<section heading="COMCOR 22.00.02 Regulations Adopting and Amending Certain Standards of the National Fire Code Regarding Fire Protection Systems">
  <regulation heading="COMCOR 22.00.02 Regulations Adopting and Amending Certain Standards of the National Fire Code Regarding Fire Protection Systems">
    <subsection heading="22.00.02.01">
      <paragraph indent="2">In accordance with the procedures authorized in Chapter 22, "Fire Safety Code", of the Montgomery County Code, 1996, this Executive Regulation applies to the design, installation, and maintenance of fire protection systems in buildings or structures.  Where there are differences between this regulation and the Montgomery County Building Code, the more restrictive provision(s) will apply.</paragraph>
      <paragraph indent="2">In this regulation the term “Fire Chief” means the Fire Chief of the Montgomery County Fire and Rescue Service and includes the Fire Chief’s designees.</paragraph>
    </subsection>
    <subsection heading="22.00.02.02">
      <paragraph indent="2">All references to the National Fire Codes and standards adopted in these regulations are to those codes, standards, recommended practices, and manuals in the National Fire Codes, published by the National Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.  Unless otherwise noted, all references to those codes and standards published in the 2003 edition of National Fire Protection Association’s Uniform Fire Code (NFPA 1) are adopted in their entirety.</paragraph>
      <paragraph indent="2">The Fire Chief must review these regulations and propose amendments within six months after the date the State Fire Prevention Commission adopts new amendments to NFPA 1 and NFPA 101 into the State Fire Prevention Code.</paragraph>
    </subsection>
    <subsection heading="22.00.02.03 Fire Protection System Permit">
      <paragraph indent="1">A permit must be obtained from the Fire Chief to operate any fire protection system in any building or other structure, except one and two family dwellings.</paragraph>
      <paragraph indent="2">(a)   Fire protection system means any fire alarm device or system, or suppression device or system, which is designated and installed to:</paragraph>
      <paragraph indent="3">1.   detect, control, or extinguish a fire;</paragraph>
      <paragraph indent="3">2.   alert occupants or the fire department, or both, that a fire has occurred; or</paragraph>
      <paragraph indent="3">3.   be used by fire and rescue personnel on scene to aid in suppressing a fire.</paragraph>
      <paragraph indent="2">(b)   Fire protection systems must be inspected and approved at time of installation and annually thereafter. The Fire Chief must issue a permit upon approval of the system.</paragraph>
      <paragraph indent="2">(c)   A fire protection systems permit must be obtained prior to installation of any kitchen cooking equipment suppression system.</paragraph>
    </subsection>
    <subsection heading="22.00.02.04Fire Protection SystemLicense">
      <paragraph indent="2">A contractor or person responsible for the installation, modification, service, or third-party inspection of any fire protection system or any portion thereof in Montgomery County, must obtain and carry on their person a license from the Fire Chief subject to the following criteria:</paragraph>
      <paragraph indent="2">(a)   Qualifications required.</paragraph>
      <paragraph indent="3">(1)   Residential license (13D and 13R sprinkler systems): National Institute for Certification of Engineering Technologies (NICET) Level II Certification, Registered Professional Engineer Certification, or other nationally recognized certification as approved by the Fire Chief.</paragraph>
      <paragraph indent="3">(2)   General license (all other fire protection systems):  National Institute for Certification of Engineering Technologies (NICET) Level III Certification, Registered Professional Engineer Certification, or other nationally recognized certification as approved by the Fire Chief.</paragraph>
      <paragraph indent="2">(b)   When required by the system manufacturer for systems other than sprinkler systems, proof of training for installing or maintaining particular system types.</paragraph>
      <paragraph indent="2">(c)   Proof of financial stability.</paragraph>
      <paragraph indent="2">(d)   Demonstrated competency in Montgomery County requirements.</paragraph>
      <paragraph indent="2">(e)   Licenses will be subject to annual renewal.</paragraph>
      <paragraph indent="2">(f)   The Fire Chief may rescind these licenses for cause.</paragraph>
    </subsection>
    <subsection heading="22.00.02.05 Maintenance of Residential Sprinkler Systems">
      <paragraph indent="2">All leases must have the following provision: “Sprinkler System. In units equipped with fire sprinkler systems, no portion of the system may be changed or altered except by a licensed, certified sprinkler installer.  Sprinkler heads must not be painted, covered, obstructed, or any item hung from them.  Prior to any alteration of the sprinkler system or any changes, additions, or removal of partitions, or walls, plans must be submitted to the Department of Permitting Services”.</paragraph>
    </subsection>
    <subsection heading="22.00.02.06">
      <paragraph indent="1">Smoke Control System shop drawing submittals must include:</paragraph>
      <paragraph indent="2">(a)   Plans and specifications</paragraph>
      <paragraph indent="2">(b)   Engineering calculations and/or computer model</paragraph>
      <paragraph indent="2">(c)   Floor plans</paragraph>
      <paragraph indent="2">(d)   System diagrams and details</paragraph>
      <paragraph indent="2">(e)   Sequence of operations and control layout</paragraph>
      <paragraph indent="2">(f)   Preliminary test procedures</paragraph>
      <paragraph indent="2">(g)   Acceptance test procedures</paragraph>
      <paragraph indent="2">(h)   Pass/fail criteria</paragraph>
    </subsection>
    <subsection heading="22.00.02.07">
      <paragraph indent="2">NFPA 12A, add: Halon systems shall not be installed as required protection in accordance with the state and/or local building or fire codes due to the environmental impact of discharge testing, the lack of adequate alternative test methods, and availability of alternative agents such as carbon dioxide.</paragraph>
    </subsection>
    <subsection heading="22.00.02.08">
      <paragraph indent="2">NFPA 13, paragraph 8.1.1, add new paragraph (7) as follows:</paragraph>
      <paragraph indent="3">(7)   Sprinklers are required in attached balconies or porches unless at least 50 percent of the longest exterior side is open to the atmosphere.</paragraph>
    </subsection>
    <subsection heading="22.00.02.09">
      <paragraph indent="2">NFPA 13, paragraph 8.4.5.1, add: Listed residential sprinkler heads must be used in dwelling units except Detention and Correctional occupancies.</paragraph>
    </subsection>
    <subsection heading="22.00.02.10">
      <paragraph indent="2">NFPA 13, paragraph 8.14.7.5, add: Sprinklers are not required under noncombustible or limited exterior canopies over drive up windows.  Any canopy with the potential for extended vehicle standing or parking below shall have sprinkler protection on the underside of the canopy.</paragraph>
    </subsection>
    <subsection heading="22.00.02.11">
      <paragraph indent="2">NFPA 13, paragraph 8.14.10.3 (protection of electrical equipment rooms) is deleted.</paragraph>
    </subsection>
    <subsection heading="22.00.02.12">
      <paragraph indent="2">NFPA 13, paragraph 8.14.19.1 is amended as follows: In new installations expected to supply sprinklers below a ceiling and in any speculative areas subject to tenant changes, minimum one inch sprinkler outlets must be provided.</paragraph>
    </subsection>
    <subsection heading="22.00.02.13">
      <paragraph indent="2">NFPA 13, paragraph 8.14.19.2 is amended as follows: after the word “bushings” delete everything and replace with “for hydrostatic testing only, and must be removed prior to the occupancy of the space.”</paragraph>
    </subsection>
    <subsection heading="22.00.02.14">
      <paragraph indent="2">NFPA 13, paragraphs 8.15.1.1.1 and 8.16.1.1, add: When a sprinkler system serves more than one level, each level must be consistently and separately valved by a listed and approved control valve.  In addition, where a sprinkler system is required to activate a local building fire alarm system, the sprinkler system must have a separate and distinct water flow detecting device for each floor and zone.</paragraph>
      <paragraph indent="2">Exception 1:   In buildings not exceeding three floors and 3000 square feet per floor.</paragraph>
      <paragraph indent="2">Exception 2:   Unoccupied and unused attics may be zoned with the level below.</paragraph>
      <paragraph indent="2">Exception 3:   Mezzanines not exceeding 3000 square feet in area.</paragraph>
      <paragraph indent="2">Exception 4:     Detention and correctional facilities.</paragraph>
    </subsection>
    <subsection heading="22.00.02.15">
      <paragraph indent="2">NFPA 13, paragraph 8.16.2, add the following requirements for fire department connections:</paragraph>
      <paragraph indent="2">(a)   Must be located within 100 feet from a free standing (not wall type) hydrant, and between 18 and 48 inches from grade to the centerline of the inlets.</paragraph>
      <paragraph indent="2">(b)   Number of 2 ½  in. inlets:</paragraph>
      <paragraph indent="3">System Demand (gpm)         No. of Inlets</paragraph>
      <paragraph indent="3">up to 749                  2</paragraph>
      <paragraph indent="3">750-999                  3</paragraph>
      <paragraph indent="3">1000 and above               4</paragraph>
      <paragraph indent="2">(c)   Multiple connections for the same building shall be interconnected.</paragraph>
      <paragraph indent="2">(d)   When a section of a building is fed by a connection (i.e., partial systems), permanent all weather identification signs shall be provided on connections.</paragraph>
      <paragraph indent="2">(e)   Must be sized at least as large as the main sprinkler system riser pipe or the fire pump discharge line, whichever is larger.</paragraph>
    </subsection>
    <subsection heading="22.00.02.16">
      <paragraph indent="2">NFPA 13, paragraph 11.1, add:  Calculations for new systems or new portions of systems must meet the criteria below.</paragraph>
      <paragraph indent="2">(a)   Highest hazard and most demanding use allowed by building construction permit or property zoning.</paragraph>
      <paragraph indent="2">(b)   Storage use: Available storage height for high storage of a class 4 non-encapsulated material.</paragraph>
      <paragraph indent="2">(c)   Laboratory use: ordinary group 2 for class A, B, or C labs.</paragraph>
      <paragraph indent="2">(d)   All uses: 20% safety factor. For systems without a pump, this is based on the demand pressure only at the supply point. For systems with a pump, this is based on both the demand pressure and demand flow at the pump discharge.  All design options, except grids, must be explored.</paragraph>
      <paragraph indent="0">Exception to safety factor only: Owner occupied buildings may use a lower safety factor if a pump would be necessary to achieve the 20%.</paragraph>
    </subsection>
    <subsection heading="22.00.02.17">
      <paragraph indent="2">NFPA 13, paragraph 11.2.3.5.1, add: The number of design sprinklers shall be at least 5 under ceilings which are not flat, smooth and level unless specifically listed for a four sprinkler design area.</paragraph>
    </subsection>
    <subsection heading="22.00.02.18">
      <paragraph indent="2">NFPA 13, paragraph 15.1.2, add: Pressure and flow availability as determined by a public utility shall be used for new taps.  Pressure and flow availability for existing taps shall be determined by an interior flow test. In any case, the supply information shall be corrected for the low hydraulic gradient.  Booster pumps and pump/tank supplies shall only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
    </subsection>
    <subsection heading="22.00.02.19">
      <paragraph indent="2">NFPA 13D, paragraph 1.1, add: This standard also applies to Day care homes containing 12 clients or less if located within converted one and two family dwellings or townhouses.</paragraph>
    </subsection>
    <subsection heading="22.00.02.20">
      <paragraph indent="2">NFPA 13D, add new paragraph:</paragraph>
      <paragraph indent="1">5.1.4   Where a dedicated sprinkler booster pump is provided the following conditions must be met:</paragraph>
      <paragraph indent="3">(1)   Pumps shall not sit directly on the floor.</paragraph>
      <paragraph indent="5">(2)   Pumps shall be powered from the house electrical service by a nominal 220-240 circuit as required by Montgomery County Electrical Code.</paragraph>
      <paragraph indent="5">(3)   Power at the pump shall be supervised passively by motor disconnect within sight that also controls a lighting circuit for other than a stair or pump room.</paragraph>
      <paragraph indent="5">(4)   Sprinkler system shall be connected to a bathroom toilet to create a passive purge system.</paragraph>
      <paragraph indent="5">(5)   Pump shall be connected to a time delay relay (run timer).</paragraph>
    </subsection>
    <subsection heading="22.00.02.21">
      <paragraph indent="2">NFPA 13D, paragraph 6.1, add: Pressure and flow availability as determined by a public utility must be used and must be adjusted to the low hydraulic gradient.  Booster pumps and pump/tank supplies may only be used where it is demonstrated that the public water supply is inadequate as determined by the director of the Department of Permitting Services.</paragraph>
    </subsection>
    <subsection heading="22.00.02.22">
      <paragraph indent="2">NFPA 13D, paragraph 6.2: Add section (5) Well pumps</paragraph>
      <paragraph indent="1">(5)   A well pump shall have sufficient capacity and pressure to meet the sprinkler system demand.  The stored water capacity of sections 6.1.2 and 6.1.3 shall be permitted to be a combination of the water in the well (including the refill rate) plus the water in the holding tank if such tank can supply the sprinkler system.</paragraph>
    </subsection>
    <subsection heading="22.00.02.23">
      <paragraph indent="2">NFPA 13D, add new paragraph:</paragraph>
      <paragraph indent="3">6.2.1   Where a water storage tank(s) is provided the following conditions shall be met:</paragraph>
      <paragraph indent="5">(1)   Tank shall be provided with an automatic filling valve (float valve or equivalent).</paragraph>
      <paragraph indent="5">(2)   A method of seeing the water level in the tank shall be provided without having to open the tank.</paragraph>
    </subsection>
    <subsection heading="22.00.02.24">
      <paragraph indent="2">NFPA 13D, paragraph 6.2 (4), add new sentence: “A valve must be provided for routine testing of the pump.”</paragraph>
    </subsection>
    <subsection heading="22.00.02.25">
      <paragraph indent="2">NFPA 13D, 7.1.2, delete “the” in the beginning and add “fed by a tank” after piping.</paragraph>
    </subsection>
    <subsection heading="22.00.02.26">
      <paragraph indent="2">NFPA 13D, section 7.5.5.1, add: Where possible to maintain listed coverage, sprinkler heads shall be positioned so as to eliminate the need to install sprinkler heads of a higher temperature rating.</paragraph>
    </subsection>
    <subsection heading="22.00.02.27">
      <paragraph indent="2">NFPA 13D, paragraph 7.5.5, add new paragraph 7.5.5.4:</paragraph>
      <paragraph indent="3">7.5.5.4   Dry type sprinklers shall be used in areas which are not heated to at least 40 degrees F.</paragraph>
    </subsection>
    <subsection heading="22.00.02.28">
      <paragraph indent="2">NFPA 13D, paragraph 8.1.2, add: The number of design sprinklers shall be at least three under ceilings which are not flat, smooth, and level, unless specifically listed with a two sprinkler design area.</paragraph>
    </subsection>
    <subsection heading="22.00.02.29">
      <paragraph indent="2">NFPA 13D, paragraph 8.2.4 is amended as follows:</paragraph>
      <paragraph indent="2">Obstructions:</paragraph>
      <paragraph indent="2">(a)   Sprinklers shall be positioned so that response time and discharge are not adversely affected by features such as sloped ceilings, beams, lights, and fan motors.</paragraph>
      <paragraph indent="2">(b)   Unprotected bulkheads or soffits behind the spray of sidewall sprinklers shall not exceed 8 inches in width.</paragraph>
      <paragraph indent="2">(c)   Sprinkler heads in closets shall not be located directly above shelves.</paragraph>
    </subsection>
    <subsection heading="22.00.02.30">
      <paragraph indent="2">NFPA 13D, paragraph 8., add: All calculations shall include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
    </subsection>
    <subsection heading="22.00.02.31">
      <paragraph indent="2">NFPA 13D, paragraph 8.6.4, add the following after garages: “...unless located partially or wholly beneath living space.”</paragraph>
    </subsection>
    <subsection heading="22.00.02.32">
      <paragraph indent="2">NFPA 13R, paragraph 6.5.3, add: Pressure and volume availability as determined by a public utility shall be used and shall be adjusted to the low hydraulic gradient. Booster pumps and pump/tank supplies may only be used where it is demonstrated that the public water supply is inadequate.</paragraph>
    </subsection>
    <subsection heading="22.00.02.33">
      <paragraph indent="2">NFPA 13R, paragraph 6.6.4.1 is replaced to read: In all apartment buildings, a single 2 ½ in. fire department connection with a feed line sized at least as large as the main system riser shall be provided when the system has 20 or more sprinklers.  The fire department connection shall be located on a street front and be 18 to 48 inches from the centerline of the inlet to finish grade.  Paragraph 6.6.4.2 is deleted.</paragraph>
    </subsection>
    <subsection heading="22.00.02.34">
      <paragraph indent="2">NFPA 13R, paragraph 6.7.1.2, add: The number of design sprinklers shall be at least five under ceilings which are not flat, smooth and level unless specifically listed with a four sprinkler design area.</paragraph>
    </subsection>
    <subsection heading="22.00.02.35">
      <paragraph indent="2">NFPA 13R, paragraph 6.7.1.5.3 is amended as follows:</paragraph>
      <paragraph indent="2">Obstructions:</paragraph>
      <paragraph indent="2">(a)   Sprinklers shall be positioned so that response time and discharge are not adversely affected by features such as sloped ceilings, beams, lights, and fan motors.</paragraph>
      <paragraph indent="2">(b)   Unprotected bulkheads or soffits behind the spray of side wall sprinklers shall not exceed 8 inches in width.</paragraph>
      <paragraph indent="2">(c)   Sprinkler heads in closets must not be located directly above shelves.</paragraph>
    </subsection>
    <subsection heading="22.00.02.36">
      <paragraph indent="2">NFPA 13R, paragraph 6.7.4, add: All calculations must include at least a 10% safety factor to account for minor field changes, unless a booster pump is necessary to obtain this safety factor.</paragraph>
    </subsection>
    <subsection heading="22.00.02.37">
      <paragraph indent="2">NFPA 14, paragraph 4.7.2 is amended as follows: Each fire hose valve shall be provided with</paragraph>
      <paragraph indent="0">2 ½  in. valved hose connections, 2 ½  in. to 1 ½  in. reducers, caps, and chains.</paragraph>
    </subsection>
    <subsection heading="22.00.02.38">
      <paragraph indent="2">NFPA 14, paragraph 5.1.2, add:</paragraph>
      <paragraph indent="2">(1)   Systems shall be automatic wet type.</paragraph>
      <paragraph indent="2">(2)   Standpipe systems in unheated areas shall be automatic dry type.</paragraph>
      <paragraph indent="2">(3)   Standpipe systems in detached open parking garages may be the manual dry type, if the piping is air supervised for breaks or open valves.</paragraph>
      <paragraph indent="2">(4)   Occupant use hose is prohibited in new or existing buildings.</paragraph>
      <paragraph indent="2">(5)   New standpipe systems shall be Class 1 only.</paragraph>
    </subsection>
    <subsection heading="22.00.02.39">
      <paragraph indent="2">NFPA 14, paragraph 6.3 (Fire Department Connections), add:</paragraph>
      <paragraph indent="2">(1)   Shall be located within 100 feet from a free standing (not wall type) hydrant.</paragraph>
      <paragraph indent="2">(2)   Number of 2 ½  in. inlets:</paragraph>
      <paragraph indent="3">System Demand (gpm)      No. of Inlets</paragraph>
      <paragraph indent="3">up to 749            2</paragraph>
      <paragraph indent="3">750-999            3</paragraph>
      <paragraph indent="3">1,000 and above         4</paragraph>
      <paragraph indent="2">(3)   Multiple connections on the same building shall be interconnected.</paragraph>
      <paragraph indent="2">(4)   When a section of a building is fed by a connection (i.e., partial systems), permanent all weather identification signs shall be provided on connections.</paragraph>
    </subsection>
    <subsection heading="22.00.02.40">
      <paragraph indent="2">NFPA 14, paragraph 7.3.2.3, add:</paragraph>
      <paragraph indent="2">(1)   Measurement shall be parallel or at right angles to walls.</paragraph>
      <paragraph indent="2">(2)   Supplemental hose valves outside the stairs shall not be located within tenant spaces, unless hose reach requirements cannot be met by placement of valves in public corridors or by use of wall hydrants for spaces opening to the exterior. Hose valve locations shall be marked by the placement of signs, the striping of columns, or other approved methods.</paragraph>
    </subsection>
    <subsection heading="22.00.02.41">
      <paragraph indent="2">NFPA 14, paragraph 7.8.1.1, add exceptions:</paragraph>
      <paragraph indent="2">Exception No. 1:   In high-rise buildings, where booster pumps are necessary to produce the required residual pressures, pumps and piping systems must be sized to provide for the demand of the hydraulically most remote hose station, or the sprinkler system demand, whichever is greater. The standpipe system must also be sized to provide the required flow and pressure for all hose stations required to be flowing, when supplied by 150 psi at 1000 gpm at the fire department connection(s). Two sets of calculations will, therefore, be required under this exception.</paragraph>
      <paragraph indent="2">Exception No. 2:   Systems in buildings that are not high rise, and dry systems with no automatic water supply, may be sized to obtain the required flows and pressures, when supplied by 150 psi at 1000 gpm at the fire department connection(s).</paragraph>
      <paragraph indent="2">Exception No. 3:   In existing buildings, after shell occupancy, hose valves added to correct reach violations created by tenant modifications may be supplied by 3 inch pipe without recalculation.</paragraph>
    </subsection>
    <subsection heading="22.00.02.42">
      <paragraph indent="2">NFPA 20, paragraph 5.14.6.4, add a new sentence: Eccentric reducers must be installed with the flat side on the bottom when fed directly from above.</paragraph>
    </subsection>
    <subsection heading="22.00.02.43">
      <paragraph indent="2">NFPA 20, paragraph 5.18.1.2, add: A relief valve may be installed to reduce operating pressure below 175 psi at high gradient.</paragraph>
    </subsection>
    <subsection heading="22.00.02.44">
      <paragraph indent="2">NFPA 20, paragraph 5.18.7 is amended entirely to state: Relief valves shall not be piped back into the source of the supply.</paragraph>
    </subsection>
    <subsection heading="22.00.02.45">
      <paragraph indent="2">NFPA 72, paragraph 4.4.6.1, add the following sentence: An annunciator with the following features is required when the building is greater than one story, over 20,000 square feet in area per floor, or has more than one type of alarm initiating device.</paragraph>
      <paragraph indent="2">Exception No. 1:   Apartments protected by a 13R sprinkler system.</paragraph>
      <paragraph indent="2">Exception No. 2:   Any building not exceeding two stories above grade and 3,000 square feet per floor.</paragraph>
      <paragraph indent="2">(a)   Annunciator shall have a visible signal for each different floor, zone, and device type. Supervised computer screen or printer type annunciators may be used to meet this requirement if the zone identification is approved by the Fire Chief.</paragraph>
      <paragraph indent="2">(b)   Zones shall not exceed a single floor, 20,000 square feet, or 300 linear feet. Sprinkler systems may be zoned in accordance with the applicable sprinkler standard.</paragraph>
      <paragraph indent="2">(c)   If two or more zones per floor are required, a graphic outline on or adjacent to the annunciator shall be provided showing the building outline, zone boundaries, "you are here" notation, north compass arrow, all stairways, stairway identification numbers, all standpipe risers, elevators, and the building address.</paragraph>
      <paragraph indent="2">(d)   A lamp type annunciator shall have a lamp test switch unless the annunciator circuits are supervised.</paragraph>
      <paragraph indent="2">(e)   The annunciator shall be located at, and visible from, the main fire department entrance.</paragraph>
      <paragraph indent="2">(f)   If two or more buildings are controlled by one alarm system, an annunciator shall be installed in each building with a pilot lamp indicating the building of alarm origination.</paragraph>
    </subsection>
    <subsection heading="22.00.02.46">
      <paragraph indent="2">NFPA 72, add new paragraph 5.7.3.2.5:</paragraph>
      <paragraph indent="1">5.7.3.2.5   Detectors which activate required extinguishing systems on a cross-zoned or multiple-zone basis shall be spaced at a maximum of one-half of their allowed or listed square footage spacing.</paragraph>
    </subsection>
    <subsection heading="22.00.02.47">
      <paragraph indent="2">NFPA 72, paragraph 5.7.4.2.2, add: Activation of duct smoke detectors must sound an audible alarm in a normally occupied area or through the building fire alarm system, and must be identified as duct detector trouble.  If connected to the building alarm, the signal must be supervisory only and must not initiate the building evacuation alarm unless a confirmation or verification feature is provided to minimize unwanted alarms.</paragraph>
    </subsection>
    <subsection heading="22.00.02.48">
      <paragraph indent="2">NFPA 72, paragraph 5.7.1.7 is amended as follows: Detectors located at the top of shafts and stairs must be on a supervisory circuit only unless a confirmation or verification feature is provided to minimize unwanted alarms. The location must be identified at the annunciator or fire alarm control panel.</paragraph>
    </subsection>
    <subsection heading="22.00.02.49">
      <paragraph indent="2">NFPA 72, paragraph 5.10.2, add: Standpipe or main water flow indicators, if provided, must sound a supervisory signal only.</paragraph>
    </subsection>
    <subsection heading="22.00.02.50">
      <paragraph indent="2">NFPA 72, the second sentence under paragraph 5.12.4 is changed to read "The center of each station must be between 42 and 48 inches above the floor level." Also, this paragraph shall be amended by the addition of the following: Approved "911" instruction signs shall be permanently affixed and maintained at each manual fire alarm station, unless the fire alarm is monitored by a UL listed central station.</paragraph>
    </subsection>
    <subsection heading="22.00.02.51">
      <paragraph indent="2">NFPA 72, paragraph 6.9.9.14 is amended as follows: At least six handsets shall be provided in the fire control room.</paragraph>
    </subsection>
    <subsection heading="22.00.02.52">
      <paragraph indent="2">NFPA 72, paragraphs 11.5.1.1, 11.5.2.1, and 11.5.4.1: delete the exception for each section.</paragraph>
    </subsection>
    <subsection heading="22.00.02.53">
      <paragraph indent="2">NFPA 72, paragraph 11.5.6.1 (4) is deleted.</paragraph>
    </subsection>
    <subsection heading="22.00.02.54">
      <paragraph indent="2">NFPA 72, paragraph 11.5.8.1 (2), delete the exception.</paragraph>
    </subsection>
    <subsection heading="22.00.02.55">
      <paragraph indent="2">NFPA 72, paragraph 11.5.12.1 (2), delete the exception.</paragraph>
    </subsection>
    <subsection heading="22.00.02.56">
      <paragraph indent="2">NFPA 72, paragraph 11.8.3.5, add new paragraphs (10) and (11):</paragraph>
      <paragraph indent="2">(10)   Separate entrances to sleeping rooms shall be protected separately unless the door leads only to a bathroom or clothes/linen closet.</paragraph>
      <paragraph indent="2">(11)   Enclosed rooms such as dens, libraries, studies, or sitting rooms which could be used as a temporary sleeping area shall be treated as bedrooms.</paragraph>
    </subsection>
  </regulation>
</section>