<section number="4-143" name="General Building Heights and Areas; Section 509, Incidental Uses" law="code" slug="sec-4-143" node_id="PTIITI17PULOLAPRGECOMA_SUBTITLE_4BU_DIV1BUCO_SD2AMINBUCO_S4-143GEBUHEARSE509INUS">
  <text>The following additions are made to Table 509 of the IBC:</text>
  <level label="a">
    <table>
      <row>
        <cell>Room or Area</cell>
        <cell>Separation and/or Protection</cell>
      </row>
      <row>
        <cell>Storage areas 1 over 1,000 square feet not in an S or F</cell>
        <cell>1 hour or Automatic Sprinkler Protection</cell>
      </row>
      <row>
        <cell>Storage areas 1 over 2,500 square feet not in an S or F</cell>
        <cell>1 hour and Automatic Sprinkler Protection</cell>
      </row>
      <row>
        <cell>New residential buildings with attached garages and carports where rooms or spaces store electric powered vehicles</cell>
        <cell>2 hour fire barrier with 90 minute door and heat detector</cell>
      </row>
      <row>
        <cell>Note: 1 Storage areas include walk-in freezers and refrigerators.</cell>
      </row>
    </table>
  </level>
  <level label="b">
    <text>Electric energy storage systems shall comply with IFC, Section 1207, and NFPA 1. When there is a conflict the most stringent code shall apply. Electrochemical Energy Storage Systems with 15 kWh or more capacity, located within 100 feet of a residential, school, library or hospital area shall have a minimum 2-hour fire resistance rated exterior walls and ceilings with opening protectives and ventilation systems.</text>
  </level>