Sec. 22-156. Table 5

Codified through Bill No. CB-018-2026, adopted May 12, 2026, effective July 24, 2026. Source: Municode, Supplement 2026 Update 2. Editorial notes and legislative history omitted.

Prince George's County, Md., Code § 22-156 (2026)

Sec. 22-156. Table 5Copy Citation

(a)
Septic Tank Capacity and Design Flow.
RESIDENTIAL SINGLE-COMPARTMENT TANK
GROSS SQUARE FOOTAGESEPTIC TANK CAPACITYDESIGN FLOWMINIMUM DRAINFIELD LENGTH
0 - 1,750 sq. ft1,000 gals.720 gal/day70
1,751 - 2,250 sq. ft1,500 gals.900 gal/day100
2,251 - 3,000 sq. ft1,750 gals.1,000 gal/day120
> 3,000 sq. ft2,000 gals.1,000 gal/day130
RESIDENTIAL DOUBLE-COMPARTMENT TANK
GROSS SQUARE FOOTAGESEPTIC TANK CAPACITYDESIGN FLOWMINIMUM DRAINFIELD LENGTH
0 - 1,750 sq. ft1,000 gals.720 gal/day70
1,751 - 2,250 sq. ft1,250 gals.900 gal/day100
2,251 - 3,000 sq. ft1,500 gals.1,000 gal/day120
> 3,000 sq. ft1,800 gals.1,000 gal/day130
(b)
Commercial Septic Tank Capacity.
(1)
Tank Capacity will be based on a forty-eight (48) hour retention capacity as calculated from the average sewage flow.
(2)
Two-compartment septic tanks shall be required for commercial establishments having a design flow in excess of 1,000 gallons/day.