      </subsection>
      <subsection heading="22.00.04.12">
        <paragraph indent="2">NFPA 101, section 4.8, add the following subsection:</paragraph>
        <paragraph indent="3">4.8.2.4   Emergency plans shall be maintained in a location approved by the Fire Chief.</paragraph>
      </subsection>
      <subsection heading="22.00.04.13">
        <paragraph indent="2">Amend NFPA 101, subsection 6.1.4.1 by deleting the phrase “...four or more...”</paragraph>
      </subsection>
      <subsection heading="22.00.04.14">
        <paragraph indent="2">Amend NFPA 101, subsection 6.1.9.1 to change the definition of “Residential Board and Care Occupancy” by changing “A building or portion thereof...” to “A building or portion thereof that does not qualify as a one- and two-family dwelling...”</paragraph>
      </subsection>
      <subsection heading="22.00.04.15">
        <paragraph indent="2">NFPA 101, subsection 7.2.1.5.7.1, add an item (6), to read:</paragraph>
        <paragraph indent="3">(6)   Entry levels shall provide free access to an approved second exit.  These levels shall be designated in “core/shell” building permit drawings with future tenant layouts arranged accordingly.</paragraph>
      </subsection>
      <subsection heading="22.00.04.16">
        <paragraph indent="2">NFPA 101, delete subsections 7.2.3.9.2(3)(b), and 12.2.2.2.4.</paragraph>
      </subsection>
      <subsection heading="22.00.04.17">
        <paragraph indent="2">NFPA 101, subsection 7.3.1.2, add on the chart for Business Use “for calculating occupant loads in shell use business use is 6.0 square meters or 65 square feet per person.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.18">
        <paragraph indent="2">NFPA 101, subsection 7.5.1.3.1, add new subsection 7.5.1.3.1.1:</paragraph>
        <paragraph indent="3">7.5.1.3.1.1   In non-sprinklered new buildings, parallel paths of travel shall be considered remote if not less than forty (40) feet apart, or separated by assemblies having continuous one hour fire resistance with self-closing and positive latching twenty (20) minute fire resistance rated opening protectives.  In fully sprinklered buildings and existing buildings paths of travel shall be considered remote if not less than thirty (30) feet apart, or separated by assemblies with self-closing opening protectives which are resistant to the passage of smoke.  This minimum separation of paths shall not supersede minimum separation of exits or doors in 7.5.1.3.2.</paragraph>
      </subsection>
      <subsection heading="22.00.04.19">
        <paragraph indent="2">NFPA 101, Subsection 7.9.1.2, replace the word “only” in the first sentence with “but not limited to,”.</paragraph>
      </subsection>
      <subsection heading="22.00.04.20">
        <paragraph indent="2">NFPA 101, subsection 7.10.8.3.2, add: If the sign is on the door, then the door must be equipped with an approved self-closing device.</paragraph>
      </subsection>
      <subsection heading="22.00.04.21">
        <paragraph indent="2">NFPA 101, subsection 7.12.1, add 7.12.1(4):</paragraph>
        <paragraph indent="3">(4)   In special purpose industrial occupancies, spaces not subject to human occupancy because of the presence of machinery or equipment shall be permitted with 100% of the exits discharging through a level of exit discharge.</paragraph>
      </subsection>
      <subsection heading="22.00.04.22">
        <paragraph indent="2">NFPA 101, subsection 8.6.6(3), add a second sentence: Buildings, wherein the communicating space(s) is (are) provided with automatic smoke detection and alarm in accordance with NFPA 72, will be considered to satisfy the requirements of ‘readily obvious’.</paragraph>
      </subsection>
      <subsection heading="22.00.04.23">
        <paragraph indent="2">NFPA 101, subsection 8.6.7(6)(b) is fully changed to read: Manual controls that are located at the annunciator panel or in the Fire Control Room.</paragraph>
      </subsection>
      <subsection heading="22.00.04.24">
        <paragraph indent="2">NFPA 101, add new section 9.1.5:</paragraph>
        <paragraph indent="3">9.1.5   All newly constructed below ground floors of a building, all floors in buildings greater than 25,000 ft2 per floor, and all floors of buildings greater than 3 stories in height of Type I and II construction shall meet minimum emergency radio communication system performance criteria adopted by Montgomery County.  Proof that minimum performance criteria are met shall be provided in writing to the Fire Chief.</paragraph>
        <paragraph indent="5">(1)   System performance testing shall be performed in accordance with technical standards for systems and testing personnel established by Montgomery County.</paragraph>
        <paragraph indent="5">(2)   Compliance testing must be performed at time of occupancy and annually thereafter.</paragraph>
        <paragraph indent="5">(3)   Field testing may be performed upon reasonable notification of the owner or occupant by any authorized fire and rescue personnel.</paragraph>
        <paragraph indent="5">Exception:   The requirements of this section shall not apply to areas within an individual dwelling unit.</paragraph>
      </subsection>
      <subsection heading="22.00.04.25">
        <paragraph indent="2">NFPA 101, subsections 9.6.1.7 and 9.7.6.1, add: When a property owner or the owner’s agent cannot be contacted to establish a fire watch, the Montgomery County Fire and Rescue Service at their discretion may provide the fire watch and charge the property owner the inspection overtime rate per person per hour.</paragraph>
      </subsection>
      <subsection heading="22.00.04.26">
        <paragraph indent="2">NFPA 101, subsection 9.6.2.5, add two new subsections:</paragraph>
        <paragraph indent="2">(a)   9.6.2.5.1 Zoned fire alarm systems shall have manual pull stations located at the entrance to each exit enclosure and at the main exit.</paragraph>
        <paragraph indent="2">(b)   9.6.2.5.2 When a fire alarm system is required in a multiple tenant building, for each tenant exiting directly to the exterior of the building, a manual pull station and approved occupant notification shall be located at each required or marked exit.</paragraph>
      </subsection>
      <subsection heading="22.00.04.27">
        <paragraph indent="2">NFPA 101, subsections 9.6.2.8 and 9.6.2.9, add the following sentence:</paragraph>
        <paragraph indent="1">“Environments not suitable for smoke detectors (due to high probability of unwanted alarms) must be provided with listed rate-of-rise or rate compensated heat detection, or approved alternative means of detection.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.28">
        <paragraph indent="2">NFPA 101, subsection 9.6.2.10.2, add the phrase “and have secondary battery back-up power” at the end of the sentence.</paragraph>
      </subsection>
      <subsection heading="22.00.04.29">
        <paragraph indent="2">NFPA 101 add new subsections 9.6.2.12, 24.3.4.4, 26.3.3.6, 28.3.4.6, 30.3.4.6, 32.2.3.4.4 and 32.3.3.4.9: In new construction a carbon monoxide alarm or detector(s) installed in accordance with Chapter 5, Section 5.1, “Recommended Protection”, of NFPA 720, shall be installed in any family living unit containing a fuel-burning appliance, fireplace, or having an attached garage.</paragraph>
      </subsection>
      <subsection heading="22.00.04.30">
        <paragraph indent="2">NFPA 101, subsection 9.6.3.2.1, delete the word “lobby”.</paragraph>
      </subsection>
      <subsection heading="22.00.04.31">
        <paragraph indent="2">NFPA 101, subsection 9.6.3.4, add text at the end of the sentence: “only when the initial fire alarm signal is automatically transmitted without delay to a listed central station in accordance with 9.6.4.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.32">
        <paragraph indent="2">NFPA 101, subsection 9.6.3.7, add a second sentence to read: “Required audibility must be met with any and all intervening doors (between any space and the audible devices) closed.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.33">
        <paragraph indent="2">NFPA 101, subsection 9.6.3.9, add: Where voice type occupant notification is used, automatic pre-recorded messages must be used complying with Section 9.6.  Live voice as the sole notification method is prohibited.</paragraph>
        <paragraph indent="3">Exception:   Previously “approved” live voice systems, shall be permitted to remain.</paragraph>
      </subsection>
      <subsection heading="22.00.04.34">
        <paragraph indent="2">NFPA 101, subsection 9.6.4.2, delete all text following the word “automatically” in the second section, and replace with “to a listed central station.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.35">
        <paragraph indent="2">NFPA 101, delete subsection 9.6.4.3.</paragraph>
      </subsection>
      <subsection heading="22.00.04.36">
        <paragraph indent="2">NFPA 101, subsection 9.6.5.2(3), add the following sentence: “Manual fire alarm initiation must not activate floor or zone-dependent smoke control systems.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.37">
        <paragraph indent="2">NFPA 101, subsection 9.7.1.2, the second sentence is amended to read: “The sprinkler piping must be valved with the domestic water system.  Any and all work must be performed by a licensed sprinkler contractor.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.38">
        <paragraph indent="2">NFPA 101, subsection 9.7.2.2 is amended to read: “Where supervised automatic sprinkler protection is required by another section of this Code, waterflow alarms must be automatically transmitted to a listed central station.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.39">
        <paragraph indent="2">NFPA 101, subsection 9.7.3.1 is amended to read: “Where water as an extinguishing agent is not compatible with the fire hazard or is prohibited by law, statute or ordinance, the affected area shall be equipped with an approved automatic fire suppression system utilizing a suppression agent that is compatible with the fire hazard.  Such system shall be installed in accordance with the appropriate standard as determined in Table 9.7.3.1.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.40">
        <paragraph indent="2">NFPA 101, subsection 11.8.3.1, add new subsection 11.8.3.1.1:</paragraph>
        <paragraph indent="3">11.8.3.1.1   In buildings having staged evacuation the voice fire alarm system shall send a predetermined message to the floor where the alarm originated, to the floor immediately below and to the floor immediately above, providing information and direction to the occupants.  Any subsequent alarm(s) on other than the initial fire floor must initiate the voice fire alarm as described above.  The voice fire alarm shall be designated to be heard clearly by all occupants within the designated portions thereof as required by Section 9.6, but it shall not sound automatically in elevator cars and enclosed exit stairways.  Communicating levels shall be considered one floor/fire area for the audible and visual fire alarm signals.</paragraph>
      </subsection>
      <subsection heading="22.00.04.41">
        <paragraph indent="2">NFPA 101, subsections 11.8.5(6) and (8), are amended/added, as applicable, to read as follows:</paragraph>
        <paragraph indent="3">(6)   Emergency generator status indicators, and remote starting.</paragraph>
        <paragraph indent="3">(8)   Fire pump status indicators and remote starting only.</paragraph>
      </subsection>
      <subsection heading="22.00.04.42">
        <paragraph indent="2">NFPA 101, subsections 12.2.5.4.1(1), 12.2.5.4.1(2), 13.2.5.4.1(1), and 13.2.5.4.1(2) change “1000" to “250".</paragraph>
      </subsection>
      <subsection heading="22.00.04.43">
        <paragraph indent="2">NFPA 101, section 12.3.5, add new subsection 12.3.5.1 and renumber the existing subsections 12.3.5.1 through 12.3.5.3.  New subsection 12.3.5.1 reads: The following assembly occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7:</paragraph>
        <paragraph indent="3">(1)   Bars</paragraph>
        <paragraph indent="3">(2)   Dance Halls</paragraph>
        <paragraph indent="3">(3)   Discotheques</paragraph>
        <paragraph indent="3">(4)   Nightclubs</paragraph>
        <paragraph indent="3">(5)   Assembly occupancies with festival seating</paragraph>
      </subsection>
      <subsection heading="22.00.04.44">
        <paragraph indent="2">NFPA 101, add new subsection 12.3.5.2 to read: All new Assembly Occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.  Sprinkler protection is not required over recreation areas devoid of fuel loading (such as over pool water surface, ice rink ice surface or a court of noncombustible construction), if provided with draftstopping around the area of omission, in accordance with NFPA 13.</paragraph>
      </subsection>
      <subsection heading="22.00.04.45">
        <paragraph indent="2">NFPA 101, subsections 12.7.6.3 and 13.7.6.3, add:</paragraph>
        <paragraph indent="3">(1)   It is the duty of the individual in charge to call the attention of those present, immediately before the beginning of the proceedings for which the people are assembled, to the number and location of the exits, and to state that the doors to all exits are unlocked.  Before making the announcement, it is the duty of the individual to make an actual inspection to verify that the doors are unlocked and the means of egress are free of obstructions, and to correct any deficiencies found.</paragraph>
        <paragraph indent="3">(2)   It is the duty of the individual in charge to call the attention of everyone present at the proceedings to the exits by displaying or announcing the following:  “Notice.  For your own safety, look for your nearest exit. In case of emergency, walk, do not run, to that exit”.</paragraph>
        <paragraph indent="3">(3)   The requirements for calling the attention of everyone present at the proceedings to the exits is complied with by one of the following methods:</paragraph>
        <paragraph indent="4">(a)   Oral announcements of the notices in this section at the beginning of the proceedings.</paragraph>
        <paragraph indent="4">(b)   Showing the notices in this Section on the viewing screen where the motion pictures are shown.</paragraph>
        <paragraph indent="4">(c)   Printing the notices in this section in bold type letters not less than ¼ inch in height on the back of programs for the proceedings.  Nothing but the notice shall be placed on the back of the program.</paragraph>
        <paragraph indent="4">(d)   Having a fixed sign or signs displaying the notices in this section printed in letters of a size and clearness that can be easily read from each point in the assembly room.</paragraph>
      </subsection>
      <subsection heading="22.00.04.46">
        <paragraph indent="2">NFPA 101, section 13.3.5, add new subsection 13.3.5.1 and renumber the existing subsections 13.3.5.1 through 13.3.5.3.  New subsection 13.3.5.1 reads: Where occupant load exceeds 100, the following assembly occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7:</paragraph>
        <paragraph indent="3">(1)   Bars</paragraph>
        <paragraph indent="3">(2)   Dance Halls</paragraph>
        <paragraph indent="3">(3)   Discotheques</paragraph>
        <paragraph indent="3">(4)   Nightclubs</paragraph>
        <paragraph indent="3">(5)   Assembly occupancies with festival seating</paragraph>
      </subsection>
      <subsection heading="22.00.04.47">
        <paragraph indent="2">NFPA 101, new section 13.3.5.2 is changed to read: Any existing assembly occupancy and required exits with an occupant load of 100 or more shall be protected by an approved automatic sprinkler system in accordance with Section 9.7.  This requirement shall not apply to assembly occupancies used only for worship with fixed seating and not part of a mixed occupancy (see 6.1.14.3).</paragraph>
      </subsection>
      <subsection heading="22.00.04.48">
        <paragraph indent="2">NFPA 101, subsection 14.2.11.1.1(1) is amended by adding the following after “...tools”, “keys, special knowledge, or excessive force.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.49">
        <paragraph indent="2">NFPA 101, sections 16.1 and 17.1, add new subsections 16.1.1.6 and 17.1.1.6: Day-care centers providing day care for school age children before and after school hours in a building which is in use as a public or private school are not required to meet the provisions of this chapter, but shall meet the provisions for educational occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.04.50">
        <paragraph indent="2">NFPA 101, subsections 16.2.11.1.1(1), 16.2.11.1.1(3), 17.2.11.1.1(3), 17.2.11.1.1(1), 24.2.2.3(3), 32.2.2.3.1(3), and 33.2.2.3.1(3), add the following exception:</paragraph>
        <paragraph indent="2">Exception:   A minimum net clear opening of 5.0 square feet shall be permitted for secondary means of escape at grade.</paragraph>
      </subsection>
      <subsection heading="22.00.04.51">
        <paragraph indent="2">NFPA 101, subsection 16.3.4.5, add the following exceptions:</paragraph>
        <paragraph indent="3">Exception 1:   Day-care occupancies located in school facilities where enrollment is limited to children kindergarten age and older and capable of self preservation, where no sleeping facilities are provided and the school is provided with approved full automatic sprinkler protection.</paragraph>
        <paragraph indent="3">Exception 2:   In buildings equipped with a selective fire alarm system, smoke detection at stairwell doors shall only be required at locations that would activate the alarm in the day-care center.</paragraph>
      </subsection>
      <subsection heading="22.00.04.52">
        <paragraph indent="2">NFPA 101, add new subsection 16.3.5.4 to read: Buildings containing new day care centers above or below the level(s) of exit discharge must be protected with full automatic sprinkler protection installed in accordance with section 9.7.</paragraph>
      </subsection>
      <subsection heading="22.00.04.53">
        <paragraph indent="2">NFPA 101, subsections 16.6.1.1.2, and 17.6.1.1.2, delete the phrase “...more than 3, but...”</paragraph>
      </subsection>
      <subsection heading="22.00.04.54">
        <paragraph indent="2">NFPA 101, subsections 16.6.1.4.1(A) and (B) and 17.6.1.4.1(A) and (B) are amended as follows:</paragraph>
        <paragraph indent="3">(a)   Subsections 16.6.1.4.1(A) and 17.6.1.4.1 (A), delete “more than three but”, change “seven clients” to “nine clients”, change “six clients” to “eight clients”, and add a new sentence: “Where more than two clients, up to a maximum of four clients incapable of self-preservation are being cared for, a minimum of two staff personnel must be present at all times.”</paragraph>
        <paragraph indent="3">(b)   Subsections 16.6.1.4.1(B) and 17.6.1.4.1(B), change “at least seven” to “at least nine”, and change “no more than three clients” to “no more than four clients.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.55">
        <paragraph indent="2">NFPA 101, subsections 16.6.1.7.1 and 17.6.1.7.1, delete the existing wording and replace with the following:</paragraph>
        <paragraph indent="2">In family day-care homes, a day-care provider’s own children under the age of two years shall be counted as clients served and the following shall apply:</paragraph>
        <paragraph indent="3">(1)   At any given time, a day-care provider shall not care for more than eight clients, of whom no more than four may be under the age of two years.</paragraph>
        <paragraph indent="3">(2)   An adult to child ratio of at least one adult to every two children under the age of two years shall be maintained at all times.</paragraph>
      </subsection>
      <subsection heading="22.00.04.56">
        <paragraph indent="2">NFPA 101, subsection 16.6.2.1 and 17.6.2.1, add the following sentence: “Bulkhead doors shall not be permitted to serve as a primary means of escape.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.57">
        <paragraph indent="2">NFPA 101, subsections 16.6.2.2 (Reserved) and 17.6.2.2 (Reserved) are amended as follows:</paragraph>
        <paragraph indent="2">SLIDING DOOR.</paragraph>
        <paragraph indent="3">For family day-care homes, a sliding door used as a required means of egress shall comply with the following conditions:</paragraph>
        <paragraph indent="3">a.   The sliding door shall have not more than one, easily operated, locking device that does not require special knowledge, effort, or tools to operate;</paragraph>
        <paragraph indent="3">b.   There may not be draperies, screens, or storm doors that could impede egress;</paragraph>
        <paragraph indent="3">c.   The sill or track height may not exceed ½ inch above the interior finish floor;</paragraph>
        <paragraph indent="3">d.   The surface onto which exit is made shall be an all weather surface such as a deck, patio, sidewalk, etc.;</paragraph>
        <paragraph indent="3">e.   The floor level outside the door may be one step lower than the inside, but not more than 8 inches lower;</paragraph>
        <paragraph indent="3">f.   The sliding door shall open to a clear open width of at least 28 inches;</paragraph>
        <paragraph indent="3">g.   Before day dare use, each day the sliding door shall be unlocked and tested to the full required width to be sure it is operating properly, and the door shall be nonbinding and slide easily.</paragraph>
        <paragraph indent="3">h.   During periods of snow or freezing rain, door tracks shall be cleared out and the door opened periodically throughout the day in order to ensure proper operation.</paragraph>
      </subsection>
      <subsection heading="22.00.04.58">
        <paragraph indent="2">NFPA 101, subsections 16.6.2.3 (Reserved) and 17.6.2.3 (Reserved) are amended as follows:</paragraph>
        <paragraph indent="3">SPECIAL MEANS OF ESCAPE REQUIREMENTS: For family day-care homes, dead-bolt locks shall be provided with approved interior latches, or these locks shall be of a captured key design from which the key cannot be removed from the interior side of the lock when the lock is in the locked position.  These locks shall be unlocked at all times when the home is occupied for the purpose of family day care.</paragraph>
        <paragraph indent="3">Exception:   A double-keyed dead-bolt lock may be used on the secondary means of escape if the key is readily accessible and the lock is unlocked at all times the home is occupied for the purpose of family day care.</paragraph>
      </subsection>
      <subsection heading="22.00.04.59">
        <paragraph indent="2">NFPA 101,subsection 16.6.3.4.3, add of the following Exception:</paragraph>
        <paragraph indent="2">Exception:   Battery detectors rather than house electric service-powered detectors shall be accepted when in the opinion of the authority having jurisdiction, the facility has demonstrated testing, maintenance and battery replacement programs that ensure reliability of power to the detectors.</paragraph>
      </subsection>
      <subsection heading="22.00.04.60">
        <paragraph indent="2">NFPA 101, subsections 16.7 and 17.7, add new subsections 16.7.1.1 and 17.7.1.1, respectively as follows: A written prearranged plan of escape in case of fire or other emergency shall be readily available for reference and inspection purposes. This emergency plan shall include a means and procedure to alert all occupants of an emergency.</paragraph>
      </subsection>
      <subsection heading="22.00.04.61">
        <paragraph indent="2">NFPA 101, subsections 16.7.4.1 and 17.7.4.1, add an Exception:</paragraph>
        <paragraph indent="3">Exception: Day-Care Homes.</paragraph>
      </subsection>
      <subsection heading="22.00.04.62">
        <paragraph indent="2">NFPA 101, subsections 16.7.5 and 17.7.5, add an Exception:</paragraph>
        <paragraph indent="2">Exception: Day-Care Homes with no more than three clients for overnight lodging.</paragraph>
      </subsection>
      <subsection heading="22.00.04.63">
        <paragraph indent="2">NFPA 101, subsection 17.3.4.5, add the following language after “one room”: “...or Day-care occupancies located in school facilities where enrollment is limited to children kindergarten age and older and capable of self preservation, where no sleeping facilities are provided and the school is provided with approved full automatic sprinkler protection.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.64">
        <paragraph indent="2">NFPA 101, subsection 17.3.4.5(1), add the following sentence: “In buildings equipped with a selective fire alarm system, smoke detection at stairwell doors shall only be required at locations that would activate the alarm in the day-care center.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.65">
        <paragraph indent="2">NFPA 101, subsection 17.6.3.4.4, delete “Existing...”</paragraph>
      </subsection>
      <subsection heading="22.00.04.66">
        <paragraph indent="2">NFPA 101, subsection 24.1.1.1, place a period after the word “dwellings” and replace the remainder of the sentence with the following:</paragraph>
        <paragraph indent="2">One- and two-family dwellings include:</paragraph>
        <paragraph indent="3">(a)   A building containing not more than two dwelling units in which each dwelling unit is occupied by members of a single family with not more than five outsiders, if any, accommodated in rented rooms.</paragraph>
        <paragraph indent="3">(b)   A living unit for five or fewer individuals with disabilities as defined in (d) of this section.</paragraph>
        <paragraph indent="3">(c)   A living unit for six to eight individuals with disabilities as defined, in addition to live-in staff, if specific information is presented to the authority having jurisdiction that the residents of the living unit have no unique and specific needs which warrant imposition of the fire safety standards required by either Chapter 26, 32 or 33 of the NFPA 101 Life Safety Code (2003 edition).</paragraph>
        <paragraph indent="3">(d)   “Individuals with disabilities” means those individuals who have a disability as defined in the Fair Housing Amendment Act of 1988, 42 U.S.C. § 3601, et. seq., as follows:</paragraph>
        <paragraph indent="4">(1)   A physical or mental impairment which substantially limits one or more of such persons’ major life activities;</paragraph>
        <paragraph indent="4">(2)   A record of having such an impairment; or</paragraph>
        <paragraph indent="4">(3)   Being regarded as having such impairment, but such term does not include current, illegal use of or addiction to a controlled substance (as defined in 21 U.S.C., Section 802).</paragraph>
      </subsection>
      <subsection heading="22.00.04.67">
        <paragraph indent="2">NFPA 101, subsection 24.2.5.1, add the following exception:</paragraph>
        <paragraph indent="2">Exception:   Maximum riser heights of 8¼ inches (210 mm) and minimum tread depths of 9 inches (229 mm) shall be permitted for stairs in new construction.  A nosing not less than ¾ inch (19 mm) but not more than 1¼ inch (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm).</paragraph>
      </subsection>
      <subsection heading="22.00.04.68">
        <paragraph indent="2">NFPA 101, subsection 24.3.4.3, add at the end of the sentence, “...only if the existing smoke detectors are battery operated.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.69">
        <paragraph indent="2">NFPA 101, subsection 26.1.1.1, change “...buildings...” to “...buildings that do not qualify as one- and two-family dwellings...”.</paragraph>
      </subsection>
      <subsection heading="22.00.04.70">
        <paragraph indent="2">NFPA 101, subsection 28.3.4.1 is amended to read “...through 28.3.4.6, shall be provided.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.71">
        <paragraph indent="2">NFPA 101, subsection 28.3.4.3.5, delete all wording after “provided”.</paragraph>
      </subsection>
      <subsection heading="22.00.04.72">
        <paragraph indent="2">NFPA 101, delete subsections 29.3.4.5.2 and 31.3.4.5.2.</paragraph>
      </subsection>
      <subsection heading="22.00.04.73">
        <paragraph indent="2">NFPA 101, delete subsections 30.3.4.3.3 and 30.3.4.3.4.</paragraph>
      </subsection>
      <subsection heading="22.00.04.74">
        <paragraph indent="2">NFPA 101, subsection 32.3.1.3, replace the phrase “Chapter 7 of NFPA 5000, Building Construction Safety Code” with “33.3.1.3".</paragraph>
      </subsection>
      <subsection heading="22.00.04.75">
        <paragraph indent="2">NFPA 101, subsections 33.2.3.4.3.5 and 33.3.3.4.7.1, add at the end of the sentence, “...and have secondary battery back-up power.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.76">
        <paragraph indent="2">NFPA 101, add new subsections 36.1.2.3 and 37.1.2.3: “Structures that are predominantly residential dwellings, and that include mercantile occupancy open to the general public, shall have substantial separation between the occupancies that is resistant to the passage of smoke. Openings shall be protected with self-closing minimum 1¾" solid wood bonded core doors, in minimum eighteen (18) gauge steel frames.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.77">
        <paragraph indent="2">NFPA 101, subsection 36.4.4.4.3.1, delete item (3).</paragraph>
      </subsection>
      <subsection heading="22.00.04.78">
        <paragraph indent="2">NFPA 101, subsection 36.3.4.1 and 37.3.4.1 are amended to read as follows: General.  Class A mercantile occupancies and multiple story Class B mercantile occupancies shall be provided with a fire alarm system in accordance with section 9.6.</paragraph>
      </subsection>
      <subsection heading="22.00.04.79">
        <paragraph indent="2">NFPA 101, add new subsections 38.1.2.3 and 39.1.2.3: “Structures that are predominantly residential dwelling, and that include business occupancy open to the general public, must have substantial separation between the occupancies that is resistant to the passage of smoke.  Openings must be protected with self-closing minimum 1¾" solid wood bonded core doors in minimum eighteen (18) gauge steel frames.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.80">
        <paragraph indent="2">NFPA 101, subsections 38.2.4.2 and 39.2.4.2, add new section (6) to read as follows:</paragraph>
        <paragraph indent="3">(6)   Any two story business occupancy building not exceeding 3000 square feet gross floor area per floor shall be permitted a single exit with an approved outside stairway, or a single totally enclosed interior stairway to the second floor having discharge directly outside the building, if the total travel distance to the outside of the building does not exceed 100 feet, the travel distance to the interior stairway does not exceed 75 feet, and such interior stairway does not communicate with any other floor. An interior single exit stairway shall be permitted to be arranged as a floor communicating stair, with one (1) hour fire resistance rated opening protectives at the entrances from each level, and protection provided as follows: The building shall be provided with a non-supervised AC hard-wired smoke detection and alarm system in accordance with NFPA 72 arranged to sound an alarm audible throughout each level, and the stairway shall be provided with approved automatic sprinkler protection, with sprinklers located at the top of the stair and over each landing and on the tenant side of each interior fire door leading to the stairway, in accordance with NFPA 13.</paragraph>
      </subsection>
      <subsection heading="22.00.04.81">
        <paragraph indent="2">NFPA 101, subsections 38.3.4.3(2) and 39.3.4.3(2), are amended to read: “Sound an audible alarm in a constantly attended location and transmit a signal to a listed Central Station.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.82">
        <paragraph indent="2">NFPA 101, subsections 40.3.4.3.1, 42.3.4.3.1 and 42.8.3.4.3.1 are amended to read: “The required fire alarm system must meet Section 9.6.3 as amended.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.83">
        <paragraph indent="2">NFPA 101, subsection 39.2.2.2.3 is amended to read: “The re-entry provisions of 7.2.1.5.7 shall apply.”</paragraph>
      </subsection>
      <subsection heading="22.00.04.84">
        <paragraph indent="2">NFPA 101, subsection 42.8.2.2.3.1, add the following Exception:</paragraph>
        <paragraph indent="3">Exception: Subsection 7.2.2.5.1 shall not apply to open air parking structures.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.00.06 Fire Safety Code - Fire Protection Systems">
    <regulation heading="COMCOR 22.00.06 Fire Safety Code - Fire Protection Systems">
      <subsection heading="22.00.06.01">
        <paragraph indent="0">In accordance with the procedures authorized in Chapter 22, “Fire Safety Code”, of the Montgomery County Code, as amended, this Executive Regulation applies to the design, installation, alteration, and maintenance of fire protection systems in buildings or structures.  Where there are differences between this regulation and the Montgomery County Building Code, the more restrictive provision(s) will apply.</paragraph>
        <paragraph indent="0">In this regulation the term “Director” means the Director of the Department of Permitting Services and includes the Director’s designees.</paragraph>
        <paragraph indent="0">The Department of Permitting Services has the authority to enforce the requirements of the Montgomery County Fire Safety Code as it pertains to new and existing buildings, facilities, elements, structures, and conditions.</paragraph>
        <paragraph indent="0">New buildings, new systems, or new conditions are subject to this regulation.  Existing buildings, existing systems, or existing conditions which are altered are subject to this regulation to the extent required by the Maryland Building Rehabilitation Code, the Montgomery County Fire Safety Code, and the Maryland State Fire Prevention Code.  Unaltered existing buildings, existing systems, or existing conditions are subject to this regulation only when an inimical or distinct hazard exists.</paragraph>
        <paragraph indent="0">This regulation amends and replaces Executive Regulation No. 19-13.</paragraph>
      </subsection>
      <subsection heading="22.00.06.02">
        <paragraph indent="0">All references to the National Fire Codes and standards adopted in this regulation are to those codes, standards, recommended practices, and manuals in the National Fire Codes, published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.  Unless otherwise noted, all references are to those codes and standards published in the 2015 edition of National Fire Protection Association’s Fire Code (NFPA 1) and are adopted in their entirety.</paragraph>
        <paragraph indent="0">Terms used in this regulation that are defined in the state adopted consensus codes have the meanings used in the consensus code.</paragraph>
        <paragraph indent="0">For the purpose of this regulation, the Director is the designated Authority Having Jurisdiction (AHJ) in NFPA 1.</paragraph>
      </subsection>
      <subsection heading="22.00.06.03">
        <paragraph indent="0">NFPA 1, section 1.10 is deleted.</paragraph>
      </subsection>
      <subsection heading="22.00.06.04">
        <paragraph indent="0">Designs for smoke management systems must be submitted for review and approval as part of a building permit. Submittals for smoke management systems must include:</paragraph>
        <paragraph indent="2">(a)   Plans and specifications</paragraph>
        <paragraph indent="2">(b)   Engineering calculations and/or computer model</paragraph>
        <paragraph indent="2">(c)   Floor plans</paragraph>
        <paragraph indent="2">(d)   System diagrams and details</paragraph>
        <paragraph indent="2">(e)   Sequence of operations and control layout</paragraph>
        <paragraph indent="2">(f)   Preliminary test procedures</paragraph>
        <paragraph indent="2">(g)   Acceptance test procedures</paragraph>
        <paragraph indent="2">(h)   Pass/fail criteria</paragraph>
        <paragraph indent="2">(i)   Maintenance requirements including periodic testing criteria</paragraph>
      </subsection>
      <subsection heading="22.00.06.05">
        <paragraph indent="0">NFPA 13, section 7.2, add the following: Dry pipe systems may only be installed where heat is not adequate to prevent freezing.</paragraph>
      </subsection>
      <subsection heading="22.00.06.06">
        <paragraph indent="0">NFPA 13, sub-paragraph 7.2.3.6.1 is deleted.</paragraph>
      </subsection>
      <subsection heading="22.00.06.07">
        <paragraph indent="0">NFPA 13, subsection 8.1.1, add new principle (9) as follows:</paragraph>
        <paragraph indent="2">(9)   Sprinklers are required under attached balconies or porches unless at least 50 percent of the longest exterior side is open to the atmosphere.</paragraph>
      </subsection>
      <subsection heading="22.00.06.08">
        <paragraph indent="0">NFPA 13, paragraph 8.3.2.1 is amended as follows: In dwelling units, ordinary temperature-rated sprinklers must be used.</paragraph>
      </subsection>
      <subsection heading="22.00.06.09">
        <paragraph indent="0">NFPA 13, Section 8.3.2.4, add the following: “Intermediate temperature sprinkler heads must only be installed if an acceptable layout can not be achieved without a sprinkler head in the high temperature area.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.10">
        <paragraph indent="0">NFPA 13, paragraph 8.4.5.1, add: Listed residential sprinkler heads must be used in dwelling units except Detention and Correctional occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.06.11">
        <paragraph indent="0">NFPA 13, subsection 8.8.1, add: Extended coverage sprinklers are not permitted in speculative business and mercantile occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.06.12">
        <paragraph indent="0">NFPA 13, paragraph 8.15.7.1, add: Any canopy with the potential for extended vehicle standing or parking below must have sprinkler protection on the underside of the canopy.</paragraph>
      </subsection>
      <subsection heading="22.00.06.13">
        <paragraph indent="0">NFPA 13, Paragraph 8.15.8.2, add new sub-paragraph:</paragraph>
        <paragraph indent="1">8.15.8.2.1. When sprinklers are required, sprinklers must not be installed directly above shelving.</paragraph>
      </subsection>
      <subsection heading="22.00.06.14">
        <paragraph indent="0">NFPA 13, paragraph 8.15.15.1, is amended as follows: For new ceiling installations, drop-out ceilings are prohibited.</paragraph>
      </subsection>
      <subsection heading="22.00.06.15">
        <paragraph indent="0">NFPA 13, subparagraph 8.16.1.1.1.1 and paragraph 8.17.1.1, add: When a sprinkler system serves more than one level, each level must be consistently and separately valved by a listed and approved control valve.  In addition, where a sprinkler system is required to activate a building fire alarm system, the sprinkler system must have a separate and distinct water flow detecting device for each floor and zone.</paragraph>
        <paragraph indent="0">Exception 1:   In buildings not exceeding three floors and 3000 square feet per floor.</paragraph>
        <paragraph indent="2">Exception 2:   Unoccupied and unused attics may be zoned with the level below.</paragraph>
        <paragraph indent="2">Exception 3:   Mezzanines not exceeding 3000 square feet in area.</paragraph>
        <paragraph indent="2">Exception 4:   Detention and correctional facilities.</paragraph>
      </subsection>
      <subsection heading="22.00.06.16">
        <paragraph indent="0">NFPA 13, subsection 8.17.2, add the following requirements for fire department connections:</paragraph>
        <paragraph indent="3">(a)   Must be located within 100 feet from a fire hydrant, and between 18 and 48 inches from grade to the centerline of the inlets.</paragraph>
        <paragraph indent="3">(b)   Number of 2 ½ in. inlets:</paragraph>
        <paragraph indent="5">System Demand (gpm)         No. of Inlets</paragraph>
        <paragraph indent="5">up to 749            2</paragraph>
        <paragraph indent="5">750 - 999            3</paragraph>
        <paragraph indent="5">1000 and more            4</paragraph>
        <paragraph indent="3">(c)   Multiple connections for the same building must be interconnected.</paragraph>
        <paragraph indent="3">(d)   When a section of a building is fed by a connection (i.e., partial systems), permanent all weather identification signs must be provided on connections.</paragraph>
        <paragraph indent="3">(e)   Must be sized at least as large as the main sprinkler system riser pipe or the fire pump discharge line, whichever is larger.</paragraph>
      </subsection>
      <subsection heading="22.00.06.17">
        <paragraph indent="0">NFPA 13, section 11.1, add: Calculations for new systems or new portions of systems must meet the criteria below.</paragraph>
        <paragraph indent="3">(a)   Highest hazard and most demanding use allowed by building construction permit or property zoning.</paragraph>
        <paragraph indent="3">(b)   Storage use: Available storage height for high storage of a class 4 non- encapsulated material.</paragraph>
        <paragraph indent="3">(c)   All uses: 20% safety factor.  For systems without a pump, this is based on the demand pressure only at the supply point.  For systems with a pump, this is based on both the demand pressure and demand flow at the pump discharge.  All design options, except grids in speculative buildings, must be explored.</paragraph>
        <paragraph indent="1">Exception to safety factor only: Owner occupied buildings may use a lower safety factor if a pump would be necessary to achieve the 20%.</paragraph>
      </subsection>
      <subsection heading="22.00.06.18">
        <paragraph indent="0">NFPA 13, paragraph 11.2.2.3, delete (3) and (4).</paragraph>
      </subsection>
      <subsection heading="22.00.06.19">
        <paragraph indent="0">NEPA 13, subsection 24.1.2, add: Pressure and flow availability as determined by a hydraulic information sheet received from a public utility must be used for new taps.  Pressure and flow availability for existing taps must be determined by an interior flow test.  In any case, the supply information must be corrected for the low hydraulic gradient.  Fire pumps and fire pump/tank supplies must only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.06.20">
        <paragraph indent="0">NFPA 13, section 25.1, add: (5): Finished surfaces must be completed within a 1' radius of sprinklers before the final inspection.</paragraph>
      </subsection>
      <subsection heading="22.00.06.21">
        <paragraph indent="0">NFPA 13, paragraph 25.2.1.11, add a third sentence: Pendent sprinkler heads must not be installed in plastic pipe until after the hydrostatic test is passed.</paragraph>
      </subsection>
      <subsection heading="22.00.06.22">
        <paragraph indent="0">NFPA 13D, subsection 1.1.1, add a second sentence: This standard also applies to Day Care homes containing 12 clients or less if located within converted one and two family dwellings or townhouses.</paragraph>
      </subsection>
      <subsection heading="22.00.06.23">
        <paragraph indent="0">NFPA 13D, section 6.1, add: Pressure and flow availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may be used only where it is demonstrated that the public water supply is inadequate as determined by the Director.</paragraph>
      </subsection>
      <subsection heading="22.00.06.24">
        <paragraph indent="0">NFPA 13D, subsection 6.1.1, add: All calculations must include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.06.25">
        <paragraph indent="0">NFPA 13D, section 6.2: Add (6)</paragraph>
        <paragraph indent="1">(6)   System specific data plate on durable material to be fixed at sprinkler system main riser.</paragraph>
      </subsection>
      <subsection heading="22.00.06.26">
        <paragraph indent="0">NFPA 13D, paragraph 7.5.6.1, add: Where possible to maintain listed coverage, sprinkler heads must be positioned so as to eliminate the need to install sprinkler heads of a higher temperature rating.</paragraph>
      </subsection>
      <subsection heading="22.00.06.27">
        <paragraph indent="0">NFPA 13D, subsection 7.5.7, add: Finished surfaces must be completed within a 1' radius of all sprinklers before the final inspection.</paragraph>
      </subsection>
      <subsection heading="22.00.06.28">
        <paragraph indent="0">NFPA 13D, paragraph 8.2.5.1, add sub-paragraph 8.2.5.1.1:</paragraph>
        <paragraph indent="3">8.2.5.1.1 Sprinkler heads in closets must not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.06.29">
        <paragraph indent="0">NFPA 13D, subsection 8.3.4, add the following after garages: “...unless located partially or wholly beneath living space.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.30">
        <paragraph indent="0">NFPA 13D, subsection 9.1.2: Delete Methods (1), (2) and (4).</paragraph>
      </subsection>
      <subsection heading="22.00.06.31">
        <paragraph indent="0">NFPA 13D, paragraph 11.2.1.4, add a second sentence: When systems utilizing plastic pipe are being hydrostatically tested, pendent sprinklers are not permitted.</paragraph>
      </subsection>
      <subsection heading="22.00.06.32">
        <paragraph indent="0">NFPA 13R, subsection 5.4.2, add: Antifreeze, dry pipe and preaction systems are prohibited in dwelling units and interior corridors leading to dwelling units.</paragraph>
      </subsection>
      <subsection heading="22.00.06.33">
        <paragraph indent="0">NFPA 13R, subparagraph 6.4.6.3.2, add: Sprinkler heads in closets must not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.06.34">
        <paragraph indent="0">NFPA 13R, subsection 6.11.1 is amended to read: “In all apartment buildings, at least one fire department connection must be provided for buildings accessible by the fire department, that exceed 2000 square feet or are more than a single story. The fire department connection must be a minimum of one 2 ½ inch inlet with a feed line sized at least as large as the main system riser.  The fire department connection must be located on a fire department access road and be 18 to 48 inches from the centerline of the inlet to finish grade.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.35">
        <paragraph indent="0">NFPA 13R, section 7.4, add: All calculations must include at least a 10% safety factor to account for minor field changes, unless a listed fire pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.06.36">
        <paragraph indent="0">NFPA 13R, section 9.1, add: Pressure and volume availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may be used only where it is demonstrated that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.06.37">
        <paragraph indent="0">NFPA 13R, section 9.4, add: Domestic pumps are permitted for townhomes.</paragraph>
      </subsection>
      <subsection heading="22.00.06.38">
        <paragraph indent="0">NFPA 13R, subsection 10.2.2. Add a new paragraph:</paragraph>
        <paragraph indent="1">10.2.2.3 Pendent sprinkler heads must not be installed in plastic pipe until after the hydrostatic test is passed.</paragraph>
      </subsection>
      <subsection heading="22.00.06.39">
        <paragraph indent="0">NFPA 14, subsection 4.8.2 is amended as follows: Each fire hose valve must have a 2 ½ in. hose connection, 2 ½ in. to 1 ½ in. reducer, cap, and chain.</paragraph>
      </subsection>
      <subsection heading="22.00.06.40">
        <paragraph indent="0">NFPA 14, subsection 5.1.2, add:</paragraph>
        <paragraph indent="3">(1)   Systems must be automatic wet type.</paragraph>
        <paragraph indent="3">(2)   Standpipe systems in unheated areas must be automatic dry type.</paragraph>
        <paragraph indent="3">(3)   Standpipe systems in detached open parking garages may be the manual dry type, if the piping is air supervised for breaks or open valves.</paragraph>
        <paragraph indent="3">(4)   Occupant use hose is prohibited in new or existing buildings.</paragraph>
        <paragraph indent="3">(5)   New standpipe systems must be Class I only.</paragraph>
      </subsection>
      <subsection heading="22.00.06.41">
        <paragraph indent="0">NFPA 14, section 6.4 (Fire Department Connections), add:</paragraph>
        <paragraph indent="3">(1)   Number of 2 ½ in. inlets:</paragraph>
        <paragraph indent="5">System Demand (gpm)      No. of Inlets</paragraph>
        <paragraph indent="5">up to 749         2</paragraph>
        <paragraph indent="5">750-999         3</paragraph>
        <paragraph indent="5">1,000 and more         4</paragraph>
        <paragraph indent="3">(2)   Multiple connections on the same building must be interconnected.</paragraph>
        <paragraph indent="3">(3)   When a section of a building is fed by a connection (i.e., partial systems), permanent all-weather identification signs must be provided on connections.</paragraph>
      </subsection>
      <subsection heading="22.00.06.42">
        <paragraph indent="0">NFPA 14, paragraph 7.3.2.2, add:</paragraph>
        <paragraph indent="3">(1)   Measurement must be parallel or at right angles to walls.</paragraph>
        <paragraph indent="3">(2)   Supplemental hose valves outside the stairs must not be located within tenant spaces, unless hose reach requirements cannot be met by placement of valves in public corridors or by use of wall hydrants for spaces opening to the exterior.  Hose valve locations must be marked by the placement of signs, the striping of columns, or other approved methods.</paragraph>
      </subsection>
      <subsection heading="22.00.06.43">
        <paragraph indent="2">NFPA 14, subsection 7.8.1, add exceptions:</paragraph>
        <paragraph indent="0">Exception 1: In high-rise buildings, where booster pumps are necessary to produce the required residual pressures, pumps and piping systems must be sized to provide for the demand of the hydraulically most remote hose station, or the sprinkler system demand, whichever is greater.  The standpipe system must also be sized to provide the required flow and pressure for all hose stations required to be flowing, when supplied by 150 psi at 1000 gpm at the fire department connection(s).  Two sets of calculation will, therefore, be required under this exception.</paragraph>
        <paragraph indent="1">Exception 2: Systems in buildings that are not high-rise, and dry systems with no automatic water supply, may be sized to obtain the required flows and pressures, when supplied by 150 psi at 1000 gpm at the fire department connection(s).</paragraph>
        <paragraph indent="1">Exception 3: In existing buildings, after shell occupancy, hose valves added to correct reach violations created by tenant modifications may be supplied by 3 inch pipe without recalculation.</paragraph>
      </subsection>
      <subsection heading="22.00.06.44">
        <paragraph indent="0">NFPA 20, paragraph 4.7.7.2, add: A relief valve is permitted to be installed to reduce operating pressure below 175 psi at high gradient.</paragraph>
      </subsection>
      <subsection heading="22.00.06.45">
        <paragraph indent="0">NFPA 20, subsection 14.2.3, add: Fire pump control equipment must be inspected and approved by a Montgomery County electrical inspector before a fire pump performance test is performed and witnessed by Montgomery County.</paragraph>
      </subsection>
      <subsection heading="22.00.06.46">
        <paragraph indent="0">NFPA 20, subsection 4.18.7 is amended entirely to state: For other than static water supplies, relief valves must not be piped back into the source of the supply.</paragraph>
      </subsection>
      <subsection heading="22.00.06.47">
        <paragraph indent="0">NFPA 72, subsection 10.4.3 is amended by adding paragraph 10.4.3.1</paragraph>
        <paragraph indent="0">10.4.3.1 When fire alarm equipment is installed in a parking garage or other similar space, if the AHJ determines that the humidity or temperature of the space or both cannot be maintained, then the fire alarm equipment must be listed for outdoor use and the environment where it is installed.</paragraph>
      </subsection>
      <subsection heading="22.00.06.48">
        <paragraph indent="0">NFPA 72, subsection 10.18.3, add the following sentence: An annunciator with the following features is required when the building is greater than one story, has a sprinkler system, or has more than one type of alarm initiating device.</paragraph>
        <paragraph indent="3">Exception 1: Apartments protected by a 13R sprinkler system.</paragraph>
        <paragraph indent="1">Exception 2: Any building not exceeding two stories above grade and 3,000 square feet per floor.</paragraph>
        <paragraph indent="3">(a)   Annunciator must have a visible signal for each different floor, zone, and device type.  Supervised computer screen or printer type annunciators may be used to meet this requirement if the zone identification is approved by the Director or Director’s designees.</paragraph>
        <paragraph indent="3">(b)   Unless approved by the authority having jurisdiction, zones must not exceed a single floor, 52,000 square feet, or 300 linear feet.  Sprinkler systems are permitted to be zoned under the applicable sprinkler standard.</paragraph>
        <paragraph indent="3">(c)   In zones greater than 22,500 square feet, a graphic outline on or adjacent to the annunciator must be provided showing the building outline, fire alarm and sprinkler zone boundaries, “you are here” notation, north compass arrow, all stairways, stairway identification numbers, sprinkler zones, all standpipe risers, fire department connections, elevators, and the building address.</paragraph>
        <paragraph indent="3">(d)   A lamp type annunciator must have a lamp test switch unless the annunciator circuits are supervised.</paragraph>
        <paragraph indent="3">(e)   The annunciator must be located at, and be visible from, the main fire department entrance unless the building has a fire command center.</paragraph>
        <paragraph indent="3">(f)   If two or more buildings are controlled by one alarm system, an annunciator must be installed in each building with a pilot lamp indicating the building of alarm origination.</paragraph>
        <paragraph indent="3">(g)   The graphic orientation must match the building orientation.</paragraph>
        <paragraph indent="3">(h)   The graphic floor level designations must match the elevator floor level designations.</paragraph>
      </subsection>
      <subsection heading="22.00.06.49">
        <paragraph indent="0">Amend NFPA 72, paragraph 14.4.10.3 to read as follows:</paragraph>
        <paragraph indent="1">“Test procedures. The test plan must ensure testing throughout the building. Test procedures must be as directed by the design professional and the AHJ. Using the Montgomery County control channel, each floor must be RF (radio frequency) signal level mapped utilizing a calibrated, portable spectrum analyzer. Each floor must be divided into equal grids of no larger than 50 feet by 50 feet. Individual testing points must not be spaced greater than 50 feet apart. Each grid must meet the required signal strength level, and provide a Delivered Audio Quality (DAQ) of not less than 3.5. (DAQ 3.5 is defined as ‘Speech understandable with repetition rarely required. Some noise/distortion.’) A maximum of two non-adjacent grids will be allowed to fail on the same floor. Failure of any two adjacent grids is considered a failure for the entire floor. Critical rooms, including, but not limited to, such areas as the fire command/control center, fire pump room, emergency generator room, stairwells with a standpipes, and other staging areas as identified by the AHJ, must not fail coverage at all.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.50">
        <paragraph indent="0">Amend NFPA 72, paragraph 14.4.10.5 to read as follows:</paragraph>
        <paragraph indent="1">“The design and acceptance testing of the in-building public safety radio enhancement system must be performed under the supervision of a Maryland registered professional engineer with a minimum of 5 years of experience in the design, installation, and alignment of bi-directional amplifier systems.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.51">
        <paragraph indent="0">Amend NFPA 72, subsection 14.4.10 to add paragraph 14.4.10.7 to read as follows:</paragraph>
        <paragraph indent="1">14.4.10.7 Maintenance. The building owner must maintain a service contract for emergency repair of the system. The service contract must be such that telephone support is available within 2 hours, and on-site maintenance service can be provided within 24 hours of recognition that the in-building public safety radio enhancement system is not operating correctly. A copy of the contract must be submitted to the AHJ at the time of acceptance testing. If the service contract is terminated, both the building owner and contractor must notify the AHJ within 24 hours.</paragraph>
      </subsection>
      <subsection heading="22.00.06.52">
        <paragraph indent="0">NFPA 72, paragraph 17.7.1.7 is amended as follows: Detectors located at the top of shafts and stairs must be on a supervisory circuit only, unless a confirmation or verification feature is provided.  The location must be identified at the annunciator or fire alarm control panel.</paragraph>
      </subsection>
      <subsection heading="22.00.06.53">
        <paragraph indent="0">NFPA 72, paragraph 17.7.4.4, add: Activation of duct smoke detectors must sound an audible alarm in a normally occupied area or through the building fire alarm system, and must be identified as duct detector. Where connected to the building alarm, the signal must be supervisory only and must not initiate the building evacuation alarm unless a confirmation or verification feature is provided.</paragraph>
      </subsection>
      <subsection heading="22.00.06.54">
        <paragraph indent="0">NFPA 72, subsection 17.12.2, add: Standpipe or main water flow indicators, if provided, must sound a supervisory signal only.</paragraph>
      </subsection>
      <subsection heading="22.00.06.55">
        <paragraph indent="0">NFPA 72, section 17.14, is amended by adding paragraph 17.14.8.7</paragraph>
        <paragraph indent="0">17.14.8.7 When fire alarm systems are not monitored by a UL listed central station, an approved permanent sign must be installed adjacent to each manual fire alarm box.  The sign must read as follows:</paragraph>
        <paragraph indent="3">Local Alarm Only:</paragraph>
        <paragraph indent="3">(1)   Activate Alarm</paragraph>
        <paragraph indent="3">(2)   Exit Building</paragraph>
        <paragraph indent="3">(3)   Call Fire Department</paragraph>
      </subsection>
      <subsection heading="22.00.06.56">
        <paragraph indent="0">NFPA 72, paragraph 24.5.1.15 is amended by changing “two” to “six”.</paragraph>
      </subsection>
      <subsection heading="22.00.06.57">
        <paragraph indent="0">NFPA 72, paragraph 24.5.2.2 is modified to read as follows:</paragraph>
        <paragraph indent="0">“Radio Coverage. Radio coverage must be provided throughout the building such that a minimum of 95% of the building (including underground levels, basements, elevators, stairways, etc.) is covered at a minimum of 95% of the time.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.58">
        <paragraph indent="0">Amend NFPA 72, add subparagraph 24.5.2.5.6 to read as follows:</paragraph>
        <paragraph indent="0">“Where required by the AHJ, a two inch diameter conduit/conduit sleeves must be provided vertically from the roof level to the lowest level of the structure. This conduit will provide a vertical path for cable to all levels and should pass through the in-building public safety radio enhancement system equipment room. At a minimum, one 20-amp AC circuit and building ground must be located at the public safety radio enhancement system equipment and any outside antenna locations.”</paragraph>
      </subsection>
      <subsection heading="22.00.06.59">
        <paragraph indent="0">NFPA 72, paragraph 29.8.3.4, add new paragraph (14):</paragraph>
        <paragraph indent="0">(14)   Enclosed rooms with a closet such as dens, libraries, studies, or sitting rooms which could be used as a sleeping area must be treated as bedrooms.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.00.07 Fire Safety Code - Building Construction">
    <regulation heading="COMCOR 22.00.07 Fire Safety Code - Building Construction">
      <subsection heading="22.00.07.01">
        <paragraph indent="1">In accordance with the procedures authorized in Chapter 22, “Fire Safety Code,” of the Montgomery County Code, as amended, this Executive Regulation applies to the safeguarding of life, property, and the public welfare from the hazards of fire and explosion arising from the improper storage, handling, or use of substances, materials, or devices and from conditions hazardous to life, property, and the public welfare in the construction, alteration, use or occupancy of buildings, structures, sheds, tents, lots or premises.  Where there are differences between this regulation and the Montgomery County Building Code, the more restrictive provision(s) will apply.</paragraph>
        <paragraph indent="1">In this regulation the term “Director” means the Director of the Department of Permitting Services and includes the Director’s designees.</paragraph>
        <paragraph indent="1">The Department of Permitting Services has the authority to enforce the requirements of the Montgomery County Fire Safety Code as it pertains to new and existing buildings, facilities, elements, structures, and conditions.</paragraph>
        <paragraph indent="1">New buildings, new systems, or new conditions are subject to this regulation.  Existing buildings, existing systems, or existing conditions which are altered are subject to this regulation to the extent required by the Maryland Building Rehabilitation Code, the Montgomery County Fire Safety Code, and the Maryland State Fire Prevention Code.  Unaltered existing buildings, existing systems, or existing conditions are not subject to this regulation where no inimical or distinct hazard exists.</paragraph>
        <paragraph indent="1">This regulation amends and replaces Executive Regulation No. 8-16 and 7-16.</paragraph>
      </subsection>
      <subsection heading="22.00.07.02">
        <paragraph indent="1">Unless otherwise noted, all references to the National Fire Codes and Standards adopted in this regulation are to those codes, standards, recommended practices and manuals in the National Fire Codes, published by the National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02169.  The references to these National Fire Codes and Standards are set forth in Section 22-14 of the Montgomery County Code, as amended.</paragraph>
        <paragraph indent="1">Terms used in this regulation that are defined in the state-adopted consensus codes have the meanings used in the consensus code.</paragraph>
        <paragraph indent="1">For the purpose of this regulation, the Director is the designated Authority Having Jurisdiction (AHJ) in NFPA 1.</paragraph>
        <paragraph indent="1">In accordance with the procedures authorized in Chapter 22, “Fire Safety Code”, of the Montgomery County Code, as amended, this Executive Regulation also applies to the design, installation, alteration, and maintenance of fire protection systems in buildings or structures.  Where there are differences between this regulation and Chapter 8 (Buildings – Regulations) of the Code of Montgomery County Regulations, the more restrictive provision(s) will apply.  In this regulation the term “Fire Chief” means the Fire Chief of the Montgomery County Fire and Rescue Service and includes the Fire Chief’s designees.  The Department of Permitting Services has been delegated authority by the Fire Chief to enforce the requirements of the Montgomery County Fire Safety Code as it pertains to new and existing buildings, facilities, elements, structures, and conditions.</paragraph>
      </subsection>
      <subsection heading="22.00.07.03">
        <paragraph indent="1">Where the Public Safety Article, Annotated Code of Maryland, or the Montgomery County Code requires a permit, license, or certificate of approval be obtained, it must be obtained from the Department of Permitting Services, the State Fire Marshal, or other authority deemed appropriate by the County.  Terms used in this regulation which are defined in the state-adopted consensus codes have the definitions as contained in consensus codes.  For the purposes of this regulation, the Director is the designated Authority Having Jurisdiction (AHJ) as defined by NFPA 1.</paragraph>
      </subsection>
      <subsection heading="22.00.07.04">
        <paragraph indent="1">Standards Adopted.  The following standards published by the National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, Massachusetts 02169, are incorporated in these regulations except as expressly amended.  These codes, and the associated codes and standards incorporated by reference, are adopted to set the minimum requirements to establish a reasonable level of safety from the hazards created by fire, explosion, and dangerous conditions.  The references to these National Fire Codes and Standards are set forth in Section 22-14 of the Montgomery County Code, as amended.  The dates or editions of the individual codes and standards are as listed in this section.</paragraph>
        <paragraph indent="3">NFPA No.   Code or Standard</paragraph>
        <paragraph indent="3">1      Fire Code – 2021 edition</paragraph>
        <paragraph indent="3">13      Standard for the Installation of Sprinkler Systems – 2019 edition</paragraph>
        <paragraph indent="3">13D      Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes – 2019 edition</paragraph>
        <paragraph indent="3">13R      Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies – 2019 edition</paragraph>
        <paragraph indent="3">14      Standard for the Installation of Standpipe and Hose Systems – 2019 edition</paragraph>
        <paragraph indent="3">20      Standard for the Installation of Stationary Pumps for Fire Protection – 2019 edition</paragraph>
        <paragraph indent="3">72      National Fire Alarm and Signaling Code – 2019 edition</paragraph>
        <paragraph indent="3">80      Standard for Fire Doors and Other Opening Protectives – 2019 edition</paragraph>
        <paragraph indent="3">92      Standard for Smoke Control Systems – 2021 edition</paragraph>
        <paragraph indent="3">96      Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations – 2021 edition</paragraph>
        <paragraph indent="3">101      Life Safety Code – 2021 edition</paragraph>
        <paragraph indent="3">720      Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment – 2015 edition</paragraph>
        <paragraph indent="3">850      Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations – 2021 edition</paragraph>
        <paragraph indent="3">1221      Standard for the Installation, Maintenance, and Use of Emergency Services Communication Systems – 2019 edition</paragraph>
        <paragraph indent="3">1225      Standard for Emergency Services Communications – 2022 edition</paragraph>
      </subsection>
      <subsection heading="22.00.07.05">
        <paragraph indent="1">The Director must review this regulation and propose amendments within six months after the date the State Fire Prevention Commission adopts new amendments to NFPA 1 and NFPA 101 into the State Fire Prevention Code.</paragraph>
      </subsection>
      <subsection heading="22.00.07.06">
        <paragraph indent="1">Amend NFPA 1, Subsection 1.7.12.2 to add a second sentence “The AHJ is authorized to require plans to bear the stamp of a registered design professional.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.07">
        <paragraph indent="1">Delete NFPA 1, Section 1.10.</paragraph>
      </subsection>
      <subsection heading="22.00.07.08">
        <paragraph indent="1">Delete NFPA 1, Subsection 1.11.3.</paragraph>
      </subsection>
      <subsection heading="22.00.07.09">
        <paragraph indent="1">Amend NFPA 1, Subsection 1.12.1, to add the following Subsection 1.12.1.1:</paragraph>
        <paragraph indent="2">1.12.1.1 Permits, certificates, notices, approvals or orders required by this code must be governed by the policies and procedures of the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.10">
        <paragraph indent="1">Amend NFPA 1, Subsection 1.12.6.13 to replace “Permits shall” with “Permits may”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.11">
        <paragraph indent="1">Amend NFPA 1, Subsection 1.12.8 to replace “shall” with “may”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.12">
        <paragraph indent="1">Amend NFPA 1, Subsection 1.13.2 to delete “Mandatory.” and replace “shall” with “may”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.13">
        <paragraph indent="1">Delete NFPA 1, Subsections 1.13.12.4 and 1.16.4.3.</paragraph>
      </subsection>
      <subsection heading="22.00.07.14">
        <paragraph indent="1">Amend NFPA 1, Subsections 2.1.1, 2.1.1.1, and 2.1.1.2 to replace “Compliance” with “Where permitted by the AHJ, compliance”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.15">
        <paragraph indent="1">Amend NFPA 1, Section 2.2 to delete the referenced publication NFPA 5000 Building Construction and Safety Code, 2021 edition.  Wherever NFPA 5000 is referenced, other than for extracted text, substitute the building code adopted by the AHJ.  Delete the referenced publication NFPA 150 Standard on Fire and Life Safety in Animal Housing Facilities, 2019 edition.</paragraph>
      </subsection>
      <subsection heading="22.00.07.16">
        <paragraph indent="1">Amend NFPA 1, Subsection 3.3.14 to add the following Subsection:</paragraph>
        <paragraph indent="2">3.3.14.13 Consumer Fireworks Retail Sales Area.  The portion of a consumer fireworks retail sales facility or store, including the immediately adjacent aisles, where consumer fireworks are located for the purpose of retail display and sale to the public.</paragraph>
      </subsection>
      <subsection heading="22.00.07.17">
        <paragraph indent="1">Amend NFPA 1, Subsections as follows:</paragraph>
        <paragraph indent="2">(1)   3.3.108 to delete the wording and replace with the following:  Existing.  That which is already in existence greater than one calendar year after being approved, accepted, or commissioned by the authority having jurisdiction;</paragraph>
        <paragraph indent="2">(2)   3.3.136 and Subsection 3.3.136.1 to add “and as referenced in Public Safety Article, § 10-101, Annotated Code of Maryland;</paragraph>
        <paragraph indent="2">(3)   amend Subsection 3.3.199.6 to delete “more than 3 but”;</paragraph>
        <paragraph indent="2">(4)   amend Subsections 3.3.199.7 and 6.1.4.1 to delete “four or more”;</paragraph>
        <paragraph indent="2">(5)   amend Subsections 3.3.199.11, 3.3.199.16, 3.3.199.24, 3.3.199.28, 6.1.5.1, and 6.1.9.1 to replace “four” with “six”; and</paragraph>
        <paragraph indent="2">(6)   amend Subsections 3.3.199.25, 3.3.199.25.1, and 6.1.8.1.1 to replace “three” with “five” and delete “, if any, accommodated in rented rooms”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.18">
        <paragraph indent="1">Amend NFPA 1, Subsection 4.5.8.1 to delete the phrase “for compliance with the provisions of this Code”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.19">
        <paragraph indent="1">Amend NFPA 1, Subsection 4.5.8.3 to delete the phrase “by the Code”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.20">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.1.2 to add “except as amended by COMAR 29.06.01.07, COMAR 29.06.01.08, and COMAR 29.06.01.09”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.21">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.2.7.1 to delete the existing wording and replace it with “Fire prevention inspections on existing premises may occur at a frequency as determined by the authority having jurisdiction.  Recommended minimum inspection frequencies are contained in Table 10.2.7.1.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.22">
        <paragraph indent="1">Amend NFPA 1, Subsections 10.4.1 and 10.4.2 to replace “AHJ” with “AHJ or incident commander”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.23">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.10.6.1 to replace “10 ft (3 m)” with “20 ft (6.1 m)”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.24">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.10.6.3 to add the following after the phrase “must be permitted.”:  If the equipment is installed on any deck or overhanging portion, atop the roof, or within 20 ft (6.1 m) of a structure, it must also comply with all of the following:</paragraph>
        <paragraph indent="2">(1)   the building must be equipped with an approved automatic sprinkler system.  A standpipe with a hose valve outlet at the level of the proposed feature area must be available;</paragraph>
        <paragraph indent="2">(2)   the equipment cannot be installed beneath any overhanging portion of the building;</paragraph>
        <paragraph indent="2">(3)   canopies, trellis, or similar coverings for weather protection must be at least four (4) ft above the cooking surface and constructed of non-combustible materials;</paragraph>
        <paragraph indent="2">(4)   portable cooking equipment is not permitted;</paragraph>
        <paragraph indent="2">(5)   cooking with solid fuels is not permitted;</paragraph>
        <paragraph indent="2">(6)   any furnishings or installations within ten (10) ft of the equipment must be noncombustible, including the flooring or ground cover;</paragraph>
        <paragraph indent="2">(7)   a manual shut-off must be installed in a readily accessible location within six (6) ft of the appliance.  The shut-off will stop the supply of fuel, or in the case of an electrical appliance, disconnect the power supply, in case of an emergency;</paragraph>
        <paragraph indent="2">(8)   the equipment must have a timer not to exceed one hour which will automatically shut off the equipment in accordance with item g.; and</paragraph>
        <paragraph indent="2">(9)   the cooking surface cannot be located within ten (10) ft of a property line or any operable openings into a building.</paragraph>
      </subsection>
      <subsection heading="22.00.07.25">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.11.1 as follows:</paragraph>
        <paragraph indent="2">(1)   amend 10.11.1 to replace “address numbers” with “premises identification”;</paragraph>
        <paragraph indent="2">(2)   add Subsection 10.11.1.1 that reads, “Subject to the approval of the AHJ, individual suites within structures and rear entrances and/or access from service corridors must be clearly identified;</paragraph>
        <paragraph indent="2">(3)   amend Subsections 10.11.1.2, 10.11.1.6, 10.11.1.7 and 10.11.1.8 to replace “Address numbers” with “Premises identification”;</paragraph>
        <paragraph indent="2">(4)   amend Subsection 10.11.1.4 to delete existing wording and replace with “Where required by the AHJ, the assignment of addresses to buildings must be in accordance with an approved method.”;</paragraph>
        <paragraph indent="2">(5)   delete Subsection 10.11.1.5; and</paragraph>
        <paragraph indent="2">(6)   add 10.11.1.9 that reads, “Where required by the AHJ, symbols in compliance with NFPA 170, Standard for Fire Safety and Emergency Symbols, must be used.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.26">
        <paragraph indent="1">Amend NFPA 1, Subsection to replace “any vehicles” with “any vehicles, buildings.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.27">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.15.5.1 to replace “Portable” with “Unless otherwise approved by the AHJ, portable”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.28">
        <paragraph indent="1">Amend NFPA 1, Subsection A10.15.5.1 to add the following:  For the purposes of reducing the distances between the operation and refueling of portable and vehicle-mounted generators and any building or enclosure opening, including windows, doors, and air intakes, one or more of the following conditions may be considered:</paragraph>
        <paragraph indent="2">(1)   nature of the occupancy of the building or enclosure;</paragraph>
        <paragraph indent="2">(2)   expected duration of generator use;</paragraph>
        <paragraph indent="2">(3)   use of certified low CO emission generators;</paragraph>
        <paragraph indent="2">(4)   actual available distance between the generator and building or enclosure openings;</paragraph>
        <paragraph indent="2">(5)   installation of approved CO detection within the building or enclosure;</paragraph>
        <paragraph indent="2">(6)   openness of building or enclosure perimeter walls and ceiling; or</paragraph>
        <paragraph indent="2">(7)   physical barriers or other means to deflect generator exhaust from building or enclosure openings.</paragraph>
      </subsection>
      <subsection heading="22.00.07.29">
        <paragraph indent="1">Amend NFPA 1, Section 10.16 to add the following Subsection 10.16.6 as follows:</paragraph>
        <paragraph indent="2">The AHJ has the authority to require that outdoor storage of any combustible material be enclosed by an approved fence or other protective enclosure to prevent unauthorized access.</paragraph>
      </subsection>
      <subsection heading="22.00.07.30">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.16.1 to replace “10 ft (3 m)” with “15 ft (4.6 m)” and “property line” with “property line, building, or adjacent pile of combustible material”; and add the following:  The AHJ may increase the separation distance where the AHJ determines that a higher hazard to the adjoining property exists.</paragraph>
      </subsection>
      <subsection heading="22.00.07.31">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.16.5 to add the phrase “and 10,000 ft2 in area”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.32">
        <paragraph indent="1">Amend NFPA 1, Subsection 10.19.7 to replace “repaired” with “repaired on any balcony, under any overhanging portion, or”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.33">
        <paragraph indent="1">Amend NFPA 1, Section 11.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">11.1.9 Clearance.  A clear space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height must be provided in front of electrical service equipment.  Where the electrical service equipment is wider than 30 inches (762 mm), the clear space must not be less than the width of the equipment.  No storage of any materials must be located within the designated clear space.  Exception:  Where other specialized dimensions are required or permitted by NFPA 70.</paragraph>
      </subsection>
      <subsection heading="22.00.07.34">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.1.5.6 to delete existing wording and replace with the following:  Extension cords cannot be used as a substitute for permanent wiring.</paragraph>
      </subsection>
      <subsection heading="22.00.07.35">
        <paragraph indent="1">Amend NFPA 1, to add Subsections 11.1.7.2.1 and 11.1.7.2.2 to read:</paragraph>
        <paragraph indent="2">11.1.7.2.1 In new buildings, excluding one- and two-family dwellings, a shunt trip to disconnect the electrical service to the building must be provided as follows:</paragraph>
        <paragraph indent="2">(1)   in the emergency command center, where an emergency command center is in the building;</paragraph>
        <paragraph indent="2">(2)   at the fire alarm annunciator, where there is a fire alarm annunciator and where there is no emergency command center; and</paragraph>
        <paragraph indent="2">(3)   in an appropriately sized and weatherproof fire department access box on the address side of the building, where there is no emergency command center or fire alarm annunciator.</paragraph>
        <paragraph indent="2">11.1.7.2.2 In existing buildings, excluding one- and two-family dwellings, where there are significant upgrades to the building electrical service, such as modifying or replacing the switchgear, a disconnecting means must be provided as for new installations.</paragraph>
      </subsection>
      <subsection heading="22.00.07.36">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.1.7.3 to add the following Subsection:</paragraph>
        <paragraph indent="2">11.1.7.3.2 Doors to electrical control panel rooms must be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording in contrasting letters not less than 1 inch (25 mm) high and not less than 1/4 inch (6.4 mm) in stroke width.</paragraph>
      </subsection>
      <subsection heading="22.00.07.37">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.3.6.1 to add the following sentence:  Keys for new elevators must be cut to a uniform key code to comply with the Maryland State Elevator Code.</paragraph>
      </subsection>
      <subsection heading="22.00.07.38">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.9.1 to replace “approved by the fire department” with “approved by the AHJ”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.39">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.9.1 to add the following Subsections:</paragraph>
        <paragraph indent="2">11.9.1.1 In new installations, the emergency command center must have a door directly to the exterior of the building on the address side.  The exterior door to the emergency command center must be within 50 feet, measured along the path of travel, of a fire department access road.  A fire department access box must be provided within six (6) feet of the door to the emergency command center.</paragraph>
        <paragraph indent="2">11.9.1.2 The exterior door to the emergency command center must have an all-weather sign with raised letters on a contrasting background, not less than 1 inch in size reading:  EMERGENCY COMMAND CENTER.</paragraph>
      </subsection>
      <subsection heading="22.00.07.40">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.9.5(8) to read as follows:</paragraph>
        <paragraph indent="2">(8)   Fire pump status indicators and remote starting.</paragraph>
      </subsection>
      <subsection heading="22.00.07.41">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.10.11.1 to replace “conducted as follows:” with “conducted as follows unless otherwise directed by the AHJ:”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.42">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.12.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">11.12.1.1 The provisions of this section do not apply to detached parking shade structures, carports, solar trellises and similar structures.</paragraph>
      </subsection>
      <subsection heading="22.00.07.43">
        <paragraph indent="1">Amend NFPA 1, Subsection 11.12.2.1.1 to replace the word “Buildings” with the phrase “New and existing buildings other than one- and two-family dwellings”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.44">
        <paragraph indent="1">Amend NFPA 1, to add Subsection 11.12.3.3.3.1 that reads as follows:  Where approved by the Director, a performance-based, alternative method of compliance may be permitted in accordance with NFPA 1, Section 1.4.</paragraph>
      </subsection>
      <subsection heading="22.00.07.45">
        <paragraph indent="1">Amend NFPA 1, Subsection 12.6.9.1 to add the following new Subsection:</paragraph>
        <paragraph indent="2">12.6.9.1.2 The AHJ must:</paragraph>
        <paragraph indent="2">(1)   approve the placement of a natural cut or balled tree;</paragraph>
        <paragraph indent="2">(2)   limit the number of natural cut or balled trees displayed; and</paragraph>
        <paragraph indent="2">(3)   order the removal of any tree if the tree poses a hazard to life or safety.</paragraph>
      </subsection>
      <subsection heading="22.00.07.46">
        <paragraph indent="1">Amend NFPA 1, Subsection 12.6.9.1.1 to replace “Christmas” with “Unless otherwise approved by the AHJ, Christmas”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.47">
        <paragraph indent="1">Amend NFPA 1, Subsection 12.6.9.5 to add the following Subsection:</paragraph>
        <paragraph indent="2">12.6.9.5.3 Combustible artificial decorative vegetation must be tested by a laboratory recognized by the Office of the State Fire Marshal.</paragraph>
      </subsection>
      <subsection heading="22.00.07.48">
        <paragraph indent="1">Amend NFPA 1, Subsection 12.6.9.6.1 to replace “1/2 in. (13 mm)” with “2 in. (50 mm)” and add the following sentence:  “A natural cut tree must not exceed 10 ft. (3 m) in height, excluding the tree stand.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.49">
        <paragraph indent="1">Amend NFPA 1, Section 13.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">13.1.14 Appearance of Equipment.  The AHJ is permitted to prohibit any device that has the physical appearance of a life safety or fire protection function but does not perform that life safety or fire protection function.</paragraph>
      </subsection>
      <subsection heading="22.00.07.50">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.1.3.1 to replace “by Chapters 11 through 43” with “by the AHJ or Chapters 11 through 43”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.51">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.1.3.2 to replace “by 9.3.5” with “by the AHJ or 9.3.5”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.52">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.2.1 by adding the following Subsection:</paragraph>
        <paragraph indent="2">13.2.1.3 On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, an approved sign must be mounted at the street front or on the side of the building.  Such sign must have the letters “FDC” not less than six (6) inches high and words in letters not less than two (2) inches high or an arrow to indicate the location of the connection.  Approved existing signs are permitted to remain in place.</paragraph>
      </subsection>
      <subsection heading="22.00.07.53">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.2.2.2 to add new item (6) that reads:</paragraph>
        <paragraph indent="2">Where the building code adopted by Montgomery County requires a Class III system, a Class I system is permitted.</paragraph>
      </subsection>
      <subsection heading="22.00.07.54">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.3.1.2 to add the following Subsection:</paragraph>
        <paragraph indent="2">13.3.1.2.1 For new ceiling installations, drop-out ceilings as referenced in NFPA 13, Subsections 9.2.16 and 9.3.11 are prohibited.</paragraph>
      </subsection>
      <subsection heading="22.00.07.55">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.3.1.8.2.1 to read:  “Where supervised automatic sprinkler protection is required by another section of this Code, waterflow alarms must be automatically transmitted to a listed central station.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.56">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.3.2.26.5 to delete existing wording and replace with the following:  An automatic sprinkler system must be installed throughout all mini-storage building fire areas greater than 2500 ft2 (232 m2) and where any of the individual storage units are separated by less than a 1-hour fire resistance-rated barrier.  Fire areas are defined by approved fire barriers having a fire resistance rating of not less than 3 hours.</paragraph>
      </subsection>
      <subsection heading="22.00.07.57">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.3.3.1 and 13.3.3.2 to delete the phrase “installed in accordance with this Code.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.58">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.4.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">13.4.1.1.1 A fire pump component, including the pump, driver, or controller, must be permitted to be installed in below-ground vaults or pits unless otherwise approved by the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.59">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.6.1.2 to add the phrase “, unless otherwise permitted by the AHJ.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.60">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.6.4.1.2.1 and 13.6.4.1.2.3 to replace “certified” with “certified or licensed as required by the AHJ”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.61">
        <paragraph indent="1">Delete Subsections 13.6.4.1.2.1.1,, 13.6.4.1.2.1.4, and 13.6.4.1.2.1.5.</paragraph>
      </subsection>
      <subsection heading="22.00.07.62">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.7.6 as follows:</paragraph>
        <paragraph indent="2">(1)   Add the following sentence to the end of the section:  “This Subsection does not permit the omission of manual fire alarm boxes in accordance with other provisions of this Subsection unless specifically permitted by Chapters 11 through 43.”</paragraph>
        <paragraph indent="2">(2)   Add two new Subsections as follows:</paragraph>
        <paragraph indent="3">13.7.1.7.6.1 Zoned fire alarm systems must have manual pull stations located at the entrance to each exit enclosure and at the main exit.</paragraph>
        <paragraph indent="3">13.7.1.7.6.2 When a fire alarm system is required in a multiple tenant building, for each tenant exiting directly to the exterior of the building, a manual pull station and approved occupant notification must be located at each required or marked exit.</paragraph>
      </subsection>
      <subsection heading="22.00.07.63">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.7.9 to add the following sentence:  “In environments not suitable for smoke detectors, alternate means of detection must be provided and must comply with NFPA 72 Section 10.3 (2019 edition).”</paragraph>
      </subsection>
      <subsection heading="22.00.07.64">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.9.2.1, delete the phrase “lobby,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.65">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.9.4 by deleting the wording after “without delay” and replacing it with:  to a listed central station in accordance with 13.7.1.10.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.66">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.9.8 by adding a second sentence to read:  “Required audibility must be met with all intervening doors (between any space and the audible devices) closed.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.67">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.9.10 as follows:</paragraph>
        <paragraph indent="2">(1)   amend 13.7.1.9.10, 13.7.1.9.10.1, and 13.7.1.9.10.2 to delete the word “live”;</paragraph>
        <paragraph indent="2">(2)   amend Subsection 13.7.1.9.10.2(1), delete the phrase, “, either live or recorded,”; and</paragraph>
        <paragraph indent="2">(3)   where voice type occupant notification is used, automatic pre-recorded messages must be used complying with Section 13.7.  Live voice as the sole notification method is prohibited – except that previously “approved” live voice systems are permitted to remain.</paragraph>
      </subsection>
      <subsection heading="22.00.07.68">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.10.2 by deleting the list of four items and replace the phrase “via any of the following means acceptable to the AHJ” with “by a listed central station fire alarm system”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.69">
        <paragraph indent="1">Delete NFPA 1, Subsections 13.7.1.10.3, 13.7.1.13.9.4, 13.7.1.13.9.5, 13.7.2.1.4.2(3), 13.7.2.3.4.2(5), 13.7.2.13.2.3(3), 13.7.2.14.6.3(3), 13.7.2.15.6.3(3), 13.7.2.16.6.3(3), 13.7.2.17.6.3(3), 13.7.2.18.5.4, 13.7.2.19.4.3(3), and 13.7.2.20.9.3(3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.70">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.1.11.2(3) by adding the following sentence:  “Manual fire alarm initiation must not activate floor or zone-dependent smoke control systems.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.71">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.7.2.3.1.2 and 13.7.2.4.1.2 to add Subsections 13.7.2.3.1.2.1 and 13.7.2.4.1.2.1 that reads:  For the purposes of this Section, each industrialized building, which is an independently certified unit serving as a portable or temporary classroom, must be considered a single building regardless of the number of units in the cluster sharing an egress system.</paragraph>
      </subsection>
      <subsection heading="22.00.07.72">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.7.2.5.5 and 13.7.2.6.5 to add the following exception:</paragraph>
        <paragraph indent="2">Exception:  Day-care occupancies located in school facilities where enrollment is limited to children capable of self-preservation, where no sleeping facilities are provided, and the school is provided with approved full automatic sprinkler protection.</paragraph>
      </subsection>
      <subsection heading="22.00.07.73">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.2.5.6.4 to add the following:  For compliance with NFPA 101, Subsection 43.7.2.1(2), approved battery-powered smoke alarms, rather than house electrical service-powered smoke alarms must be permitted where the facility has testing, maintenance, and smoke alarm replacement programs that ensure reliability of power to the smoke alarms.</paragraph>
      </subsection>
      <subsection heading="22.00.07.74">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.2.6.6.5 to delete “existing” and replace “battery” with “smoke alarm”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.75">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.2.13.1.3 to add at the end of the sentence:  “...only if the existing smoke alarms comply with Public Safety Article § 9-109, Annotated Code of Maryland.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.76">
        <paragraph indent="1">Amend NFPA 1, Subsections and 13.7.2.22.7.1 by adding at the end of the sentence, “...and have secondary battery back-up power.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.77">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.2.22.8.1 to delete “13.7.2.22.8.2 and”.  Delete Subsection 13.7.2.22.8.2.</paragraph>
      </subsection>
      <subsection heading="22.00.07.78">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.7.2.23.1 and 13.7.2.24.1 to delete the existing wording and replace as follows:  Class A mercantile occupancies and multiple story Class B mercantile occupancies must have a fire alarm system in accordance with Section 13.7 and NFPA 101.</paragraph>
      </subsection>
      <subsection heading="22.00.07.79">
        <paragraph indent="1">Amend NFPA 1, Subsections 13.7.2.28.1.2 and Section 13.7.2.28.1.3 to replace “Storage occupancies” with “Storage occupancies less than three stories”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.80">
        <paragraph indent="1">Amend NFPA 1, Subsection 13.7.2.29.3.1 by adding a new Subsection 13.7.2.29.3.1.1 as follows:</paragraph>
        <paragraph indent="2">13.7.2.29.2.1.1 In buildings having an approved staged evacuation plan, the voice fire alarm communication system must send approved information and direction in a pre-recorded message.  In high-rise buildings, the message must be provided to at least the floor where the alarm originated, to the floor immediately below, and to the floor immediately above.  Any subsequent alarm(s) on other than the initial fire floor must initiate the voice fire alarm as described above.  The voice fire alarm must be designed to be heard clearly by all occupants within the designated portions thereof as required by NFPA 101, Section 9.6, but it must not sound automatically in elevator cars and enclosed exit stairways.  Communicating levels must be considered one floor/fire area for the audible and visual fire alarm signals.</paragraph>
      </subsection>
      <subsection heading="22.00.07.81">
        <paragraph indent="1">Amend NFPA 1, Subsection 14.5.2.7 item (2) to add subitem “(d)”, and Subsection 14.5.2.7.1 to add item “(7)” that reads as follows:  “All stairway doors must unlock simultaneously, without unlatching, upon a signal from the emergency command center, if one is present.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.82">
        <paragraph indent="1">Amend NFPA 1, Subsection to add an item (6), to read:</paragraph>
        <paragraph indent="2">(6)   Entry levels must provide free access to an approved second exit.  These levels must be designated in “core/shell” building permit drawings with future tenant layouts arranged accordingly.</paragraph>
      </subsection>
      <subsection heading="22.00.07.83">
        <paragraph indent="1">Amend NFPA 1, Table 14.8.1.2 to add the following:</paragraph>
        <paragraph indent="0">Use |  | (ft 2 per person) | (m 2 per person)
Assembly Use | Tennis court (area of play) | 50 net | 15.24 net
Assembly Use | Bars g | 18 linear in./person | 455 linear mm/person
Business Use | Core/shell | 65 (gross) | 6 (gross)
g :  Measured at the patron side of the bar</paragraph>
      </subsection>
      <subsection heading="22.00.07.84">
        <paragraph indent="1">Amend NFPA 1, Subsection 14.13.1.2 to replace the word “only” in the first sentence with “, but not be limited to,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.85">
        <paragraph indent="1">Amend NFPA 1, Subsection 14.14.8.3.1 to add:  If the sign is on the door, then the door must be equipped with an approved self-closing device.</paragraph>
      </subsection>
      <subsection heading="22.00.07.86">
        <paragraph indent="1">Amend NFPA 1, Section 18.1 to add the following Subsections:</paragraph>
        <paragraph indent="2">18.1.1.3 Alternative Application.  The alternative application of performance-based design, as specified in Chapter 5 of NFPA 1, Fire Code, may be used to achieve compliance with any fire department apparatus access requirement.  Performance-based design is intended to address a construction method or practice that cannot be effectively addressed by prescriptive code.  An appropriate, alternative design which provides an equivalent level of safety or protection must be proposed.  Use of performance-based design is at the discretion of the design professional and is subject to approval by the Director.  It is the intent of this Subsection to be administered in a manner consistent with The Fire Department Access Guidelines Document, Chapter 49, Streets and Roads, of the Montgomery County Code, and its executive regulations.</paragraph>
        <paragraph indent="2">18.1.1.4 Definitions.  For the purposes of fire department access and water supply, the following definitions apply:</paragraph>
        <paragraph indent="2">(1)   Fire Department Apparatus Access.  Any required public, private, or access roads, driveways, parking lots, shoulders, and buffers, whose use is required to allow access and operational setup for firefighting and rescue apparatus.  Not all roadways are required for fire department apparatus access.  The Director may require, and must approve, all suitable gates, access boxes, and fire lanes to ensure adequate fire department apparatus access.</paragraph>
        <paragraph indent="2">(2)   One- and Two-Family Dwellings.  Detached one- and two-family dwellings and attached single-family dwellings (townhomes) not more than three stories in height, with no dwellings superimposed over the dwelling or portion thereof, and having no window opening or visual wall treatments that resemble a window opening, greater than 27 feet above adjoining grade measured to the bottom of the opening, with a separate, independent means of egress.</paragraph>
        <paragraph indent="2">(3)   Commercial Residential:  Any apartment building as defined by NFPA 101, and any townhouse greater than three stories in height, having a window opening with an exterior height greater than 27 feet above adjoining grade measured to the bottom of the opening, or having a dwelling superimposed over another dwelling or portion thereof, will need to meet “commercial” requirements with regard to fire department access requirements.</paragraph>
        <paragraph indent="2">(4)   Operating Bay.  Clear and unobstructed fire department apparatus load bearing surface along fire department apparatus access that increases operating width to a minimum of 26 feet wide.  It may be defined by bollards and accessed via 3-inch mountable curb.  The minimum length of an operating bay is 50 feet.</paragraph>
      </subsection>
      <subsection heading="22.00.07.87">
        <paragraph indent="1">Amend NFPA 1, to add new Subsection 18.1.3.1.1 that reads:  A fire department apparatus access plan may be required as part of any development or re-development plan.</paragraph>
      </subsection>
      <subsection heading="22.00.07.88">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.1.3.2 to delete the existing wording and replace with the following:  Existing and proposed fire hydrant locations in accordance with 18.5 must be indicated on the fire department access plan for review and approval by the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.89">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.2.1, to add two new Subsections as follows:</paragraph>
        <paragraph indent="2">18.2.2.1.1 All occupancies other than one- and two-family dwellings must have an approved access box.</paragraph>
        <paragraph indent="2">Exception 1:  The requirement for an access box does not apply when the occupancy provides 24-hour on-site staffing with access to all areas in the building or complex.  At least one person is required to staff a fixed location proximate to the main building or complex entrance to provide immediate access for the fire department.</paragraph>
        <paragraph indent="2">Exception 2:  For multiple occupancies located within a single structure, a single access box is permitted with approval of the AHJ.</paragraph>
        <paragraph indent="2">Exception 3:  For multiple structures within a residential building complex, a single access box is permitted with approval of the AHJ.</paragraph>
        <paragraph indent="2">18.2.2.1.2 The size, contents, and location of the access box must be determined by the AHJ in cooperation with the occupancy owner or management.</paragraph>
      </subsection>
      <subsection heading="22.00.07.90">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.2.1 to replace the phrase “exterior door” with “exterior door acceptable to the AHJ” and add the following sentence:  “In new installations, not less than one exit stair which serves all stories of the building must be accessible by an internal corridor from the main entrance of the building or fire department response location.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.91">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.2.2 to add the following sentence at the end of the Subsection:  “The exterior route around the building(s), including townhomes of any height in clusters of four (4) or more, must be at least 15 feet of unobstructed, walkable grade unless otherwise approved by the Director.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.92">
        <paragraph indent="1">Delete NFPA 1, Subsection 18.2.3.4.</paragraph>
      </subsection>
      <subsection heading="22.00.07.93">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.5.1.1 to add the following sentence and Subsections:</paragraph>
        <paragraph indent="1">Unobstructed width may include multiple features of the cross-section, such as travel lanes, bike lanes, and load-bearing shoulders provided the width is continuous and no obstructive features intervene in the cross-section.  Obstructive features include, but are not limited to, parking lanes, green space, and non-mountable curbs.</paragraph>
        <paragraph indent="2">(1)   On-street parking is permitted on one side if the fire department apparatus access is at least 28 feet wide.</paragraph>
        <paragraph indent="2">(2)   On-street parking is permitted on both sides if the fire department apparatus access is at least 36 feet wide.</paragraph>
        <paragraph indent="2">(3)   Fire department apparatus access serving only one- and two-family dwellings may be 26 feet wide and allow parking on one side, if there are 50-foot long operating bays at 300-foot intervals.</paragraph>
      </subsection>
      <subsection heading="22.00.07.94">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.5.2 to delete the existing wording and replace with the following:  Fire apparatus access roads must be provided with an all-weather surface and designed to support imposed loading requirements of the largest MCFRS fire apparatus.  Elevated decks designated as “fire department apparatus access” must have an all-weather surface and be load-bearing up to 75 pounds per square inch, as specified in the 2016 NFPA 1901, Standard for Automotive Fire Apparatus, Section 19.21, or as approved by the Director.</paragraph>
      </subsection>
      <subsection heading="22.00.07.95">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.5.3.1 to delete the existing wording and replace with the following:  The minimum interior turning radius for a fire department apparatus access roadway is 25 feet.  The minimum exterior turning radius for a fire department apparatus access roadway is 50 feet.  This is only required at turning points on fire department apparatus access routes.</paragraph>
      </subsection>
      <subsection heading="22.00.07.96">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.2.3.5.4 to add the following at the end of the sentence:  A cul-de-sac at the closed end must be at least 90 feet in diameter, and a “T-turnaround” must have each leg of the tee at least 60 feet long and 20 feet wide.</paragraph>
      </subsection>
      <subsection heading="22.00.07.97">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.3.1.1 to delete the existing wording and replace with the following:  “In non-municipally supplied areas, static water sources must comply with the 2017 edition of NFPA 1142, Water Supplies for Suburban and Rural Firefighting.  Existing roads providing a means of access to a required water supply must comply with the minimum criteria set forth in Section 7.5 of the 2017 edition of NFPA 1142.  The minimum water supply must be available and accessible prior to any new construction.</paragraph>
        <paragraph indent="2">(1)   If an acceptable water supply does not exist at the time of subdivision of any new residential development or redevelopment, comprised of more than one one- or two-family dwellings, with fire department access roads for the development having aggregate travel distance of 2200 feet or more, adequate fire department water supply must be provided.</paragraph>
        <paragraph indent="2">(2)   If an acceptable water supply does not exist on-site and within 1,000 feet of the structure(s) for any new commercial development or redevelopment, the applicant must install a new, or upgrade an existing, on-site water supply that is acceptable to the Director.</paragraph>
        <paragraph indent="3">a.   A dry hydrant, in accordance with Chapter 8 of NFPA 1142, must be located along an approved fire apparatus access road in accordance with Section 18.5.</paragraph>
        <paragraph indent="3">b.   The approved water supply must comply with NFPA 1, Section 18.4.</paragraph>
      </subsection>
      <subsection heading="22.00.07.98">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.5.1 to add “and existing” after the words “all new” and before the word “building,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.99">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.5.1.6 to replace “12 ft (3.7 m)” with “7 ft (2.1 m)”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.100">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.5.2, items (1) and (2) to replace “600 ft. (183 m)” and “800 ft (244 m)”, with “400 ft (122 m)” and “500 ft (152 m)”, respectively.</paragraph>
      </subsection>
      <subsection heading="22.00.07.101">
        <paragraph indent="1">Amend NFPA 1, Subsection 18.5.4.2 to delete the existing wording and replace with the following:  For new and existing structures, the hydrant closest to the property must be capable of delivering a minimum flow of 1,000 gallons-per-minute with 20 psi residual pressure calculated at the non-flowing hydrant.  The next closest hydrant must be capable of flowing a minimum of 500 gallons-per-minute at the same time.</paragraph>
      </subsection>
      <subsection heading="22.00.07.102">
        <paragraph indent="1">Amend NFPA 1, Subsection 20.2.4.2.3 to delete the existing wording and replace with the following:</paragraph>
        <paragraph indent="2">Fire emergency egress drills must be conducted as follows:</paragraph>
        <paragraph indent="2">(1)   not less than one fire emergency egress drill must be conducted every month the facility is in session, unless the following criteria are met:</paragraph>
        <paragraph indent="3">(a)   in climates where the weather is severe, the monthly fire emergency egress drills are permitted to be deferred; and</paragraph>
        <paragraph indent="3">(b)   in educational occupancies which are:</paragraph>
        <paragraph indent="4">(i)   fully protected by an automatic sprinkler system, the total number of annual fire emergency egress drills will be five (5), with at least two (2) of the required drills must be conducted in the first four (4) months of the school year; or</paragraph>
        <paragraph indent="4">(ii)   not fully protected by an automatic sprinkler system, the total number of annual fire emergency egress drills must be eight (8) with at least three (3) of the required drills conducted in the first four (4) months of the school year;</paragraph>
        <paragraph indent="2">(2)   all occupants of the building must participate in the fire emergency egress drill; and</paragraph>
        <paragraph indent="2">(3)   one (1) fire emergency egress drill, other than for educational occupancies that are open on a year-round basis, must be required within the first 30 days of operation.</paragraph>
      </subsection>
      <subsection heading="22.00.07.103">
        <paragraph indent="1">Amend NFPA 1, Subsections 20.3.4.1.1 and 20.3.4.1.2 to delete the phrase “more than 3, but” and the “,” after “12”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.104">
        <paragraph indent="1">Amend NFPA 1, Subsection 20.3.4.1.6 to delete the wording after “where operating” and replace with the following:  “a day-care in which eight or less clients receive care, maintenance, or supervision while services are being held in the building.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.105">
        <paragraph indent="1">Amend NFPA 1, Subsection 20.3.4.2.2.2(3) to replace the word “building” with “day-care”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.106">
        <paragraph indent="1">Amend NFPA 1, to add new Subsection 20.16.1.3 that reads as follows:  “In new buildings, where the aggregate gross floor area exceeds 100,000 square feet, or where the floor of an occupiable story is greater than 75 ft (23 m) above the lowest level of fire department vehicle access, an emergency command center, in accordance with Section 11.9, is required.  Exception:  Buildings or structures used exclusively for open-air parking.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.107">
        <paragraph indent="1">Amend NFPA 1, Subsection 25.2.2.1 to add the phrase “or other approved testing standard approved by the State Fire Marshal”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.108">
        <paragraph indent="1">Amend NFPA 1, Subsection 26.1.5 to add the following Subsections:</paragraph>
        <paragraph indent="2">26.1.5.2 When requested by the AHJ, a hazard assessment must be conducted by a technically qualified person acceptable to the AHJ.</paragraph>
        <paragraph indent="2">26.1.5.3 When requested by the AHJ, a list of hazardous materials used in each laboratory must be provided.  The list must specify the chemical name, quantity and hazard class.</paragraph>
        <paragraph indent="2">26.1.5.4 New laboratories or laboratories where the NFPA 45 laboratory hazard classification changes must post an information placard near the main entrance to the laboratory.  The placard must state the building name or address, room number, NFPA 45 laboratory hazard classification, edition of NFPA 45, maximum allowable quantities of flammable liquids both inside a storage cabinet and open use, and maximum quantities of flammable gases permitted within the laboratory.</paragraph>
      </subsection>
      <subsection heading="22.00.07.109">
        <paragraph indent="1">Amend NFPA 1, Subsection 31.3.6.2.2 to add the following item:</paragraph>
        <paragraph indent="2">(9)   Piles containing leaves and other extraneous or hogged material, such as whole tree chip piles, must be turned or reclaimed at least every 3 months.</paragraph>
      </subsection>
      <subsection heading="22.00.07.110">
        <paragraph indent="1">Amend NFPA 1, Subsection 31.3.6.3.2 to delete the existing wording and replace with the following:</paragraph>
        <paragraph indent="2">Piles may not exceed 20 feet in height, 50 feet in width, and 350 feet in length.</paragraph>
      </subsection>
      <subsection heading="22.00.07.111">
        <paragraph indent="1">Amend NFPA 1, Subsection 34.1.3 to replace “An approved storage” with “Where required by the AHJ, an approved storage”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.112">
        <paragraph indent="1">Delete NFPA 1, Chapter 35, Animal Housing Facilities.</paragraph>
      </subsection>
      <subsection heading="22.00.07.113">
        <paragraph indent="1">Amend NFPA 1, Subsection 38.6.1.6.1.4 to replace “or approved” with “or certified by a nationally recognized testing laboratory”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.114">
        <paragraph indent="1">Amend NFPA 1, Section 42.7.5 to add the following Subsections:</paragraph>
        <paragraph indent="2">42.7.5.7 Management/owners officials or employees must conduct daily site visits to ensure that all equipment is operating properly.</paragraph>
        <paragraph indent="2">42.7.5.8 Regular equipment inspection and maintenance at the unattended self- service facility must be conducted.</paragraph>
        <paragraph indent="2">42.7.5.9 Fuel dispensing equipment must comply with one of the following:</paragraph>
        <paragraph indent="2">(1)   The amount of fuel being dispensed is limited in quantity by preprogrammed card; or</paragraph>
        <paragraph indent="2">(2)   Dispensing devices must be programmed or set to limit uninterrupted fuel delivery of not more than 25 gallons and must require a manual action to resume continued delivery.</paragraph>
      </subsection>
      <subsection heading="22.00.07.115">
        <paragraph indent="1">Amend NFPA 1, Subsection 42.7.5.5 to add the following:</paragraph>
        <paragraph indent="2">The following information must be conspicuously posted in this area:</paragraph>
        <paragraph indent="2">(1)   the exact address of the unattended self-service facility; and</paragraph>
        <paragraph indent="2">(2)   the telephone number of the owner or operator of the unattended self- service facility.</paragraph>
      </subsection>
      <subsection heading="22.00.07.116">
        <paragraph indent="1">Amend NFPA 1, Subsection 50.8.1 to add the following Subsections:</paragraph>
        <paragraph indent="2">50.8.1.7 Commercial Outdoor Cooking Operations.  These requirements apply to commercial outdoor cooking operations such as those that typically take place under a canopy or tent-type structure at fairs, festivals and carnivals.  This includes, but is not limited to, deep frying, sauteing, and grilling operations.</paragraph>
        <paragraph indent="3">50.8.1.7.1 Tent and Canopy Requirements.</paragraph>
        <paragraph indent="4">50.8.1.7.1.1 Tents or canopies where cooking equipment not protected in accordance with NFPA 96 are not permitted unless otherwise approved by the AHJ.</paragraph>
        <paragraph indent="4">50.8.1.7.1.2 All tent and canopy material must comply with flame resistance requirements of Section 25.2.2.</paragraph>
        <paragraph indent="3">50.8.1.7.2 LP Gas Fuel Requirements.</paragraph>
        <paragraph indent="4">50.8.1.7.2.1 LP gas tank size is limited to 60 pounds.  The total amount of LP gas on site must not exceed 60 pounds for each appliance that is rated not more than 80,000 btu/hr and 120 pounds for each appliance rated more than 80,000 btu/hr.</paragraph>
        <paragraph indent="4">50.8.1.7.2.2 Tanks must be maintained in good physical condition and must have a valid hydrostatic date stamp.</paragraph>
        <paragraph indent="4">50.8.1.7.2.3 Tanks must be secured in their upright position with a chain, strap, or other approved method that prevents the tank from tipping over.</paragraph>
        <paragraph indent="4">50.8.1.7.2.4 Tanks must be located so that they are not accessible to the public.  LP gas tanks must be located at least 5 feet from any cooking or heating equipment or any open flame device.</paragraph>
        <paragraph indent="4">50.8.1.7.2.5 All LP gas equipment must be properly maintained and comply with the requirements of NFPA 58.</paragraph>
        <paragraph indent="4">50.8.1.7.2.6 Regulators.  Single-stage regulators must not supply equipment that is rated more than 100,000 btu/hr rating.  Two-stage regulators must be used with equipment that is rated more than 100,000 btu/hr.</paragraph>
        <paragraph indent="3">50.8.1.7.3 General Safety Requirements.</paragraph>
        <paragraph indent="4">50.8.1.7.3.1 All electrical cords must be maintained in a safe condition and must be secured to prevent damage.</paragraph>
        <paragraph indent="4">50.8.1.7.3.2 Moveable cooking equipment must have wheels removed or must be placed on blocks or otherwise secured to prevent movement of the appliance during operation.</paragraph>
        <paragraph indent="4">50.8.1.7.3.3 Portable fire extinguishers must be provided in accordance with NFPA 1, Section 13.6, and must be specifically listed for such use.</paragraph>
        <paragraph indent="2">50.8.1.8 There must be no obstructions or impediments to immediate escape from vehicles or other mobile units used for cooking operations.</paragraph>
      </subsection>
      <subsection heading="22.00.07.117">
        <paragraph indent="1">Amend NFPA 1, Subsection 50.8.7.4.4 to replace “not be transported or stored inside the vehicle” with “be secured in an upright position during transport and storage”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.118">
        <paragraph indent="1">Amend NFPA 1, 52.1.1 to add the following to the end of the sentence:  “and NFPA 855.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.119">
        <paragraph indent="1">Amend NFPA 1, Chapter 52, to add the following Section and Subsections:</paragraph>
        <paragraph indent="1">52.10 ELECTRICAL VEHICLE (EV) CHARGING STATIONS.</paragraph>
        <paragraph indent="2">52.10.1 General.  The provisions of this Section apply to installation of electric vehicle charging stations.  Exception:  EV charging station(s) in Group R-4 occupancies must comply with Section 52.10.11.</paragraph>
        <paragraph indent="2">52.10.2 Construction documents.  The following information must be provided with the permit application:</paragraph>
        <paragraph indent="3">(1)   location and layout diagram of the room or area in which the EV charging station is to be installed;</paragraph>
        <paragraph indent="3">(2)   the quantities and types of EV charging station(s) to be installed;</paragraph>
        <paragraph indent="3">(3)   manufacturer’s specifications, ratings and listings of each EV charging station;</paragraph>
        <paragraph indent="3">(4)   description of energy (battery) management systems and their operation;</paragraph>
        <paragraph indent="3">(5)   location and content of required signage;</paragraph>
        <paragraph indent="3">(6)   details on fire suppression of the EV charging station, including but not limited to, smoke or fire detection, thermal management, ventilation, exhaust and deflagration venting systems, if provided; and</paragraph>
        <paragraph indent="3">(7)   support arrangement associated with the installation, including any required seismic restraint.</paragraph>
        <paragraph indent="2">52.10.3 Installation and listing.  Where provided, electric vehicle charging stations must be installed in accordance with NFPA 70.  Electric vehicle charging station equipment must be listed and labeled in accordance with UL 2202.  Electric vehicle supply equipment must be listed and labeled in accordance with UL 2594.</paragraph>
        <paragraph indent="3">52.10.3.1 Electrical disconnects.  Where the EV charging station disconnecting means is not within sight of the main electrical service disconnecting means, placards or directories must be installed at the location of the main electrical service disconnecting means indicating the location of EV charging station(s) disconnecting means in accordance with NFPA 70.</paragraph>
        <paragraph indent="3">52.10.3.2 Vehicle impact protection.  Where EV charging station are subject to impact by a motor vehicle, impact protection must be provided.</paragraph>
        <paragraph indent="2">52.10.4 Location.</paragraph>
        <paragraph indent="2">52.10.5 Fire detection.  An approved automatic smoke detection system or radiant energy-sensing fire detection system must be installed in the EV charging station area where located in enclosed parking garages.  An approved radiant energy-sensing fire detection system must be installed to protect open parking garage and rooftop installations.  Alarm signals from detection systems must be transmitted to a central station in accordance with NFPA 72.</paragraph>
        <paragraph indent="3">52.10.5.1 System status.  Visible annunciation must be provided on cabinet exteriors or in other approved locations to indicate that potentially hazardous conditions associated with the EV charging station are present.</paragraph>
        <paragraph indent="3">52.10.5.3 Elevation.  EV charging station cannot be located in the following areas:</paragraph>
        <paragraph indent="4">(1)   where the floor is located more than 75 feet (22,860 mm) above the lowest level of fire department vehicle access;</paragraph>
        <paragraph indent="4">(2)   where the floor is located more than one level below the lowest level of exit discharge;</paragraph>
        <paragraph indent="2">52.10.6 Fire suppression systems:  Enclosed parking garages containing EV charging stations mut be protected by an automatic sprinkler system designed and installed in accordance with the following:</paragraph>
        <paragraph indent="3">(1)   an automatic sprinkler system designed and installed in accordance with Section 903.3.1.1 with a minimum density of 0.3 gpm/ft2 91.14 L/min) based on the fire area or 2,500 square-foot (232 m2) design area, whichever is smaller.</paragraph>
        <paragraph indent="2">52.10.7 Reserved.</paragraph>
        <paragraph indent="2">52.10.8 Exhaust ventilation.  Where installed in enclosed parking garages, exhaust ventilation of areas and containing EV charging stations must be provided in accordance with the International Mechanical Code and Section 52.10.8.1 or 52.10.8.2.</paragraph>
        <paragraph indent="3">52.10.8.1. Ventilation based on LFL.  The exhaust ventilation system must be designed to limit the maximum concentration of flammable gas to 25 percent of the lower flammable limit (LFL) of the total volume of the room, area or walk-in unit during the worst-case event of simultaneous charging of batteries at the maximum charge rate, in accordance with nationally recognized standards.</paragraph>
        <paragraph indent="3">52.10.8.2 Ventilation based on exhaust rate.  Mechanical exhaust ventilation must be provided at a rate of not less than 1 ft3/min/ft2 (5.1 L/sec/m2) of floor 
									area of the room, aera or walk-in unit.  The ventilation must be either continuous or shall be activated by a gas detection system in accordance with Section 432.6.1.2.4.</paragraph>
        <paragraph indent="4">52.10.8.2.1 Standby power.  Mechanical exhaust ventilation must be provided with a minimum of 2 hours of standby power in accordance with NFPA 1, Section 11.7.4.</paragraph>
        <paragraph indent="4">52.10.8.2.2 Installation instructions.  Required mechanical exhaust ventilation systems must be installed in accordance with the manufacturer’s installation instructions and the International Mechanical Code.</paragraph>
        <paragraph indent="4">52.10.8.2.3 Supervision.  Required mechanical exhaust ventilation systems must be supervised in accordance with NFPA 72 or initiate an audible and visible signal at an approved constantly attending on-site location.</paragraph>
        <paragraph indent="2">52.10.9 Separation.  The EV charging station must be separated from doors, windows, operable openings into buildings or HVAC inlets by at least 10 feet (1,524 mm).</paragraph>
        <paragraph indent="3">52.10.9.1 Means of egress separation from EV charging station.  EV charging stations located outdoors and in open parking garages must be separated from any exit or exit component as required by the AHJ to ensure safe egress from the EV charging station under fire conditions, but in no case can an EV charging station be separated by less than 10 feet (3,048 mm).  EV charging stations located in enclosed parking structures must be located no less than 25 feet from any exit door.</paragraph>
        <paragraph indent="2">52.10.10 Special installations.  Rooftop and open parking garage EV charging station installments must comply with this section.</paragraph>
        <paragraph indent="3">(1)   A Class 1 standpipe outlet must be installed at an approved location on the roof level of the building or in the stairway at the top level.</paragraph>
        <paragraph indent="3">(2)   The EV charging station must be the minimum of 10 feet (3,048 mm) from the fire service access point on the rooftop.</paragraph>
        <paragraph indent="2">52.10.11 Spill control and neutralization.  Areas containing free-flowing liquid electrolyte or hazardous materials must be provided with spill control and neutralization in accordance with this section.</paragraph>
        <paragraph indent="3">52.10.11.1 Spill control.  Spill control must be provided to prevent the low of liquid electrolyte or hazardous materials to adjoining rooms or areas.</paragraph>
        <paragraph indent="3">52.10.11.2 Neutralization.  An approved method that is capable of neutralizing spilled liquid electrolyte from the largest battery or vessel to a pH between 5.0 and 9.0 must be provided.</paragraph>
      </subsection>
      <subsection heading="22.00.07.120">
        <paragraph indent="1">Amend NFPA 1, Section 65.1 to add the following Subsections:</paragraph>
        <paragraph indent="1">65.1.3 Blasting Operations General Requirements.</paragraph>
        <paragraph indent="2">65.1.3.1 Notifications.  Written notification by e-mail or facsimile must be provided to the Office of the State Fire Marshal Bomb Squad at least 24 hours prior to each blast.  The name of the company or contractor performing the blasting and the location, date, and approximate time must be identified.  The geographical coordinates (longitude and latitude) must be provided.</paragraph>
        <paragraph indent="2">65.1.3.2 Complaints.  If requested by a property owner registering a complaint and considered necessary by the State Fire Marshal, measurements on three consecutive blasts, using approved instrumentation, must be made near to the structure in question.</paragraph>
        <paragraph indent="2">65.1.3.3 Special Precautions.  When blasting operations, other than those conducted at a fixed site such as a quarry, are to be conducted within 200 feet of a pipeline or high voltage transmission line, the contractor must take additional precautionary measures and must notify the owner of the line, or the owner’s agent, that blasting operations are intended.  Approval documents from the utility purveyor must be provided to DPS for review prior to issuance of the blasting permit.</paragraph>
        <paragraph indent="2">65.1.3.4 Reports.  Blasting reports must be provided to the Montgomery County Fire Code Compliance section within one (1) business day of blasting instances.  The reports must contain information as noted in Subsection 10.4.4.3 of NFPA 495, Explosive Materials Code, 2018 edition.</paragraph>
        <paragraph indent="2">65.1.3.5 Sale and Use of Heaters and Stoves.</paragraph>
        <paragraph indent="3">65.1.3.5.1 Gasoline Stoves.  The sale or use of gasoline stoves or other similar fuel-burning cooking or heating appliances using Class I flammable liquids as defined in NFPA 1 Fire Code (2021 edition) and NFPA 30 Flammable and Combustible Liquids Code (2021 edition) is prohibited unless the appliance has been tested and listed by a testing laboratory accepted by the State Fire Marshal.  The appliance must be installed, operated, and maintained in a safe manner in accordance with the prescribed recommendation of the manufacturer and the conditions stated in the listing by the respective testing laboratory.</paragraph>
        <paragraph indent="3">65.1.3.5.2 Unvented Portable Kerosene-Fired Heaters.</paragraph>
        <paragraph indent="4">(1)   The sale or use of unvented portable kerosene-fired heaters is permitted only if the heater or appliance meets the U.L.  Subject 647 and bears the label of a testing laboratory accepted by the State Fire Marshal.</paragraph>
        <paragraph indent="4">(2)   The heaters must only be used as permitted under Commercial Law Article, § 14-1310, Annotated Code of Maryland.</paragraph>
        <paragraph indent="4">(3)   Each heater must contain a warning label stating:  “This device must not be operated while unattended”.  In addition, the heater must contain the manufacturer’s warning label required by Commercial Law Article, § 14-1310, Annotated Code of Maryland.</paragraph>
        <paragraph indent="1">22.00.07.121</paragraph>
        <paragraph indent="1">Delete NFPA 13, Subsection 8.2.3.6.1.</paragraph>
      </subsection>
      <subsection heading="22.00.07.122">
        <paragraph indent="1">Amend NFPA 13, Subsection 8.2.5, and add the following Subsection 8.2.5.1.1:  Dry pipe systems may only be installed where heat is not adequate to prevent freezing.</paragraph>
      </subsection>
      <subsection heading="22.00.07.123">
        <paragraph indent="1">Amend NFPA 13, add new Subsection 9.2.3.6 that reads as follows:</paragraph>
        <paragraph indent="2">9.2.3.6 Sprinklers are required under attached balconies or porches unless at least 50 percent of the longest exterior side is open to the atmosphere.</paragraph>
      </subsection>
      <subsection heading="22.00.07.124">
        <paragraph indent="1">Amend NFPA 13, to add Subsection 9.4.2.1.1, that reads as follows:  In dwelling units, ordinary temperature rated sprinklers must be used.</paragraph>
      </subsection>
      <subsection heading="22.00.07.125">
        <paragraph indent="1">Amend NFPA 13, Subsection 9.4.2.4, to add the following:  Immediate temperature sprinkler heads can only be installed in a high temperature area if an acceptable layout cannot be achieved with an ordinary temperature sprinkler head.</paragraph>
      </subsection>
      <subsection heading="22.00.07.126">
        <paragraph indent="1">Amend NFPA 13, Section 12.1 as follows:  Listed residential sprinkler heads must be used in dwelling units and must be selected for use and installation as indicated in this Chapter and be positioned and spaced in accordance with Section 9.5.</paragraph>
      </subsection>
      <subsection heading="22.00.07.127">
        <paragraph indent="1">Amend NFPA 13, adding Subsection 11.1.1 that reads as follows:  Extended coverage sprinklers are not permitted in speculative business and mercantile occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.07.128">
        <paragraph indent="1">Amend NFPA 13, adding Subsection 9.2.1.19.6 that reads as follows:  Any canopy with the potential for extended vehicle standing or parking below must have sprinkler protection on the underside of the canopy.</paragraph>
      </subsection>
      <subsection heading="22.00.07.129">
        <paragraph indent="1">Amend NFPA 13, Subsection 9.2.1.7 that reads as follows:  Combustible spaces filled with a listed non-combustible insulation do not require sprinkler protection and an additional insulation inspection is required prior to concealment.</paragraph>
      </subsection>
      <subsection heading="22.00.07.130">
        <paragraph indent="1">Amend NFPA 13, Subsection 9.2.4.2 to add new Subsection 9.2.4.2.1 that reads as follows:</paragraph>
        <paragraph indent="2">9.2.4.2.1 When sprinklers are required, sprinklers must not be installed directly above shelving.</paragraph>
      </subsection>
      <subsection heading="22.00.07.131">
        <paragraph indent="1">Amend NFPA 13, Subsection 9.3.11.1 to delete the wording and replace with the following:  For new ceiling installations, drop-out ceilings are prohibited.</paragraph>
      </subsection>
      <subsection heading="22.00.07.132">
        <paragraph indent="1">Amend NFPA 13, Subsections 16.9.3.1.1 and 16.11.2.1 to add:  When a sprinkler system serves more than one level, each level must be consistently and separately valved by a listed and approved control valve.  In addition, where a sprinkler system is required to activate a building fire alarm system, the sprinkler system must have a separate and distinct water flow detecting device for each floor and zone.</paragraph>
        <paragraph indent="2">Exception 1:  In buildings not exceeding three floors and 3,000 square feet per floor.</paragraph>
        <paragraph indent="2">Exception 2:  Unoccupied and unused attics may be zoned with the level below.</paragraph>
        <paragraph indent="2">Exception 3:  Mezzanines not exceeding 3,000 square feet in area.</paragraph>
        <paragraph indent="2">Exception 4:  Detention and correctional facilities.</paragraph>
      </subsection>
      <subsection heading="22.00.07.133">
        <paragraph indent="1">Amend NFPA 13, Section 16.12 to add the following requirements for fire department connections:</paragraph>
        <paragraph indent="0">System Demand (gpm) | No. of Inlets
Up to 749 | 2
750-999 | 3
1,000 and above | 4</paragraph>
        <paragraph indent="2">(1)   Must be located within 100 feet of a fire hydrant, and between 18 and 48 inches from grade to the centerline of the inlets.</paragraph>
        <paragraph indent="2">(2)   Multiple connects on the same building must be interconnected.</paragraph>
        <paragraph indent="2">(3)   When a section of a building is fed by a connection (i.e., partial systems), permanent all-weather identification signs must be provided on connections.</paragraph>
        <paragraph indent="2">(4)   Must be sized at least as large as the main sprinkler system riser pipe or the fire pump discharge line, whichever is larger.</paragraph>
      </subsection>
      <subsection heading="22.00.07.134">
        <paragraph indent="1">Amend NFPA 13, Subsection 19.2.1 to delete the wording and replace with the following:  Calculations for new systems or new portions of systems must meet the criteria below.</paragraph>
        <paragraph indent="2">(1)   Highest hazard and most demanding use allowed by building construction permit or property zoning.</paragraph>
        <paragraph indent="2">(2)   Storage use:  Available storage height for high storage of a class 4 non-encapsulated material.</paragraph>
        <paragraph indent="2">(3)   All uses:  20% safety factor.  For systems without a pump, this is based on the demand pressure only at the supply point.  For systems with a pump, this is based on both the demand pressure and demand flow at the pump discharge.  All design options, except grids in speculative buildings, must be explored.</paragraph>
        <paragraph indent="2">Exception to safety factor only:  Owner-occupied buildings may use a lower safety factor if a pump would be necessary to achieve the 20%.</paragraph>
      </subsection>
      <subsection heading="22.00.07.135">
        <paragraph indent="1">Amend NFPA 13, Subsection 19.3.2.3 to delete (3) and (4).</paragraph>
      </subsection>
      <subsection heading="22.00.07.136">
        <paragraph indent="1">Amend NFPA 13, Subsection 5.1.2 to add:  Pressure and flow availability as determined by a hydraulic information sheet received from a public utility must be used for new taps.  Pressure and flow availability for existing taps must be determined by an interior flow test.  In any case, the supply information must be corrected for the law hydraulic gradient.  Fire pumps and fire pump/tank supplies must only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.07.137">
        <paragraph indent="1">Amend NFPA 13, Section 28.1 to add:</paragraph>
        <paragraph indent="2">(5)   Finished surfaces must be completed within a 1 ft radius of sprinkler heads.</paragraph>
      </subsection>
      <subsection heading="22.00.07.138">
        <paragraph indent="1">Amend NFPA 13, Subsection 28.2.1.8 to add a third sentence:  Pendent sprinkler heads must not be installed in plastic pipe until after the hydrostatic test is passed.</paragraph>
      </subsection>
      <subsection heading="22.00.07.139">
        <paragraph indent="1">Amend NFPA 13D, Subsection 1.1.1 to add a second sentence:  This standard also applies to Day Care homes containing 12 clients or less if located within converted one- and two-family dwellings or townhouses.</paragraph>
      </subsection>
      <subsection heading="22.00.07.140">
        <paragraph indent="1">Amend NFPA 13D, Subsection 6.1.1 to add:  Pressure and flow availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may be used only where it is demonstrated that the public water supply is inadequate as determined by the Director of the Department of Permitting Services</paragraph>
      </subsection>
      <subsection heading="22.00.07.141">
        <paragraph indent="1">Amend NFPA 13D to add a new Subsection 6.1.1.1 that reads as follows:  All calculations must include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.07.142">
        <paragraph indent="1">Amend NFPA 13D, Section 6.2 to add a new item that reads as follows:</paragraph>
        <paragraph indent="2">(6)   System specific data plate on durable material to be fixed at sprinkler system main riser.</paragraph>
      </subsection>
      <subsection heading="22.00.07.143">
        <paragraph indent="1">Amend NFPA 13D, Subsection 7.5.6.1 to add:  Where possible to maintain listed coverage, sprinkler heads must be positioned so as to eliminate the need to install sprinkler heads of a higher temperature rating.</paragraph>
      </subsection>
      <subsection heading="22.00.07.144">
        <paragraph indent="1">Amend NFPA 13D, Subsection 8.2.5.1 to add new Subsection 8.2.5.1.5:</paragraph>
        <paragraph indent="2">8.2.5.1.5 Sprinkler heads in closets must not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.07.145">
        <paragraph indent="1">Amend NFPA 13D, Subsection 8.3.4 to add the following after the word “garages”:  “, unless located partially or wholly beneath living space.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.146">
        <paragraph indent="1">Amend NFPA 13D, Subsection 9.1.2 to delete Methods (1), (2) and (4).</paragraph>
      </subsection>
      <subsection heading="22.00.07.147">
        <paragraph indent="1">Amend NFPA 13D, Subsection 11.1.1 to add the following sentence:  Finished surfaces must be completed within a 1 ft radius of all sprinklers before the final inspection.</paragraph>
      </subsection>
      <subsection heading="22.00.07.148">
        <paragraph indent="1">Amend NFPA 13D, Subsection 11.2.1.4 to add a second sentence:  When systems utilizing plastic pipe are being hydrostatically tested, pendent sprinklers are not permitted.</paragraph>
      </subsection>
      <subsection heading="22.00.07.149">
        <paragraph indent="1">Amend NFPA 13R, Subsection 5.4.3 to add the following:  Antifreeze, dry pipe and preaction systems are prohibited in dwelling units and interior corridors leading to dwelling units.</paragraph>
      </subsection>
      <subsection heading="22.00.07.150">
        <paragraph indent="1">Amend NFPA 13R, Subsection 6.4.6.3.2 to add item (3):</paragraph>
        <paragraph indent="2">(3)   Sprinkler heads in closets must not be located directly above shelves.</paragraph>
      </subsection>
      <subsection heading="22.00.07.151">
        <paragraph indent="1">Amend NFPA 13R, Subsection 6.11.1 to add the following sentence:  The fire department connection must be a minimum of one 2 ½ inch inlet with a feed line sized at least as large as the main system riser.  The fire department connection must be located on a fire department access road and be 18 to 48 inches from the centerline of the inlet to finish grade.</paragraph>
      </subsection>
      <subsection heading="22.00.07.152">
        <paragraph indent="1">Amend NFPA 13R, to add new Subsection 8.2.1.1 that reads as follows:  All calculations must include at least a 10% safety factor to account for minor field changes, unless a listed fire pump is necessary to obtain this safety factor.</paragraph>
      </subsection>
      <subsection heading="22.00.07.153">
        <paragraph indent="1">Amend NFPA 13R, Section 9.1, to add the following:  Pressure and volume availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may be used only where it is determined that the public water supply is inadequate.</paragraph>
      </subsection>
      <subsection heading="22.00.07.154">
        <paragraph indent="1">Amend NFPA 13R, to add new Subsection 9.7.3 that reads as follows:  Domestic pumps are permitted for townhomes.</paragraph>
      </subsection>
      <subsection heading="22.00.07.155">
        <paragraph indent="1">Amend NFPA 13R, Subsection 10.2.2 to add a new Subsection that reads as follows:</paragraph>
        <paragraph indent="2">10.2.2.3 Pendent sprinkler heads must not be installed in plastic pipe until after the hydrostatic test is passed.</paragraph>
      </subsection>
      <subsection heading="22.00.07.156">
        <paragraph indent="1">Amend NFPA 14, Subsection 4.8.2 to delete the existing wording and replace with the following:  Each fire hose valve must have a 2 ½ inch hose connection, 2 ½ inch to 1 ½ inch reducer, cap, and chain.</paragraph>
      </subsection>
      <subsection heading="22.00.07.157">
        <paragraph indent="1">Amend NFPA 14, Subsection 5.1.2 to add new Subsection 5.1.2.1 that reads as follows:  New system installations must meet the following requirements:</paragraph>
        <paragraph indent="2">(1)   Systems must be automatic wet type.</paragraph>
        <paragraph indent="2">(2)   Standpipe systems in unheated areas must be automatic dry type.</paragraph>
        <paragraph indent="2">(3)   Standpipe systems in detached open parking garages may be the manual dry type, if the piping is air supervised for breaks or open valves.</paragraph>
        <paragraph indent="2">(4)   Occupant use hose is prohibited in new or existing buildings.</paragraph>
        <paragraph indent="2">(5)   New standpipe systems must be Class I only.</paragraph>
      </subsection>
      <subsection heading="22.00.07.158">
        <paragraph indent="1">Amend NFPA 14, Subsection 6.4.3 to add Subsection 6.4.3.2 (Fire Department Connections):</paragraph>
        <paragraph indent="0">System Demand (gpm) | No. of Inlets
Up to 749 | 2
750-999 | 3
1,000 and above | 4</paragraph>
        <paragraph indent="1">Multiple connections on the same building must be interconnected.</paragraph>
        <paragraph indent="2">(1)   When a section of a building is fed by a connection (i.e., partial systems), permanent all-weather identification signs must be provided on connections.</paragraph>
      </subsection>
      <subsection heading="22.00.07.159">
        <paragraph indent="1">Amend NFPA 14, Subsections 7.3.2.2.1.1 and 7.3.2.2.1.2 to add the following:</paragraph>
        <paragraph indent="2">(1)   Measurement must be parallel or at right angles to walls.</paragraph>
        <paragraph indent="2">(2)   Supplemental hose valves outside the stairs must not be located within tenant spaces unless hose reach requirements cannot be met by placement of valves in public corridors or by use of wall hydrants for spaces opening to the exterior.  Hose valve locations must be marked by the placement of signs, the striping of columns, or other approved methods.</paragraph>
      </subsection>
      <subsection heading="22.00.07.160">
        <paragraph indent="1">Amend NFPA 14, Subsection 7.8.1 to add the following exceptions:</paragraph>
        <paragraph indent="3">Exception 1:  In high-rise buildings, where booster pumps are necessary to produce the required residual pressures, pumps and piping systems must be sized to provide for the demand of the hydraulically most remote hose station, or the sprinkler system demand, whichever is greater.  The standpipe system must also be sized to provide the required flow and pressure for all hose stations required to be flowing, when supplied by 150 psi at 1,000 gpm at the fire department connection(s).  two sets of calculations will, therefore, be required under this exception.</paragraph>
        <paragraph indent="3">Exception 2:  Systems in buildings that are not high-rise, and dry systems with no automatic water supply, may be sized to obtain the required flows and pressures, when supplied by 150 psi at 1,000 gpm at the fire department connection(s).</paragraph>
        <paragraph indent="3">Exception 3:  In existing buildings, after shell occupancy, hose valves added to correct hose reach deficiencies created by tenant modifications may be supplied by 3 inch pipe without recalculation.</paragraph>
      </subsection>
      <subsection heading="22.00.07.161">
        <paragraph indent="1">Amend NFPA 20, Subsection 4.7.7.2 to add Subsection 4.7.7.2.1 that reads as follows:  A relief valve is permitted to be installed to reduce operating pressure below 175 psi at high gradient.</paragraph>
      </subsection>
      <subsection heading="22.00.07.162">
        <paragraph indent="1">Amend NFPA 20, Subsection 14.2.3 to add the following:  Fire pump control equipment must be inspected and approved by a Montgomery County electrical inspector before a fire pump performance test is performed and witnessed by a Montgomery County fire inspector.</paragraph>
      </subsection>
      <subsection heading="22.00.07.163">
        <paragraph indent="1">Amend NFPA 20, Subsection 4.20.7 to delete the existing wording and replace with the following:  For other than static water supplies, relief valves must not be piped back into the source of the supply.</paragraph>
      </subsection>
      <subsection heading="22.00.07.164">
        <paragraph indent="1">Amend NFPA 72, Subsection 10.4.3 to add Subsection 10.4.3.1 that reads as follows:</paragraph>
        <paragraph indent="2">10.4.3.1 When fire alarm equipment is installed in a parking garage or other similar space, if the AHJ determines that the humidity or temperature of the space or both cannot be maintained, then the fire alarm equipment must be listed for outdoor use and the environment where it is installed.</paragraph>
      </subsection>
      <subsection heading="22.00.07.165">
        <paragraph indent="1">Amend NFPA 72, Subsection 10.18.1.1 to add Subsection 10.18.1.1.3 that reads as follows:  An annunciator with the following features is required when the building is greater than one story, has a sprinkler system, or has more than one type of alarm initiating device.</paragraph>
      </subsection>
      <subsection heading="22.00.07.166">
        <paragraph indent="1">Amend NFPA 72, Subsection 10.18.4 to add Subsection 10.18.4.3 that reads as follows:  Annunciation must be in accordance with the following:</paragraph>
        <paragraph indent="2">(1)   Annunciator must have a visible signal for each different floor, zone, and device type.  Supervised computer screen or printer type annunciators may be used to meet this requirement if the zone identification is approved by the Director.</paragraph>
        <paragraph indent="2">(2)   Unless approved by the Director, zones must not exceed a single floor, 52,00 square feet, or 300 linear feet.  Sprinkler systems are permitted to be zoned under the applicable sprinkler standard.</paragraph>
        <paragraph indent="2">(3)   In zones that are greater than 22,500 square feet, a graphic outline on or adjacent to the annunciator must be provided showing the building outline, fire alarm and sprinkler zone boundaries, “you are here” notation, north compass arrow, all stairways, stairway identification numbers, sprinkler zones, all standpipe risers, fire department connections, elevators, and the building address.</paragraph>
        <paragraph indent="2">(4)   A lamp-type annunciator must have a lamp test switch unless the annunciator circuits are supervised.</paragraph>
      </subsection>
      <subsection heading="22.00.07.167">
        <paragraph indent="1">Amend NFPA 72, Subsection 10.18.3.1 to delete the existing wording and replace with the following:  All required annunciation means must be located at, and be visible from, the main fire department entrance unless the building has a fire command center.</paragraph>
      </subsection>
      <subsection heading="22.00.07.168">
        <paragraph indent="1">Amend NFPA 72, Section 14.5 to add Subsection 14.5.8 that reads as follows:</paragraph>
        <paragraph indent="2">14.5.8 Maintenance.  The building owner must maintain a service contract for emergency repair of the system.  The service contract must be such that telephone support is available within 2 hours, and on-site maintenance service can be provided within 24 hours of recognition that the in-building public safety radio enhancement system is not operating correctly.  A copy of the contract must be submitted to the AHJ at the time of acceptance testing.  If the service contract is terminated, both the building owner and contractor must notify the AHJ within 24 hours.</paragraph>
      </subsection>
      <subsection heading="22.00.07.169">
        <paragraph indent="1">Amend NFPA 72, Subsection 17.7.1.7 to add Subsection 17.7.1.7.1 that reads as follows:  Detectors located at the top of shafts and stairs must be on a supervisory circuit only unless a confirmation or verification feature is provided.  The location must be identified at the annunciator or fire alarm control panel.</paragraph>
      </subsection>
      <subsection heading="22.00.07.170">
        <paragraph indent="1">Amend NFPA 72, Subsection 17.7.4.5 to delete the existing wording and replace with the following:  Activation of duct smoke detectors must sound an audible alarm in a normally occupied area or through the building fire alarm system and must be identified as duct detector.  Where connected to the building alarm, the signal must be supervisory only and must not initiate the building evacuation alarm unless a confirmation or verification feature is provided.</paragraph>
      </subsection>
      <subsection heading="22.00.07.171">
        <paragraph indent="1">Amend NFPA 72, Subsection 17.13.3 to add Subsection 17.13.3.1 that reads as follows:  Standpipe or main water flow indicators, if provided, must sound a supervisory signal only.</paragraph>
      </subsection>
      <subsection heading="22.00.07.172">
        <paragraph indent="1">Amend NFPA 72, Subsection 17.15.9.4 to add Subsection 17.15.9.4.1 that reads as follows:  When fire alarm systems are not monitored by a UL listed central station, an approved permanent sign must be installed adjacent to each manual fire alarm box.  The sign must read as follows:</paragraph>
        <paragraph indent="2">Local Alarm Only:</paragraph>
        <paragraph indent="2">(1)   Activate Alarm</paragraph>
        <paragraph indent="2">(2)   Exit Building</paragraph>
        <paragraph indent="2">(3)   Call Fire Department</paragraph>
      </subsection>
      <subsection heading="22.00.07.173">
        <paragraph indent="1">Amend NFPA 72, Subsection 23.8.2.9.1 to read as follows:  Where multiple control units are interconnected in a network arrangement and serve the same protected premises, the control units must be arranged to be reset or silenced from one location.</paragraph>
      </subsection>
      <subsection heading="22.00.07.174">
        <paragraph indent="1">Delete NFPA 72, Subsection 23.8.2.9.2.</paragraph>
      </subsection>
      <subsection heading="22.00.07.175">
        <paragraph indent="1">Amend NFPA 72, Subsection 24.8.16 by changing “two” to “six”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.176">
        <paragraph indent="1">Amend NFPA 72, Subsection 24.9.2 to add Subsection 24.9.2.1 that reads as follows:  Radio Coverage.  Radio coverage must be provided throughout the building such that a minimum of 95% of the building (including underground levels, basements, elevators, stairways, etc.) is covered at a minimum of 95% of the time.</paragraph>
      </subsection>
      <subsection heading="22.00.07.177">
        <paragraph indent="1">Amend NFPA 72, Subsection 29.8.1.1 to add Subsection 29.8.1.1.1 that reads as follows:  Enclosed rooms with a closet such as dens, libraries, studies, or sitting rooms which could be used as a sleeping area must be treated as sleeping rooms.</paragraph>
      </subsection>
      <subsection heading="22.00.07.178">
        <paragraph indent="1">Amend NFPA 80, as referenced by NFPA 1, Subsections 8.4.2.1.2, 10.4.1.2, 11.4.1.2, 11.4.3.2.2, and 13.4.2 to add the following:</paragraph>
        <paragraph indent="2">Release of fire doors and shutters must not be solely by fusible link and must be accomplished by one or more of the following:</paragraph>
        <paragraph indent="2">(1)   approved local smoke detection at the doors;</paragraph>
        <paragraph indent="2">(2)   approved area smoke detection per NFPA 72; or</paragraph>
        <paragraph indent="2">(3)   full automatic sprinkler protection for NFPA 13 with water flow interlock.</paragraph>
      </subsection>
      <subsection heading="22.00.07.179">
        <paragraph indent="1">Amend NFPA 92, Subsection 4.4.2.1.5 by adding the following:  At a minimum, the design must achieve the performance objectives in the condition with two doors open simultaneously.  If there is a door directly to the outside from the stair, the exterior door must be one of the two doors used in the design.</paragraph>
      </subsection>
      <subsection heading="22.00.07.180">
        <paragraph indent="1">Amend NFPA 92, Subsection 5.2.3.1 by adding the following:  The design fire must be not less than 5,000 Btu/s (5,275 kW) unless approved by the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.181">
        <paragraph indent="1">Amend NFPA 96, as referenced by NFPA 1, Subsection 1.1.1, to add an exception to read:</paragraph>
        <paragraph indent="2">In places of worship and day care facilities, protection is permitted to consist of the following:</paragraph>
        <paragraph indent="2">(1)   electrical range with not more than four heating elements, each heating element must be electronically controlled to limit the element temperature to below 670 degrees F;</paragraph>
        <paragraph indent="2">(2)   a shunt trip must be installed for the electric range.  If building is equipped with a fire alarm system, the shunt trip must be interconnected with the fire alarm system.  If the building is not equipped with a fire alarm system, other automatic means/devices, approved by the AHJ, to cut off power to the unit must be installed in the kitchen;</paragraph>
        <paragraph indent="2">(3)   kitchen must not be located more than one story above the level of exit discharge;</paragraph>
        <paragraph indent="2">(4)   kitchen must not be located more than one story below the level of exit discharge; and</paragraph>
        <paragraph indent="2">(5)   kitchen must be separated from adjoining areas by fire barriers with a fire resistance rating of one hour or greater; OR, the kitchen must be protected with automatic sprinklers.</paragraph>
      </subsection>
      <subsection heading="22.00.07.182">
        <paragraph indent="1">Amend NFPA 1221, Subsection 9.6.6.1 to add the phrase:  “A fire alarm permit and” at the beginning of the sentence.</paragraph>
      </subsection>
      <subsection heading="22.00.07.183">
        <paragraph indent="1">Amend NFPA 1221, Subsection 9.6.7 to add new Subsection 9.6.7.7 that reads as follows:  Systems must be engineered to minimize the near-far effect.  Radio enhancement system designs must include sufficient antenna density to address reduced gain conditions unless one or both of the following are present:</paragraph>
        <paragraph indent="2">(1)   Class A narrow band signal booster devices with independent AGC/ALC circuits per channel are used; and/or</paragraph>
        <paragraph indent="2">(2)   systems where are portable devices within the same band are using active power control features.</paragraph>
      </subsection>
      <subsection heading="22.00.07.184">
        <paragraph indent="1">Amend NFPA 1221, Subsection 9.6.7.3 to delete the existing wording and replace with the following:  Critical Areas.  Critical areas include exist passageways, stairwells, exits, common/public areas, base building lobby areas, areas of public gathering during an emergency, fire pump and command/control rooms, dangerous process areas (e.g., dipping process areas, hazardous materials handling areas, etc.) electrical and mechanical utility rooms, police holding areas, elevator lobbies, sprinkler system sectional valve locations, elevator shafts, and must be provided with 99 percent floor area radio coverage.</paragraph>
      </subsection>
      <subsection heading="22.00.07.185">
        <paragraph indent="1">Amend NFPA 1221, Subsection 9.6.7.4 to delete the existing wording and replace with the following:  Radio Coverage.  Radio coverage must be provided throughout the building such that a minimum of 95% of the building (including underground levels, basements, elevators, stairways, etc.) is covered at a minimum of 95% of the time.</paragraph>
      </subsection>
      <subsection heading="22.00.07.186">
        <paragraph indent="1">Amend NFPA 1221, Subsection 9.6.13.2.1 to add Subsection 9.6.13.2.1.1 that reads as follows:  “Where a fire command center is not present, the dedicated monitoring panel must be located adjacent to the main fire alarm control panel for the building.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.187">
        <paragraph indent="1">Amend NFPA 1221, Subsection 11.3.9.1 to delete the entire Subsection and replace with the following:</paragraph>
        <paragraph indent="2">11.3.9.1.1 Testing Procedure.  The test plan must ensure testing throughout the building.  Test procedures must be as directed by the design professional and the AHJ.  Using the Montgomery County control channel, each floor must be RF (radio frequency) signal level mapped utilizing a calibrated, portable spectrum analyzer.  Each floor must be divided into equal grids of no larger than 25 feet by 25 feet.  Individual testing points must not be spaced greater than 25 feet apart.  Each grid must meet the required signal strength level and provide a Delivered Audio Quality (DAQ) of not less than 3.5.  (DAQ 3.5 is defined as “Speech understandable with repetition rarely required.  Some noise/distortion.”) A maximum of two non-adjacent grids will be permitted to fail on the same floor.  Failure of any two adjacent grids is considered a failure for the entire floor.</paragraph>
        <paragraph indent="2">11.3.9.1.2 Systems incorporating Class B signal-booster devices or Class B broadband fiber remote devices must be tested using two portable radios simultaneously conducting subjective voice quality checks.  One portable radio must not be positioned greater than 10 feet from the indoor antenna.  The second portable radio must be positioned at a distance that represents the farthest distance from any indoor antenna.  With both portable radios simultaneously keyed up on different frequencies within the same band, subjective audio testing must be conducted and must comply with the minimum acceptable DAQ level of 3.5.</paragraph>
        <paragraph indent="2">11.3.9.1.3 The design and acceptance testing of the in-building public safety radio enhancement system must be performed under the supervision of a professional engineer registered in the State of Maryland with a minimum of five years of experience in the design, installation, and alignment of emergency responder radio communication enhancement systems.</paragraph>
        <paragraph indent="2">11.3.9.1.4 Acceptance test data of the system must be approved by the AHJ prior to final fire alarm system approval.</paragraph>
        <paragraph indent="2">22.00.07.188</paragraph>
        <paragraph indent="2">NFPA 1225, 2022 edition, Chapter 18, is adopted in its entirety.</paragraph>
        <paragraph indent="2">22.00.07.189</paragraph>
        <paragraph indent="2">Amend NFPA 101, Sections 2.2 and 2.4 by deleting the referenced publication NFPA 150 Standard on Fire and Life Safety in Animal Housing Facilities, 2019 edition.</paragraph>
        <paragraph indent="2">22.00.07.190</paragraph>
        <paragraph indent="2">Amend NFPA 101, Section 2.4, by adding Subsection 2.4.1 that reads as follows:  Wherever NFPA 5000, 2021 edition is referenced, other than for extracted text, substitute the building code that is in effect in Montgomery County.</paragraph>
        <paragraph indent="2">22.00.07.191</paragraph>
        <paragraph indent="2">NFPA 101, Section 3.3 as follows:</paragraph>
        <paragraph indent="3">(1)   Subsection 3.3.64, add the following new Subsection and definition:</paragraph>
        <paragraph indent="4">3.3.64.3 Bulkhead Door.  A type of door assembly covering an opening in the ground providing direct access to a basement, the floor of which is not more than eight (8) feet below ground level.  The door consists of a single rigid leaf or two overlapping rigid leaves or covers which need to be pushed or lifted upwards in order to be opened.  A person, after opening the door, can walk up a series of steps to escape to the outside.</paragraph>
        <paragraph indent="3">(2)   Subsections 3.3.68.1 and 6.1.8.1.1 to replace “three” with “five” and delete “, if any, accommodated in rented rooms”;</paragraph>
        <paragraph indent="3">(3)   Subsection 3.3.84, amend the definition of “Existing” by deleting the existing wording and replace with the following:  That which is already in existence greater than one calendar year after being approved, accepted, or commissioned by the authority having jurisdiction;</paragraph>
        <paragraph indent="3">(4)   amend Subsections 3.3.150.1, 16.6.1.1.2 and 17.6.1.1.2 to delete “...more than three, but...”;</paragraph>
        <paragraph indent="3">(5)   amend Subsections 3.3.198.4 and 6.1.4.1 to delete “...four or more...”;</paragraph>
        <paragraph indent="3">(6)   amend Subsections 3.3.150.2, 6.1.5.1, 3.3.198.12 and 6.1.9.1 to replace the word “four” with “six”; and</paragraph>
        <paragraph indent="3">(7)   amend Subsection 3.3.254 to add the following new Subsection and definition:</paragraph>
        <paragraph indent="4">3.3.254.1 Incapable of self-preservation.  A person who, because of age, physical or mental disability, medical or therapeutic intervention, medication, etc., is unable to act to protect themselves from harm during an emergency situation without assistance.</paragraph>
      </subsection>
      <subsection heading="22.00.07.192">
        <paragraph indent="1">Amend NFPA 101, Subsections 4.5.8 and 4.6.12.1 to delete the phrase “for compliance with the provisions of this Code”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.193">
        <paragraph indent="1">Amend NFPA 101, Subsection 4.6.10.2 to replace “Where required by Chapters 11 through 43, construction” with “Construction”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.194">
        <paragraph indent="1">Amend NFPA 101, Subsection 4.6.12.3 to delete the phrase “by the Code” and add the following phrase after the word “removed”:  by qualified personnel.  Removal of life safety features must be approved by the Department of Permitting Services.</paragraph>
      </subsection>
      <subsection heading="22.00.07.195">
        <paragraph indent="1">Amend NFPA 101, Subsection 4.8.2, to add the following Subsection:</paragraph>
        <paragraph indent="2">4.8.2.4 Emergency action plans must be maintained in a location approved by the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.196">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.1.10 to add the following Subsection:</paragraph>
        <paragraph indent="2">7.1.10.3 Trash or recyclable materials awaiting scheduled collection cannot be placed in exits, exit access corridors, or on egress balconies.</paragraph>
      </subsection>
      <subsection heading="22.00.07.197">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.1.5.7, to add the phrase “and all stairway doors must be unlocked simultaneously without unlatching upon a signal from the fire command center.” to item (3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.198">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.1.5.7.1, to add an item (6), to read:</paragraph>
        <paragraph indent="2">(6)   Entry levels must provide free access to an approved second exit.  These levels must be designated in “core/shell” building permit drawings with future tenant layouts arranged accordingly.</paragraph>
      </subsection>
      <subsection heading="22.00.07.199">
        <paragraph indent="1">Amend NFPA 101, Subsections 7.2.1.6.4.1, 7.2.1.14.1, and 7.2.1.15.1 to replace the phrase “in Chapters 11 through 43” with the phrase “by the AHJ and Chapters 11 through 43”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.200">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.1.7.1 to delete “required to be”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.201">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.1.7.4 to delete “Required”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.202">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.2.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">7.2.2.1.3 In new installations, at least one exit stair that serves all stories of the building must be accessible by an internal corridor from the main entrance of the building or fire department response location.</paragraph>
      </subsection>
      <subsection heading="22.00.07.203">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.2.2.4.5.2, by replacing the words “Existing required” with “Interior”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.204">
        <paragraph indent="1">Delete NFPA 101, Subsection 7.2.3.9.2(3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.205">
        <paragraph indent="1">Amend NFPA 101, Table 7.3.1.2 to add the following:</paragraph>
        <paragraph indent="0">Use |  | (ft 2 per person) | (m 2 per person)
Assembly Use | Tennis court (area of play) | 50 (net) | 15.24 (net)
Assembly Use | Bars g | 18 linear in./pers | 455 linear mm/pers
Business Use | Core/shell | 65 (gross) | 16 (gross)
g :  Measured at the patron side of the bar</paragraph>
      </subsection>
      <subsection heading="22.00.07.206">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.9.1.2, to replace the word “only” in the first sentence with “but not be limited to,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.207">
        <paragraph indent="1">Amend NFPA 101, Subsection 7.10.8.3.1 by adding:  If the sign is on the door, then the door must be equipped with an approved self-closing device.</paragraph>
      </subsection>
      <subsection heading="22.00.07.208">
        <paragraph indent="1">Amend NFPA 101, Subsection 8.6.7(6)(b) by adding the following phrase at the end of the sentence:  “in a location approved by the AHJ”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.209">
        <paragraph indent="1">Amend NFPA 101, Subsection 8.7.3.3 to replace “following criteria:” in the opening sentence with “following criteria, unless otherwise permitted by the AHJ:”</paragraph>
      </subsection>
      <subsection heading="22.00.07.210">
        <paragraph indent="1">Amend NFPA 101, Section 9.1 by deleting the text in Section 9.15 and replacing it with the following:</paragraph>
        <paragraph indent="1">9.15 Emergency Responder Radio Communication Enhancement Systems (ERRCES).</paragraph>
        <paragraph indent="2">9.15.1 For newly constructed buildings, ERRCES must be provided where any of the following conditions exist:</paragraph>
        <paragraph indent="2">(1)   on all floors of a building located below the level of exit discharge;</paragraph>
        <paragraph indent="2">(2)   on all floors of a building in which any floor of the building exceeds 25,000 ft2 per floor in gross aggregate area;</paragraph>
        <paragraph indent="2">(3)   throughout any building in which the building area exceeds 100,000 ft2 in gross aggregate area; and</paragraph>
        <paragraph indent="2">(4)   on all floors of a building for any building greater than three (3) stories in height above the lowest level of fire department vehicle access.</paragraph>
        <paragraph indent="3">(a)   System performance testing must be performed in accordance with technical standards for systems and testing personnel established by Montgomery County.</paragraph>
        <paragraph indent="3">(b)   Compliance testing must be performed at time of occupancy.</paragraph>
        <paragraph indent="3">(c)   Field testing may be performed upon reasonable notification to the owner or occupant by any authorized fire and rescue personnel.</paragraph>
        <paragraph indent="2">Exception:  One- and two-family dwellings and townhomes.</paragraph>
        <paragraph indent="2">9.15.2 In existing buildings, where emergency radio communication system performance is reported to be inadequate, and the building meets the criteria of 9.15.1(a) through (d), the Director is permitted to require a technical analysis to determine the level of performance of the emergency radio communication system.  The technical analysis must comply with Section 9.6.7 of the 2019 edition of NFPA 1221, and the results certified by a Professional Engineer in the State of Maryland with at least five (5) years of experience in the design, installation, and alignment of emergency responder radio communication enhancement systems.  Where the analysis demonstrates unacceptable performance, an in-building public safety radio enhancement system must be provided.</paragraph>
        <paragraph indent="2">9.15.3 The system must be designed in accordance with Section 9.6 of the 2019 NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems, and the frequencies listed in the DPS Emergency Responder Radio Coverage In-Building Radio Signal Amplification System Standard, effective April 1, 2005.</paragraph>
        <paragraph indent="2">9.15.4 All testing, design, installation, inspection, and maintenance required by Section 9.15 must be performed by personnel approved by the Director.</paragraph>
      </subsection>
      <subsection heading="22.00.07.211">
        <paragraph indent="1">Amend Subsections 9.6.1.3 and 9.11.1 to delete “required by this Code”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.212">
        <paragraph indent="1">NFPA 101, Subsection 9.6.2.6 is amended as follows:</paragraph>
        <paragraph indent="2">(1)   Add the following sentence to the end of the Section:  “This paragraph does not permit the omission of manual fire alarm boxes in accordance with other provisions of this Subsection unless specifically permitted by Chapters 11 through 43.”</paragraph>
        <paragraph indent="2">(2)   Add two new Subsections as follows:</paragraph>
        <paragraph indent="3">9.6.2.6.1 Zoned fire alarm systems must have manual pull stations located at the entrance to each exit enclosure and at the main exit.</paragraph>
        <paragraph indent="3">9.6.2.6.2 When a fire alarm system is required in a multiple tenant building, for each tenant exiting directly to the exterior of the building, a manual pull station and approved occupant notification must be located at each required or marked exit.</paragraph>
      </subsection>
      <subsection heading="22.00.07.213">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.2.9 to add the following sentence:  “In environments not suitable for smoke detectors, alternate means of detection must be provided and must comply with NFPA 72, 2019 edition).”</paragraph>
      </subsection>
      <subsection heading="22.00.07.214">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.3.2.1 to delete the phrase “lobby,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.215">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.3.4, by deleting the phrase after the words “without delay” and replacing it with the following:  to a listed central station in accordance with 9.6.4.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.216">
        <paragraph indent="1">NFPA 101, Subsection 9.6.3.8, add a second sentence to read:  “Required audibility must be met with all intervening doors (between any space and the audible devices) closed.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.217">
        <paragraph indent="1">Amend NFPA 101, Subsections 9.6.3.10 and 9.6.3.10.1 by deleting the word “live”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.218">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.3.10 by adding:  Where voice type occupant notification is used, automatic pre-recorded messages must be used.  Live voice as the sole notification method is prohibited.</paragraph>
        <paragraph indent="1">Exception:  Previously “approved” live voice systems are permitted to remain.</paragraph>
      </subsection>
      <subsection heading="22.00.07.219">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.4.2 by deleting the list of four items and replace the phrase “via any of the following means acceptable to the authority having jurisdiction” with “by a listed central station fire alarm system.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.220">
        <paragraph indent="1">Amend NFPA 101 to delete Subsections 9.6.4.3, 9.6.8.4.3, 9.6.8.4.4, and 9.6.8.4.5.</paragraph>
      </subsection>
      <subsection heading="22.00.07.221">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.6.2(3), to add the following sentence:  “Manual fire alarm initiation must not activate floor or zone-dependent smoke control systems.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.222">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.6.8.3 to delete the phrase after the word “zone”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.223">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.7.1.1 to add the following Subsection:</paragraph>
        <paragraph indent="2">9.7.1.1.1  For new installations, drop-out ceilings as referenced in NFPA 13, Subsections 9.2.16 and 9.3.11 are prohibited.</paragraph>
      </subsection>
      <subsection heading="22.00.07.224">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.7.2.2.1, the first sentence to read:  “Where supervised automatic sprinkler protection is required, waterflow alarms must be automatically transmitted to a listed central station.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.225">
        <paragraph indent="1">Amend NFPA 101, Subsection 9.8.1 to read as follows:</paragraph>
        <paragraph indent="2">“Where water as an extinguishing agent is not compatible with the fire hazard or is prohibited by law, statute or ordinance, the affected area must be equipped with an approved automatic fire suppression system utilizing a suppression agent that is compatible with the fire hazard.  Such system must be installed in accordance with the appropriate standard as determined in Table 9.8.1.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.226">
        <paragraph indent="1">Amend Subsections 9.11.4.1 and 9.14.1 to replace “Chapter 11 through 43” with “the AHJ or Chapters 11 through 43”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.227">
        <paragraph indent="1">Amend Subsections 10.4.1 and 10.5.1 to add the following at the beginning of each sentence:  “Where required by the AHJ,”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.228">
        <paragraph indent="1">Amend NFPA 101, Subsection 11.8.1.2 to add the following at the end of the first sentence.  “High-rise buildings do not include a structure or building used exclusively for open-air parking”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.229">
        <paragraph indent="1">Amend NFPA 101, Subsection 11.8.4.1, to add new Subsection 11.8.4.1.1 that reads as follows:</paragraph>
        <paragraph indent="2">11.8.4.1.1 In buildings having staged evacuation, the voice fire alarm system must send a predetermined message to the floor where the alarm originated, to the floor immediately below and to the floor immediately above, providing information and direction to the occupants.  Any subsequent alarm(s) on other than the initial fire floor must initiate the voice fire alarm as described above.  The voice fire alarm must be designed to be heard clearly by all occupants within the designated portions thereof as required by Section 9.6, but it must not sound automatically in elevator cars and enclosed exit stairways.  Communicating levels are considered one floor/fire area for the audible and visual fire alarm signals.</paragraph>
      </subsection>
      <subsection heading="22.00.07.230">
        <paragraph indent="1">Amend NFPA 101, Subsection 11.8.4.2.2 to delete the existing wording and replace with the following:  The requirement of Subsection 11.8.4.2.1 does not apply if an approved two-way radio communications enhancement system is installed throughout the building.</paragraph>
      </subsection>
      <subsection heading="22.00.07.231">
        <paragraph indent="1">Amend NFPA 101, Subsection 11.8.6.1, to delete the existing wording and read:</paragraph>
        <paragraph indent="2">11.8.6.1.1 In new installations, the emergency command center must have a door directly to the exterior of the building on the address side.  The exterior door to the emergency command center must be within 50 feet of unimpeded travel to a fire department access road.  A fire department access box must be provided in an approved location within (6) feet of the door to the emergency command center.  The exterior door to the emergency command center must be identified on the exterior face as the emergency command center in a manner acceptable to the AHJ.</paragraph>
      </subsection>
      <subsection heading="22.00.07.232">
        <paragraph indent="1">Amend Subsection 11.8.6.2 to replace “approved by the fire department” with “approved by the AHJ”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.233">
        <paragraph indent="1">Amend NFPA 101, Subsections 11.8.6.6 (5) and (6), to read as follows:</paragraph>
        <paragraph indent="2">(5)   Emergency generator status indicators, and remote starting.</paragraph>
        <paragraph indent="2">(6)   Fire pump status indicators and remote starting.</paragraph>
      </subsection>
      <subsection heading="22.00.07.234">
        <paragraph indent="1">Amend NFPA 101, Section 11.11.2.1 to add the phrase “or other testing standard approved by the AHJ”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.235">
        <paragraph indent="1">Delete Subsection 11.12.2.</paragraph>
      </subsection>
      <subsection heading="22.00.07.236">
        <paragraph indent="1">Amend NFPA 101, Subsections 12.2.4.1 and 13.2.4.1 to add the following:</paragraph>
        <paragraph indent="2">(1)   Not less than two separate exits must be provided on every story.</paragraph>
        <paragraph indent="2">(2)   Not less than two separate exits must be accessible from every part of every story.</paragraph>
      </subsection>
      <subsection heading="22.00.07.237">
        <paragraph indent="1">Delete Subsections 12.2.1.2, 14.2.1.5, 16.2.1.1, 16.6.2.1.2, 24.2.8, 26.2.4, 28.2.1.4, 30.2.1.3, 32.2.2.7, 32.3.2.1.3, 36.2.1.6, 38.2.1.6, 40.2.1.3, and 42.2.1.3.</paragraph>
      </subsection>
      <subsection heading="22.00.07.238">
        <paragraph indent="1">Amend NFPA 101, Subsections 14.2.11.1.1(1) and 15.2.11.1.1(1) by adding “keys, special knowledge, or excessive force.” after the word “tools”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.239">
        <paragraph indent="1">Amend NFPA 101, Subsections 14.3.4.1 and 15.3.4.1 to add new Subsections 14.3.4.1.3 and 15.3.4.1.3 that read as follows:</paragraph>
        <paragraph indent="2">For the purposes of this Chapter, each industrialized building, which is an independently certified unit serving as a portable or temporary classroom, must be considered a single building regardless of the number of units in the cluster sharing an egress system.</paragraph>
      </subsection>
      <subsection heading="22.00.07.240">
        <paragraph indent="1">Amend NFPA 101, Subsections 14.2.5.1 and 15.2.5.1 to add Subsections 14.2.5.1.1 and 15.2.5.1.1 that reads as follows:</paragraph>
        <paragraph indent="2">Where industrialized buildings serving as portable or temporary classrooms are clustered into groups of buildings, each classroom must exit directly onto a common deck or other all-weather walking surface.  This common deck must have two remote, accessible exits with a common path no greater than 75 feet.  An “Exterior Area for Assisted Rescue” in accordance with the 2021 edition of the International Building Code, Section 1009.7, is permitted to be used as one of the accessible means of egress.</paragraph>
      </subsection>
      <subsection heading="22.00.07.241">
        <paragraph indent="1">Amend NFPA 101, Subsections 14.7.2.3 and 15.7.2.3 to delete existing wording and replace with the following:</paragraph>
        <paragraph indent="2">Fire emergency egress drills must be conducted as follows:</paragraph>
        <paragraph indent="2">(1)   At least one fire emergency egress drill must be conducted every month the facility is in session, unless the following criteria are met:</paragraph>
        <paragraph indent="3">(a)   in climates where the weather is sever, the monthly fire emergency egress drills may be deferred; and</paragraph>
        <paragraph indent="3">(b)   in educational occupancies which are:</paragraph>
        <paragraph indent="4">(i)   fully protected by an automatic sprinkler system, five (5) annual fire emergency egress drills must be conducted, with at least two (2) of the required drills conducted in the first four months of the school year; or</paragraph>
        <paragraph indent="4">(ii)   not fully protected by an automatic sprinkler system, eight (8) annual fire emergency egress drills must be conducted, with at least three (3) of the required drills conducted in the first four months of the school year.</paragraph>
        <paragraph indent="2">(2)   All occupants of the building must participate in the fire emergency egress drill.</paragraph>
        <paragraph indent="2">(3)   One fire emergency egress drill, other than for educational occupancies that are open on a year-round basis, must be conducted within the first 30 days of operation.</paragraph>
      </subsection>
      <subsection heading="22.00.07.242">
        <paragraph indent="1">Amend NFPA 101, Subsections 15.2.2.2.4.1 and 17.2.2.2.6.1 to add “provided that the locking device is of a type that is readily distinguishable as locked” to the end of item (3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.243">
        <paragraph indent="1">Amend NFPA 101, Subsections 15.2.2.2.4.1(9) and 17.2.2.2.6.1(9) to add a second sentence:  Any locking or unlocking condition approved by the Director as part of the emergency action plan is permitted to remain in place.</paragraph>
      </subsection>
      <subsection heading="22.00.07.244">
        <paragraph indent="1">Delete NFPA 101, Subsection 15.2.4.2 item (3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.245">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.1.2 and 17.1.2, to add Subsections 16.1.2.2 and 17.1.2.2 as follows:</paragraph>
        <paragraph indent="2">Day-care centers providing day care for school age children before and after school hours in a building that is in use as a public or private school are not required to meet the provisions of this chapter but must meet the provisions for educational occupancies.</paragraph>
      </subsection>
      <subsection heading="22.00.07.246">
        <paragraph indent="1">Amend NFPA 101, Subsection 16.1.6.2 to add a new Subsection as follows:</paragraph>
        <paragraph indent="2">16.1.6.2.1 Where day-care occupancies, with clients who are 30 months or younger in age or who are incapable of self-preservation, are located three (3) or more stories above the level of exit discharge, an independent means of egress dedicated for use by the day-care occupancy must be provided.  Exceptions:</paragraph>
        <paragraph indent="3">(1)   high-rise buildings with an approved phased evacuation plan and</paragraph>
        <paragraph indent="3">(2)   day-care homes.</paragraph>
      </subsection>
      <subsection heading="22.00.07.247">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.2.11.1.1 and 17.2.11.1.1 to add the following item:</paragraph>
        <paragraph indent="2">(4)   For windows at grade, the minimum net clear opening must be 5.0 square feet.</paragraph>
      </subsection>
      <subsection heading="22.00.07.248">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.3.2.1(2) and 17.3.2.1(2) to add new Subsection (e) that reads.</paragraph>
        <paragraph indent="2">Building mechanical spaces housing fuel-fired equipment or appliances for purposes including, but not limited to, heating, ventilation, or clothes drying.</paragraph>
      </subsection>
      <subsection heading="22.00.07.249">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.3.4.5 and 17.3.4.5 to add the following exception:</paragraph>
        <paragraph indent="2">Exception:  Day-care occupancies located in school facilities where enrollment is limited to children capable of self preservation, where no sleeping facilities are provided and the school is provided with approved full automatic sprinkler protection.</paragraph>
      </subsection>
      <subsection heading="22.00.07.250">
        <paragraph indent="1">Amend NFPA 101, Subsection 16.3.5.1 to add the following;</paragraph>
        <paragraph indent="2">Automatic sprinkler protection is not required if all of the following conditions are met:</paragraph>
        <paragraph indent="2">(1)   the day care center has not more than 30 clients;</paragraph>
        <paragraph indent="2">(2)   all rooms used for day care are located on the level of exit discharge; and</paragraph>
        <paragraph indent="2">(3)   all rooms used for day care have at least one exterior exit door at grade level.</paragraph>
      </subsection>
      <subsection heading="22.00.07.251">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.6.1.4.1.1 and 17.6.1.4.1.1 to delete the phrase “...more than 3, but...” and replace “seven” with “nine”</paragraph>
      </subsection>
      <subsection heading="22.00.07.252">
        <paragraph indent="1">Amend NFPA 101, 16.6.1.4.1.2, Subsections 16.6.1.4.1.2 and 17.6.1.4.1.2 to replace “7” with “9”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.253">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.6.1.7.1 and 17.6.1.7.1, to replace “both” with “all” and items (1) and (2) with the following items:</paragraph>
        <paragraph indent="2">(1)   The minimum staff-to-client ratio must be not less than one staff for up to eight clients, including the caretaker’s own children incapable of self-preservation.</paragraph>
        <paragraph indent="2">(2)   There must be not more than four clients incapable of self-preservation, including the caretaker’s own children incapable of self-preservation.</paragraph>
        <paragraph indent="2">(3)   A staff-to-client ratio of at least one staff to every two clients incapable of self-preservation must be maintained at all times.</paragraph>
        <paragraph indent="2">(4)   The staff-to-client ratio may be modified by the authority having jurisdiction where safeguards in addition to those specified in this section are provided.</paragraph>
      </subsection>
      <subsection heading="22.00.07.254">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.6.2.1.1 and 17.6.2.1.1, to add the following sentence:  “Bulkhead doors are not permitted to serve as a primary means of escape.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.255">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.6.2.2 (Reserved) and 17.6.2.2 (Reserved) as follows:</paragraph>
        <paragraph indent="2">SLIDING DOOR</paragraph>
        <paragraph indent="2">For family day-care homes, a sliding door used as a required means of egress must comply with the following conditions:</paragraph>
        <paragraph indent="2">(1)   the sliding door must not have more than one, easily operated, locking device that does not require special knowledge, effort, or tools to operate;</paragraph>
        <paragraph indent="2">(2)   draperies, screens, or storm doors that could impede egress must not be present;</paragraph>
        <paragraph indent="2">(3)   the sill or track height may not exceed ½ inch above the interior finish floor;</paragraph>
        <paragraph indent="2">(4)   the surface onto which exit is made must be an all-weather surface such as a deck, patio, sidewalk, etc.;</paragraph>
        <paragraph indent="2">(5)   the floor level outside the door may be one step lower than the inside, but not more than 8 inches lower;</paragraph>
        <paragraph indent="2">(6)   the sliding door must open to a clear open width of at least 28 inches;</paragraph>
        <paragraph indent="2">(7)   before day care use, each day the sliding door must be unlocked and tested to the full required width to be sure it is operating properly, and the door must be nonbinding and slide easily;</paragraph>
        <paragraph indent="2">(8)   during periods of snow or freezing rain, door tracks must be cleared out and the door opened periodically throughout the day in order to ensure proper operation.</paragraph>
      </subsection>
      <subsection heading="22.00.07.256">
        <paragraph indent="1">NFPA 101, Subsections 16.6.2.3 (Reserved) and 17.6.2.3 (Reserved) are amended as follows:</paragraph>
        <paragraph indent="2">SPECIAL MEANS OF ESCAPE REQUIREMENTS:  For family day-care homes, dead-bolt locks must be provided with approved interior latches, or these locks must be of a captured key design from which the key cannot be removed from the interior side of the lock when the lock is in the locked position.  These locks must be unlocked at all times when the home is occupied for the purpose of family day care.  Exception:  A double-keyed dead-bolt lock may be used on the secondary means of escape if the key is readily accessible and the lock is unlocked at all times the home is occupied for the purpose of family day care.</paragraph>
      </subsection>
      <subsection heading="22.00.07.257">
        <paragraph indent="1">Delete NFPA 101, Subsections 16.6.2.4.5(3) and 17.6.2.4.5(3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.258">
        <paragraph indent="1">Amend NFPA 101, Subsection 16.6.3.4.5 to replace “Reserved.” with the following:  For compliance with Subsection 43.7.2.1(2), approved battery-powered smoke alarms, rather than house electrical service-powered smoke alarms required by Subsection 16.6.3.4.4, are permitted where the facility has testing, maintenance, and smoke alarm replacement programs that ensure reliability of power to the smoke alarms.</paragraph>
      </subsection>
      <subsection heading="22.00.07.259">
        <paragraph indent="1">Amend NFPA 101, Subsections 16.7.5 and 17.7.5, to add:</paragraph>
        <paragraph indent="2">Exception:  Day-Care Homes with no more than three clients for overnight lodging.</paragraph>
      </subsection>
      <subsection heading="22.00.07.260">
        <paragraph indent="1">Amend NFPA 101, Subsections 17.6.3.4.5, 26.3.4.5.3, and 33.3.3.4.7.2 to delete “existing” and replace “battery” with “smoke alarm”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.261">
        <paragraph indent="1">Amend NFPA 101, Subsection 18.2.2.2.10 to add the word “lowest” prior to the phrase “level of fire department vehicle access”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.262">
        <paragraph indent="1">Amend NFPA 101, Table 19.1.6.1 to delete footnotes “c” and “d” from both rows of “Type V” construction.</paragraph>
      </subsection>
      <subsection heading="22.00.07.263">
        <paragraph indent="1">Amend NFPA 101, Subsections 19.1.6.7 and 19.1.6.8 to delete item (2).</paragraph>
      </subsection>
      <subsection heading="22.00.07.264">
        <paragraph indent="1">Amend NFPA 101, Subsection 19.1.6.7, item (5) to replace “Section 19.6” with “Section 9.6”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.265">
        <paragraph indent="1">Amend NFPA 101, Subsections 20.1.1.4.3.2 and 21.1.1.4.3.2 to delete the wording after the “,” and replace it with “materials in accordance with the 2019 edition of NFPA 241, Section 4.3 Temporary Enclosures, are permitted.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.266">
        <paragraph indent="1">Amend the following NFPA 101 Sections and Subsections as follows:</paragraph>
        <paragraph indent="2">(1)   Amend Subsection 22.4.6.1.3 to delete the phrase “or 22.4.6.1.5”.</paragraph>
        <paragraph indent="2">(2)   Delete NFPA 101, Subsections 22.4.6.1.5 and 23.4.6.1.5.</paragraph>
        <paragraph indent="2">(3)   Delete NFPA 101, Subsections 22.4.6.2 and 23.4.6.2..</paragraph>
        <paragraph indent="2">(4)   Amend Subsection 23.4.6.1.3 to delete the phrase “or 23.4.6.1.5”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.267">
        <paragraph indent="1">Amend NFPA 101, Subsection 24.1.1.2 to replace the word “three” with “five” and to delete the phrase “, if any, accommodated in rented rooms”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.268">
        <paragraph indent="1">Amend NFPA 101, Subsections 24.2.2.3.3, 32.2.2.3.1(3) and 33.2.2.3.1(3) to insert the phrase “, not less than 5.0 ft2 for grade floor windows” after the phrase “5.7 ft2”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.269">
        <paragraph indent="1">Amend NFPA 101, Subsection 26.1.1.1, to change “buildings” to “buildings that do not qualify as one- and two-family dwellings”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.270">
        <paragraph indent="1">Amend NFPA 101, Subsection 26.3.4.6.1 to delete the word “new”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.271">
        <paragraph indent="1">Delete NFPA 101, Subsections 26.3.4.6.3(3), 28.3.4.7.3(3), 29.3.4.3.6, 29.3.4.5.2, 29.3.4.6.3(3), 30.3.4.2.2, 30.3.4.3.4, 30.3.4.6.3(3), 31.3.4.2.2, 31.3.4.5.2, 32.2.3.4.4.3(3), and 32.3.3.4.9.3(3).</paragraph>
      </subsection>
      <subsection heading="22.00.07.272">
        <paragraph indent="1">Amend NFPA 101, Subsections 26.3.6.2.2, 28.3.5.3, 30.3.5.1.2, 31.3.5.2, 32.2.3.5.3.1, 33.2.3.5.3.4, 33.2.3.5.3.5, and 33.3.3.5.1.1 to change “in height above grade plane” to “above the lowest level of fire department vehicle access.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.273">
        <paragraph indent="1">Amend NFPA 101, Section 26.4 to delete the existing wording and replace it with the following:  Lodging and rooming occupancies must comply with Chapter 11 where located in a special structure.</paragraph>
      </subsection>
      <subsection heading="22.00.07.274">
        <paragraph indent="1">Amend NFPA 101, Subsection 28.3.4.3.6, to delete all wording after “provided” in the first sentence only.</paragraph>
      </subsection>
      <subsection heading="22.00.07.275">
        <paragraph indent="1">Amend NFPA 101, Subsections 30.3.4.2.1 and 31.3.4.2.1 to delete the wording after “with 9.6.2””.</paragraph>
      </subsection>
      <subsection heading="22.00.07.276">
        <paragraph indent="1">Amend NFPA 101, Subsection 30.3.4.3.3 to delete the phrase “unless the building complies with either 30.3.4.3.4 or 30.3.4.3.5” and delete Subsection 30.3.4.3.4.</paragraph>
      </subsection>
      <subsection heading="22.00.07.277">
        <paragraph indent="1">Amend NFPA 101, Subsection 31.3.5.7 to delete the phrase “seven or more stories in height”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.278">
        <paragraph indent="1">Delete NFPA 101, Subsections 32.2.3.5.2, 33.2.3.5.3.6, 33.3.3.4.6.1, 33.3.3.4.7.3, and 33.3.3.4.8.2.</paragraph>
      </subsection>
      <subsection heading="22.00.07.279">
        <paragraph indent="1">Amend NFPA 101, Subsection 32.2.3.5.3.2 to add the following at the beginning of the Section, “In small board and care homes serving eight or fewer residents,” and delete item (2).</paragraph>
      </subsection>
      <subsection heading="22.00.07.280">
        <paragraph indent="1">Amend NFPA 101, Subsection 33.3.3.4.6.2 and delete the wording before the word “emergency”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.281">
        <paragraph indent="1">Amend NFPA 101, Subsections 33.2.3.4.4.6 and 33.3.3.4, to add at the end of the sentence, “...and have secondary battery back-up power.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.282">
        <paragraph indent="1">Amend NFPA 101 Subsection 33.3.3.4.8.1 to delete the phrase “33.3.3.4.8.2 and”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.283">
        <paragraph indent="1">Amend NFPA 101, Subsections 36.3.4.1 and 37.3.4.1 to read as follows:  General.  Class A mercantile occupancies and multiple story Class B mercantile occupancies must be provided with a fire alarm system in accordance with Section 9.6.</paragraph>
      </subsection>
      <subsection heading="22.00.07.284">
        <paragraph indent="1">Amend NFPA 101, Subsection 36.4.4.7.3.2, to add the phrase “where approved alternative visible means of occupant notification is provided” after the word “concourses”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.285">
        <paragraph indent="1">Amend NFPA 101, Subsection 38.2.4.4(3) (a) to replace “stories.” with “stories, with no openings therein.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.286">
        <paragraph indent="1">Amend NFPA 101, Subsections 38.3.2.1 and 39.3.2.1 by adding the following sentence:  General storage areas with a floor area not greater than 100 square feet are exempt from the provisions of 8.7.</paragraph>
      </subsection>
      <subsection heading="22.00.07.287">
        <paragraph indent="1">Amend NFPA 101, Subsection 39.2.2.2.5 to read:  “The re-entry provisions of Subsection 7.2.1.5.8 do apply.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.288">
        <paragraph indent="1">Amend NFPA 101, Subsection 39.3.4.2 to delete “by one of the following means:” and replace with:  “by all of the following means where provided:”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.289">
        <paragraph indent="1">Amend NFPA 101, Subsections 40.3.4.3.1, 42.3.4.3.1 and 42.8.3.4.3.1 to only read:  “The required fire alarm system must provide occupant notification in accordance with Subsection 9.6.3.”</paragraph>
      </subsection>
      <subsection heading="22.00.07.290">
        <paragraph indent="1">Amend NFPA 1, Table 42.2.5 to replace “50” with “75” and “15” with “23” for Common Path of Travel for Ordinary Hazard Storage Occupancy not protected throughout by an approved, supervised automatic sprinkler system in accordance with Subsection 9.7.1.1(1).</paragraph>
      </subsection>
      <subsection heading="22.00.07.291">
        <paragraph indent="1">Amend NFPA 101, Subsections 42.3.4.1.2 and 42.3.4.1.3 to replace the phrase “Storage occupancies” with “Storage occupancies less than three stories”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.292">
        <paragraph indent="1">Amend NFPA 101, Subsections 42.8.3.4.1.1 and 42.8.3.4.1.3 to replace “Parking structures” with “Parking structures less than three stories”.</paragraph>
      </subsection>
      <subsection heading="22.00.07.293 Severability">
        <paragraph indent="1">The provisions of these regulations are severable. If a court of competent jurisdiction holds that a provision is invalid or inapplicable, the remainder of the regulation remains in effect.</paragraph>
      </subsection>
    </regulation>
  </section>
  <section heading="COMCOR 22.74.00 Fire Safety Instructions - Emergency Safety Plan">
    <regulation heading="COMCOR 22.74.00 Fire Safety Instructions - Emergency Safety Plan">
      <subsection heading="22.74.00.01 Fire Safety Instructions.">
        <paragraph indent="0">Emergency safety plans for multifamily rental buildings are required to be prepared by apartment building owners, or their designee, and submitted to the Department of Permitting Services for review and approval.</paragraph>
      </subsection>
      <subsection heading="22.74.00.02 Definitions.">
        <paragraph indent="0">For purposes of this Section:</paragraph>
        <paragraph indent="1">Department means the Department of Permitting Services.</paragraph>
        <paragraph indent="1">Director means the Director of the Department or the Director’s designee.</paragraph>
        <paragraph indent="1">Emergency safety plan means an action plan approved by the Department in accordance with this Section.</paragraph>
        <paragraph indent="1">Multifamily Apartment Building or Multifamily Dwelling means a building that contains three or more dwelling units that are tenant-occupied or intended to be tenant-occupied.</paragraph>
        <paragraph indent="1">Condominium means a building where residential dwelling units are individually owned and may be owner- or tenant-occupied.</paragraph>
      </subsection>
      <subsection heading="22.74.00.03 Emergency Safety Plan – Requirements.">
        <paragraph indent="1">(a)   Each landlord of a multifamily dwelling must submit a proposed emergency safety plan on a form prescribed by the Director. Condominiums are not required to submit emergency safety plans but may submit them for review and approval.</paragraph>
        <paragraph indent="1">(b)   A landlord is required to update the contents of the plan and obtain a new approval from the Department to remain in compliance with this Section every three years, or when the contents change, whichever is sooner. Changes to the plan must be submitted to the Department for review within 14 calendar days of any changes to the plan’s scope and contents.</paragraph>
      </subsection>
      <subsection heading="22.74.00.04 Scope and Contents of the Plan.">
        <paragraph indent="0">The emergency safety plan must, at a minimum, include:</paragraph>
        <paragraph indent="1">(a)   an evacuation map;</paragraph>
        <paragraph indent="1">(b)   the location of fire extinguishers;</paragraph>
        <paragraph indent="1">(c)   the type of fire alarm system installed;</paragraph>
        <paragraph indent="1">(d)   a point of contact or the type of communication that will be used by the landlord during and after the emergency;</paragraph>
        <paragraph indent="1">(e)   details regarding alternate housing when a tenant is displaced due to the building emergency; and</paragraph>
        <paragraph indent="1">(f)   fire protection system impairment procedures.</paragraph>
      </subsection>
      <subsection heading="22.74.00.05 Procedures for Submittal.">
        <paragraph indent="1">(a)   Emergency safety plans must be submitted as a required document for review and approval as part of the building’s Fire Code Compliance Permit in accordance with Section 22-10 beginning September 1, 2025.</paragraph>
        <paragraph indent="1">(b)   The emergency safety plan must comply with the emergency safety plan form and best practices documents developed by the Department.</paragraph>
        <paragraph indent="1">(c)   Emergency safety plans must be submitted and maintained electronically.</paragraph>
      </subsection>
      <subsection heading="22.74.00.06 Plan Review.">
        <paragraph indent="1">(a)   The Department is authorized to review and evaluate each emergency safety plan submitted by a landlord of a multifamily rental building in accordance with Sec. 22-74 of the County Code. The Department will either approve or deny each emergency safety plan.</paragraph>
        <paragraph indent="1">(b)   Plans will be reviewed and evaluated by the Department based on the completeness and compliance with the emergency safety plan form, which includes context pertinent to the evacuation plan of the physical building, activities surrounding evacuation such as emergency services notification and relocation of occupants, and any provisions taken based on the capabilities of occupants that may have additional needs.</paragraph>
        <paragraph indent="1">(c)   An emergency safety plan will only be approved if the Department finds that the contents of the plan are satisfactory to maintain the health, safety, and welfare of all tenants and individuals properly on the premises of multifamily rental housing.</paragraph>
      </subsection>
      <subsection heading="22.74.00.07 Increased Calls for Service – Plan Addendum Required.">
        <paragraph indent="1">(a)   If a multifamily apartment building has ten or more calls for service for fire-related emergencies within a 12-month period, the Director will require the property owner to submit an addendum to the emergency safety plan.</paragraph>
        <paragraph indent="1">(b)   Fire-related emergency service calls include activation of the building automatic fire alarm sent to a listed central station reported to the fire department, activation of the automatic sprinkler system including dry-system activations, and public calls to 9-1-1 indicating an observed fire emergency.</paragraph>
        <paragraph indent="1">(c)   The plan addendum must be submitted on the emergency safety plan addendum template, available from the Department.</paragraph>
        <paragraph indent="1">(d)   Addendums may be discontinued at the discretion of the Director based on a sustained reduction in calls for service to the affected building for a period of at least 12 months.</paragraph>
      </subsection>
      <subsection heading="22.74.00.08 Plan Addendum Contents.">
        <paragraph indent="0">A plan addendum must include, at minimum,</paragraph>
        <paragraph indent="1">(a)   efforts to hire security guards or additional building personnel if the building is experiencing malicious alarms;</paragraph>
        <paragraph indent="1">(b)   repair or replace faulty alarm systems:</paragraph>
        <paragraph indent="2">(1)   if the fire alarm system cannot be repaired, it must be replaced;</paragraph>
        <paragraph indent="2">(2)   if more than five nuisance calls occur in a 12-month period, following unsuccessful efforts to repair the fire alarm system, the fire alarm system must be replaced; and</paragraph>
        <paragraph indent="2">(3)   if the fire alarm system is impaired for greater than 60 days, the fire alarm must be replaced;</paragraph>
        <paragraph indent="1">(c)   facilitate opportunities for the County to provide outreach and educational resources to residents regarding fire safety;</paragraph>
        <paragraph indent="1">(d)   contract with a vendor to provide outreach and educational resources to residents regarding fire safety and prevention of false alarms; or</paragraph>
        <paragraph indent="1">(e)   other fire alarm reduction strategies as determined by the Director, in consultation with MCFRS.</paragraph>
      </subsection>
      <subsection heading="22.74.00.09 Fees.">
        <paragraph indent="1">(a)   The Department may charge a fee for the review or re-review of the emergency safety plan or the addendum.</paragraph>
        <paragraph indent="1">(b)   The charge for review or re-review of emergency safety plans and addendums is $95 per review. Fees must be paid in full prior to the approval of the annual Fire Code Compliance permit.</paragraph>
        <paragraph indent="1">(c)   The Department must calculate and charge an enterprise fund stabilization factor (EFSF) in accordance with COMCOR 22.00.03.08.</paragraph>
      </subsection>
      <subsection heading="22.74.00.10 Enforcement and Penalties.">
        <paragraph indent="1">(a)   The Department may issue a Notice of Violation (NOV) to the landlord for:</paragraph>
        <paragraph indent="2">(1)   failure to submit emergency action plans within 30 days for review and approval to the Department after being notified by the Department;</paragraph>
        <paragraph indent="2">(2)   failure to re-submit plans or addendums requiring corrections or modifications within 30 days as required by the Director;</paragraph>
        <paragraph indent="2">(3)   failure to submit an addendum within 60 days of notice by the Department;</paragraph>
        <paragraph indent="2">(4)   failure to pay fees associated with the review or re-review of emergency safety plans and addendums; or</paragraph>
        <paragraph indent="2">(5)   failure to maintain an approved emergency safety plan, including submittal for re-review by the Department every three years.</paragraph>
        <paragraph indent="1">(b)   If the NOV is not resolved within 30 days of issuance by the Department, a civil citation may be issued by the Director, or the Director’s designee, to the landlord or the landlord’s designee for every 30 days of non-compliance.</paragraph>
        <paragraph indent="1">(c)   Failure to pay required review fees prior to the expiration date of the Fire Code Compliance permit may result in the civil citation being sent the Montgomery County Attorney’s Office Debt Collection Unit.</paragraph>
      </subsection>
    </regulation>
  </section>