    <text>General. Sprinklers systems designed in accordance with NFPA 13D shall be protected from backflow in accordance with the WSSC Plumbing and Fuel Code.</text>
  </level>
  <level label="b">
    <text>Section 903.2.1, General. Approved automatic sprinkler systems in buildings and structures shall be provided in the locations described in this Section. For the purposes of this Section, the fire area is defined as the aggregate floor area enclosed and bounded by firewalls, exterior walls, fire barriers or horizontal assemblies of a building. Areas of the building not provided with surrounding walls shall be included in the fire area if such areas are included within the horizontal projection of the roof or floor next above.</text>
    <level label="1">
      <text>Repairs to Residential Structures. Use Group R-1, Use Group R-2, Use Group R-3, and Use Group R-4 which, because of lack of maintenance or structural damage due to a fire, explosion, or natural causes, undergo repairs or renovations which, in the opinion of the Director or the Director's designee, exceed fifty percent (50%) of the building shall have an approved automatic fire sprinkler system installed throughout the building as part of the scope of repairs to be completed.</text>
    </level>
  </level>
  <level label="c">
    <text>Section 903.2.1.1, Group A-1. An automatic sprinkler system shall be provided throughout stories and a fire area containing a Group A-1 occupancy to and including intervening floors and the level of exit discharge serving that occupancy where one of the following conditions exists:</text>
    <level label="1">
      <text>The fire area exceeds six thousand (6,000) square feet;</text>
    </level>
    <level label="2">
      <text>The fire area has an occupant load of three hundred (300) or more;</text>
    </level>
    <level label="3">
      <text>The fire area is located on a floor other than the level of exit discharge serving such occupancies; or</text>
    </level>
    <level label="4">
      <text>The fire area contains a multi-theatre complex.</text>
    </level>
  </level>
  <level label="d">
    <text>Section 903.2.1.3, Group A-3. An automatic sprinkler system shall be provided throughout stories and fire area containing a Group A-3 occupancy to and including intervening floors and the level of exit discharge serving that occupancy where one of the following conditions exists:</text>
    <level label="1">
      <text>The fire area exceeds six thousand (6,000) square feet;</text>
    </level>
    <level label="2">
      <text>The fire area has an occupant load of three hundred (300) or more; or</text>
    </level>
    <level label="3">
      <text>The fire area is located on a floor other than the level of exit discharge.</text>
    </level>
  </level>
  <level label="e">
    <text>Section 903.2.1.4, Group A-4. An automatic sprinkler system shall be provided throughout stories and a fire area containing a Group A-4 occupancy to and including intervening floors and the level of exit discharge serving that occupancy where one of the following conditions exists:</text>
    <level label="1">
      <text>The fire area exceeds six thousand (6,000) square feet;</text>
    </level>
    <level label="2">
      <text>The fire area has an occupant load of three hundred (300) or more; or</text>
    </level>
    <level label="3">
      <text>The fire area is located on a floor other than the level of exit discharge.</text>
    </level>
    <text>Exception: Sprinklers shall not be required directly over participant floor areas or swimming areas of buildings occupied exclusively for indoor participant sports such as indoor firearm ranges without tactical floor exercises, tennis, skating, swimming and equestrian activities, provided that the main floor area is located at the same level as the level of exit discharge of the main entrance and exit, and the building owner furnishes to the Director or the Director's designee a notarized statement acknowledging that the future use of the unprotected sporting floor areas of the facility will be limited to sporting activities of a low hazard nature with minimal occupant loadings and no combustibility of the contents and furnishings other than necessary to the sporting events.</text>
  </level>
  <level label="f">
    <text>Under 903.2.6 Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area.</text>
    <text>Exception: Family Home Daycare exceeding eight (8) and up to twelve (12) shall provide automatic sprinkler as per 903.3.1.3 throughout the entire building. Existing residential homes governed by the International Residential Code (IRC), without a fire protection sprinkler system, used for Family Home Daycare with five (5) or less occupants receiving care shall not be required to install a new sprinkler system required by IRC.</text>
  </level>
  <level label="g">
    <text>Section 903.2.7, Group M. An automatic sprinkler system shall be provided throughout buildings where the fire area containing a Group M occupancy where one of the following conditions exists:</text>
    <level label="1">
      <text>A Group M fire area exceeds six thousand (6,000) square feet.</text>
    </level>
    <level label="2">
      <text>A Group M fire area is located more than two (2) stories above grade plane.</text>
    </level>
    <level label="3">
      <text>The combined fire area on all floors, including any mezzanines, exceeds twelve thousand (12,000) square feet.</text>
    </level>
    <level label="4">
      <text>A Group M occupancy used for the sales, storage, or display of upholstered furniture or mattresses over five thousand (5,000) square feet.</text>
    </level>
  </level>
  <level label="h">
    <text>Section 903.2.7.1, High-Piled Storage. An automatic sprinkler system shall be provided in all buildings of Group M where storage of merchandise is in high-piled or rack storage arrays. High-piled storage shall be considered storage in excess of twelve (12) feet above the floor for purposes of this Section.</text>
  </level>
  <level label="i">
    <text>Section 903.2.8, Group R-2. An automatic sprinkler system shall be provided throughout buildings with a Group R-2 fire area. The following reductions in construction requirements are permitted when a building of use Group R-2 is fully sprinklered and is not over four (4) stories above grade on any side of the building:</text>
    <level label="1">
      <text>Attic sprinklers may be omitted provided that the ceiling of the top level is of five-eighths (5/8) inch fire code type gypsum board and the attic is draft stopped at each two (2) units maximum and all ceiling ductwork penetrations are provided with UL listed ceiling dampers;</text>
    </level>
    <level label="2">
      <text>Section 11-258 of the County Code (County Fire Safety Law) requiring heat detectors in apartments is not applicable;</text>
    </level>
    <level label="3">
      <text>Balconies of apartments may be of combustible construction, provided the balconies are sprinklered;</text>
    </level>
    <level label="4">
      <text>Sprinklers may be omitted from open-air exterior stair enclosures provided that a Class A finish is used in the stairs; and</text>
    </level>
    <level label="5">
      <text>Balcony soffit vents in unsprinklered attics are permitted.</text>
    </level>
  </level>
  <level label="j">
    <text>Section 903.2.9, Group S-1. An automatic sprinkler system shall be provided throughout buildings where the fire area containing a Group S-1 where one of the following conditions exists:</text>
    <level label="1">
      <text>Occupancy exceeds six thousand (6,000) square feet.</text>
    </level>
    <level label="2">
      <text>Where fire area is located more than two (2) stories above grade plane.</text>
    </level>
    <level label="3">
      <text>Where a Group S-1 fire area used for the storage of commercial motor vehicles where fire area exceeds five thousand (5,000) square feet.</text>
    </level>
    <level label="4">
      <text>The combined area of all Group S-1 fire areas on all floors, including mezzanines, exceeds 24,000 square feet (2230 m2).</text>
    </level>
  </level>
  <level label="k">
    <text>Section 903.2.9.4 Group S-1 upholstered furniture and mattresses. An automatic sprinkler system shall be provided throughout a Group S-1 fire area where the combined areas used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2).</text>
  </level>
  <level label="l">
    <text>Section 903.3.9, Riser and Water Supply Requirements. Every building which is required to be fully sprinklered shall be provided with a complete and separate sprinkler system riser. The riser shall include an alarm check valve or indicating device and check valve, a drain and connection for a fire department pumping connection and a control valve. The arrangement and location shall be subject to the approval of the authority having jurisdiction. A separate main supply source shall be required for each system riser. The system supply shall be based upon the low hydraulic grade shown on the Hydraulic Information Sheet, as determined by the Washington Suburban Sanitary Commission or lowest hydraulic point per the water authority in areas not served by WSSC. The demand for the automatic sprinkler system must be below the available water supply curve, unless approved by the Fire Code Official or designee as follows:</text>
    <level label="1">
      <text>Automatic sprinkler demand plus, 10% or 10 psi, whichever is greater for commercial systems under NFPA 13 and NFPA13R.</text>
    </level>
    <level label="2">
      <text>Automatic sprinkler demand plus 5% or 5 psi, whichever is greater for residential systems for under NFPA 13D.</text>
    </level>
  </level>
  <level label="m">
    <text>Section 903.6, Zones. Automatic fire suppression system zones shall coincide with the fire alarm zones required in Section 907.6.4 of this Code unless specifically exempted by the Director or the Director's designee.</text>
  </level>
  <level label="n">
    <text>Section 903.7, Thermal Protection. Heat tracing tape shall not be an acceptable means of thermal protection for any portion of a fire suppression system.</text>
    <text>Exception: Wet pipe suppression systems with heat trace tape specifically listed for intended application and installed in accordance with the listing as acceptable as approved by the Director or the Director's designee.</text>
  </level>
  <level label="o">
    <text>Section 903.3.7.1, Mechanical Protection. All piping comprising any portion of a fire protection system shall be protected against reasonable mechanical vehicular damage.</text>
  </level>