<section number="4-231" name="Mechanical Ventilation; Section 403" law="code" slug="sec-4-231" node_id="PTIITI17PULOLAPRGECOMA_SUBTITLE_4BU_DIV1BUCO_SD3AMINMECO_S4-231MEVESE403">
  <level label="a">
    <text>NFPA 90A 6.2 - A single point master shutoff switch shall be provided for the fire department which is capable of shutting down all air handling equipment to prevent the spread of smoke through the building. The switch shall be located at the entrance, inside lobby, near fire alarm annunciator or in fire control room where one present.</text>
  </level>
</section>