Sec. 4-143. General Building Heights and Areas; Section 509, Incidental Uses

Codified through Bill No. CB-018-2026, adopted May 12, 2026, effective July 24, 2026. Source: Municode, Supplement 2026 Update 2. Editorial notes and legislative history omitted.

Prince George's County, Md., Code § 4-143 (2026)

Sec. 4-143. General Building Heights and Areas; Section 509, Incidental UsesCopy Citation

The following additions are made to Table 509 of the IBC:
(a)
Room or AreaSeparation and/or Protection
Storage areas 1 over 1,000 square feet not in an S or F1 hour or Automatic Sprinkler Protection
Storage areas 1 over 2,500 square feet not in an S or F1 hour and Automatic Sprinkler Protection
New residential buildings with attached garages and carports where rooms or spaces store electric powered vehicles2 hour fire barrier with 90 minute door and heat detector
Note: 1 Storage areas include walk-in freezers and refrigerators.
(b)
Electric energy storage systems shall comply with IFC, Section 1207, and NFPA 1. When there is a conflict the most stringent code shall apply. Electrochemical Energy Storage Systems with 15 kWh or more capacity, located within 100 feet of a residential, school, library or hospital area shall have a minimum 2-hour fire resistance rated exterior walls and ceilings with opening protectives and ventilation systems.