Subdivision 4. Amendments to the International Residential Code for One- and Two-Family Dwellings
Codified through Bill No. CB-018-2026, adopted May 12, 2026, effective July 24, 2026. Source: Municode, Supplement 2026 Update 2. Editorial notes and legislative history omitted.
Subdivision 4. Amendments to the International Residential Code for One- and Two-Family Dwellings
Prince George's County, Md., Code § 4-240 (2026)
Sec. 4-240. Amendments to the International Residential Code for One- and Two-Family DwellingsLinkCopy Citation
(a)
The following deletions and amendments are made to the International Residential Code for One- and Two-Family Dwellings:
(1)
Chapters 25-33 of Part VII - Plumbing are hereby deleted and replaced with the Plumbing and Gasfitting Regulations adopted by the Washington Suburban Sanitary Commission (WSSC), known as the WSSC Plumbing and Fuel Gas Code.
(2)
Chapters 34 through 43 of Part VIII - Electrical are hereby deleted and replaced with Subtitle 9 of the County Code.
(3)
Section R112.2 is hereby amended to read as follows: Limitations on Authority. An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply or an equally good or better form of construction is proposed. The board shall not have authority to waive requirements of this code and shall not have jurisdiction over matters for which adjudication or appeal is expressly assigned to the procedures outlined in Section 13, Division 15 of this Code.
(4)
Properties where the structure is being razed and where a new structure is being constructed will be considered new single family dwelling units and will be subjected to applicable public safety and school surcharges as defined by the Fee Table in Section 2-253.63.
Prince George's County, Md., Code § 4-240.01 (2026)
Sec. 4-240.01. Building Planning; Section R-302, Fire Resistant ConstructionLinkCopy Citation
(a)
Section R-302.2.2, Parapets. Parapets constructed in accordance with Section R-302.2.3 shall be provided for townhouses as an extension of common exteriors or walls in accordance with the following:
(1)
Where roof surfaces adjacent to the wall or walls are at the same elevation, the parapet shall extend not less than thirty (30) inches above the roof surfaces; and
(2)
Where roof structures adjacent to the wall or walls are at different elevations and the higher roof is not more than thirty (30) inches above the lower roof, the parapet shall extend not less than thirty (30) inches above the lower roof surface.
Exception: A parapet is not required in Subsections (1) and (2) of this Section when townhouses are provided with residential sprinkler systems installed in accordance with Section 903 of the IBC, or when the roof is covered with a minimum Class C roof covering and the roof decking or sheathing is of noncombustible materials or approved fire-retardant treated wood for a distance of four (4) feet on each side of the wall or walls, or one layer of five-eighths (5/8) inch, or Type X gypsum board is installed directly beneath the roof decking or sheathing for a distance of four (4) feet on each side of the wall or walls.
(3)
A parapet is not required where roof surfaces adjacent to the wall or walls are at different elevations and the higher roof is more than thirty (30) inches above the lower roof. The common wall construction from the lower roof to the underside of the higher roof deck shall not have less than a one (1) hour fire-resistive rating. The wall shall be rated for exposure from both sides.
(4)
All new one- and two-family dwellings and town homes up to 3 stories in height with private garages and carports shall have a 1 hour fire barrier/separation with 45 minute door and heat detector.
Prince George's County, Md., Code § 4-241 (2026)
Sec. 4-241. Building Planning; Section R-303, Light, Ventilation, Sound and HeatingLinkCopy Citation
(a)
Section R-303.3.1 is added to read as follows: "Illumination of Toilet Rooms and Bathrooms." Illumination of toilet rooms and bathrooms is to be the equivalent of at least three (3) foot candles.
(b)
Section R-303.4.1 (IRC) is added to read as follows:
(1)
"Locations." Every door which opens directly from any one or two-family dwelling to the outdoors; fifty percent (50%) of the nominal area of every double-hung and horizontal sliding window, and that portion of every other type window normally used for ventilation; and all other openings, unless specifically exempt or modified by the Building Official in accordance with the hardship or modification provisions of this Subtitle and the IRC, shall be screened with not less than sixteen (16) mesh per inch material. In addition, every hinged screen door shall have a self-closing device in good working condition. Screen doors shall not be required on the main entrance door.
(2)
"Governing Code." Screens required by this Section shall be installed or be available to be installed on all dwelling units. The actual times that screens must be provided and installed for use on all dwellings will be governed by the Prince George's County Housing Code. These provisions shall be applicable to all dwelling structures irrespective of the date of construction.
(c)
Sound Transmission Class (STC) — Appendix AK is hereby adopted.
(d)
Section R-303.7.2 is added to read as follows: "Minimum Illumination of Stairwells." Minimum illumination of stairwells is to be the equivalent of at least three (3) foot candles. In all one- and two-family dwellings, at least one (1) light illuminating a stair shall be controlled by wall switches at each end of the stair. All exterior steps shall be provided with a light controlled by a switch on the interior.
Prince George's County, Md., Code § 4-241.01 (2026)
Sec. 4-241.01. Range Hoods; Section M1503.6, Make Up Air RequiredLinkCopy Citation
(a)
The following revision is made to Section M1503.6 Make Up Air Required of the International Residential Code:
(1)
M1503.6. Makeup air required. Exhaust hood systems capable of exhausting more than 400 cubic feet per minute (0.19m 3 /s) shall be mechanically or naturally provided with makeup air at a rate approximately equal to the exhaust air rate in excess of 400 cubic feet per minute. Such makeup air systems shall be equipped with not less than one damper. Each damper shall be a gravity damper or an electrically operated damper that automatically opens when the exhaust system operates. Dampers shall be accessible for inspection, service, repair and replacement without removing permanent construction or any other ducts not connected to the damper being inspected, serviced, repaired or replaced.
Prince George's County, Md., Code § 4-242 (2026)
Sec. 4-242. Building Planning; Section R-309, Garages and CarportsLinkCopy Citation
(a)
Section R309.2.1 — Rooms or spaces that store electric powered vehicles shall be separated from adjacent spaces by one (1) hour fire-resistance rating walls, ceilings, opening protectives and shall contain a heat detector which upon activation will result in local alarm.
(b)
Section R-309.6 is added to read as follows: "Interconnecting Doors." All doors between garages and living spaces of the one- and two-family dwellings shall be provided with a self-closing device. The self-closer may be non-listed but must be sufficient to close and latch the door from an open position of twelve (12) inches.
Prince George's County, Md., Code § 4-243 (2026)
Sec. 4-243. Building Planning; Section R-311, Means of EgressLinkCopy Citation
(a)
Section R-311.4, Minimum Number of Exits in Existing One- and Two-Family Dwellings. One- and two-family dwellings that undergo basement improvements for which a building permit is required and the work performed will render the area as "Habitable" shall have a minimum of two (2) exits. All basements must have an exit door or an emergency escape and rescue opening leading directly to the outside grade in addition to an interior stair leading to the primary means of egress of the dwelling unit.
(b)
Section R-311.7.5, Stair Treads and Risers. The maximum riser height shall be eight and one-fourth (8¼) inches, and the minimum tread depth shall be nine (9) inches. The riser height shall be measured vertically between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The walking face of treads and landings of a stairway shall be sloped no steeper than one (1) unit vertical in forty-eight (48) units horizontal two percent (2%) slope. The greatest riser height within any flight of stairs shall not exceed the smallest by more than three-eighths (3/8) inch. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than three-eighths (3/8) inch.
(c)
Section R-312.1.3, Ladder Effect. Guards where required shall not be constructed so as to have an ornamental pattern that would provide a ladder effect.
Prince George's County, Md., Code § 4-244 (2026)
Sec. 4-244. Scope and Administration: Section R105, PermitsLinkCopy Citation
(a)
Section R105.2, Work Exempt from Permit. Notwithstanding the foregoing, except for property located within Chesapeake Bay Critical Area Overlay Zones, permits shall not be required for the following, provided that the construction does not result in any violation of this Subtitle and the building codes:
(1)
Building Permits:
(a)
A one-story detached accessory structure (tool, storage shed, playhouse and similar uses) on one- and two-family dwelling properties with less than one hundred fifty (150) square feet of floor space not designed or intended for occupation or habitation and limited to one (1) accessory structure only per property.
(b)
All forms of impervious area less than five hundred (500) square feet except for parking surfaces (per property/lot) and except for impervious area in the public road right of way.
(c)
A retaining wall not greater than two (2) feet in height unless supporting a structure.
(d)
Fence(s) four (4) feet or less in height a permit is not required except fences on a corner lot per Subtitle 27-421.
(1)
Any component of fencing, regardless of height, that obstructs the public or private pedestrian path, building structure, access to a cross-walk or sidewalk, or other paved portion of the right-of-way; shall be prohibited,
(e)
Satellite dish(es) not greater than two (2) feet in diameter and height.
(f)
Residential: Installation of siding including vinyl siding replacement, roofing, or storm door/window installations, provided that no construction is involved.
(g)
Painting, papering, tiling (floor), carpeting, installation of cabinets, countertops and similar finish work.
(h)
Prefabricated swimming pools accessory to a one- and two-family dwelling occupancy (not any other use group or public swimming pool) that are less than 24 inches deep, are not greater than 5,000 gallons and are installed entirely above ground provided a four-foot fence is installed around the pool perimeter.
(i)
Swings and other playground equipment accessory to detached one- and two-family dwelling.
(j)
An agricultural building per Maryland Code, Pub. Safety § 12-508 and Subtitle 27. Consult with Prince George's Soil Conservation District for approval/permitting requirements.
(k)
Unless required by the Code Official or designee, replacement (in-kind) of non-fire rated interior/exterior doors, with same door hardware and windows with no structural modification.
(l)
If any of the above activities in this Section result in land disturbance that exceeds 5,000 square feet, exceeds 100 cubic yards of earth, and/or exceeds twelve inches of grade change, then a grading permit is required in accordance with Subtitle 32-127.
(m)
If any of the above activities in this Section alter drainage patterns, then a permit is required.
(n)
If any of the above activities involve the clearing of trees and/or woodland, the permittee shall receive approval or an exemption from The Maryland-National Capital Park and Planning Commission pertaining to tree conservation.
(2)
Mechanical Permits:
(a)
Portable heating appliance.
(b)
Portable ventilation equipment.
(c)
Portable cooling unit.
(d)
Modification of steam, hot or chilled water piping within any heating or cooling equipment regulated by this code that does not alter its approval (Listing) or make it unsafe.
(e)
Replacement of any part that does not alter its approval (Listing) or make it unsafe.
(f)
Portable evaporative cooler.
(g)
Self-contained refrigeration system containing 10 pounds (4.54 kg) or less of refrigerant and actuated by motors of 1 horsepower (0.75 kW) or less.
(h)
One-to-one in-kind replacement of plug-in appliances.
(i)
Replacement of gas appliances shall require a permit from Washington Suburban Sanitary Commission.
(3)
Electrical:
(a)
Repairs and maintenance: Minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles.
(4)
Repairs/Replacement Permits:
(a)
Ordinary repairs and replacements, other than those that include cutting away of any wall, partition or portion thereof, the removal or cutting of any structural beam or load-bearing support, or the removal or change of any required means of egress, or rearrangement of parts of a structure affecting the egress requirements; or include additions to, alteration of, replacement or relocation of water supply, sewer, drainage, drain leader, gas, soil, waste, vent or similar piping, electric wiring or mechanical or other work affecting public health or general safety.
(b)
Ordinary repairs shall include replacement-in-kind of the following:
(1)
Siding, roofing, gutters, leaders and downspouts, private sidewalks, driveways, patios, awnings and canopies (repair only), equipment, cabinets, slabs, handrails, window screens, or storm doors.
(2)
Not more than 80 square feet (7.4 sq. meters) of gypsum board (dry wall) excluding installation of fire-rated gypsum wall board or shaft liner.
(c)
Repair of non-fire rated interior/exterior doors and windows with no structural modification.
(d)
Computation of the cost of repairs for purposes of this Section shall exclude carpeting replacement, electrical panel capacity upgrades, painting, wallpapering, re-grading and landscaping, lighting fixture replacements, appliance replacements, bathroom cabinetry and fixture replacements, and modifications necessary to comply with the Americans with Disabilities Act ("ADA") requirements. Each street address shall be considered a separate dwelling for application of this Section. All repairs for which a building permit is required that are conducted within a 365-day period shall be deemed a single cumulative repair cost for purposes of the application of this Section.
(b)
A new Section R105.2.1, Historic Area Work Permit Requirement. Notwithstanding the provisions of Section R105.2, a Historic Area Work Permit must be issued by the Historic Preservation Commission prior to any work on the exterior features of a property that contains a historic site or unclassified historic resource identified on the master plan for historic preservation or that is located within a local historic district. At the time the Historic Area Work Permit is issued, the Historic Preservation Commission shall notify the Director, or the Director's designee by transmitting a copy of the Historic Area Work Permit to the Director. The Director, or the Director's designee shall maintain and enroll the Historic Area Work Permit into the registry of issued permits maintained by the Director. The Director shall not require the issuance of a County building permit for ordinary repairs as defined in Section R105.2, or for ordinary maintenance as defined in Section 29-107(d), in addition to any Historic Area Work Permit that is determined by the Historic Preservation Commission to be required.
(c)
A new Section R105.2.2, Inventory of Historic Sites, Properties within Local Historic Districts, and Unclassified Historic Resources. The Director, or the Director's designee shall maintain an electronic inventory of historic sites, properties within local historic districts, and unclassified historic resources in Prince George's County. The Historic Preservation Commission shall transmit the listing of historic sites, properties within local historic districts, and unclassified historic resources to the Director or the Director's designee on or about January 1 and July 1 of each year. The listing shall be utilized to notify the Director or his Designee and applicants for County building permits issued by the Director or his Designee that the Historic Area Work Permit requirement described in Sec. R105.2.1 applies to any property that contains a historic site or unclassified historic resource or is located within a local historic district. The Director and/or his Designee shall not issue any permits for a property that contains a historic site or unclassified historic resource or is located within a local historic district, unless the Historic Preservation Commission has first issued a Historic Area Work Permit as required under Sec. R105.2.1.
(d)
A new Section R105.3.1.1, Required Documents for Permits Application. The application shall include: (1) any and all documents showing the business partners of the owner or lessee involved in the operation and or ownership of the building structure or use for which the permit is being sought; (2) any and all organizational documentation of the entity that owns, uses or leases the building or structure; (3) any and all documents showing who will operate the business; and (4) any other data and information supported by documentation that is required by the Director or the Director's designee deemed necessary for furtherance of the intent of this Code.
(e)
A new Section R105.3.1.2, Review of Application. The application will be reviewed to ensure that it conforms with all the requirements of the pertinent laws, including but not limited to the requirements of this Code, State and local laws and ordinances. An application for a permit will be reviewed by the Director or the Director's designee, in consultation with the Police Department and the Fire/EMS Department. The Director or the Director's designee shall have the authority to deny any application under the provisions of this Division and shall also have the authority to deny an application upon a violation of this Division.
(f)
A new Section R105.3.1.3, Application Exemption. The Director or the Director's designee may refuse to accept an application for a permit from any applicant: (1) who is or was in default on a previously issued permit, or who is the permittee listed on an expired permit which is not currently in the process of being extended by County administrative action, or who has not fully complied with the application process; (2) for any other reason the Director or the Director's designee deems necessary in furtherance of the intent of this Code; or (3) for any reason that is necessary to maintain the health, safety and welfare of the public.
(g)
A new Section R105.3.1.4, By Whom an Application is Made. Application for a permit shall be made by the owner or lessee of the building or structure, or the agent of either, or by the licensed engineer or architect employed in connection with the proposed work. If the application is made by a person other than the owner in fee, the applicant shall attest on the permit application or by separate written statement, that the proposed work is authorized by the owner in fee and that the applicant is authorized to make such application. The full names and addresses of the owner, lessee, applicant, and the responsible officer if the owner or lessee is a corporate body, shall be stated on the application. Subsequent permits will be issued in the name of the owner of record at time of permit issuance.
(h)
Section R105.3.2, Time Limitation of an Application. An application for a permit for any proposed work shall be deemed to have been abandoned twelve (12) months after the date of filing, unless such application has been diligently pursued in good faith or a permit has been issued. Extensions of time may be authorized by the Director or the Director's designee. The Director or the Director's designee may request any documentation or certification deemed necessary and assess an extension fee as appropriate.
(i)
Section R105.5, Expiration. Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within one hundred eighty (180) days after the issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of one hundred eighty (180) days after the time the work is commenced. The Director or the Director's designee is authorized to grant, in writing, one or more extensions of time, for periods not more than one hundred eighty (180) days each. The extension shall be requested in writing and justifiable cause shall be demonstrated. Any permit issued for property within the area of a pending Sectional Map Amendment (as provided for in the County Zoning Ordinance) that is rezoned to a less intense zone, shall expire on its own terms upon approval of the Sectional Map Amendment by the District Council if a completed building foundation for a use not permitted in the less intense zone has not been completed. The Director or the Director's designee shall notify the permit holder of the expiration of the permit.
(j)
A new Section R105.5.1, Expiration of Permit and Correction of Code Violations. Any permit issued for residential property to correct a building code or housing code violation issued pursuant to Subtitle 4 or Subtitle 13 of the County Code shall be issued only for a period of time reasonably necessary to correct the violation, not to exceed ninety (90) days. The initial period of the permit shall be established by the Director or the Director's designee based upon the extent of the work required to correct the violation. The permit may be extended or renewed for an additional period of one hundred eighty (180) days if, in the opinion of the Director or the Director's designee, the applicant has demonstrated substantial progress to complete the work in accordance with the permit and has demonstrated substantial justification for failure to complete the work within the period of the permit. The Board of Administrative Appeals shall have no authority to grant an extension to the period of the permit.
(k)
A new Section R105.10, Building Location. No permit for building shall be issued for a structure that overlaps the County line. Location of the County line on the site plan shall be certified by a Professional Land Surveyor.
(l)
A new Section R105.1.1, Date and Hours of Operation Limits. All permits shall be issued with date and hours of operation limits listed as determined by the Director or the Director's designee. All permits shall be issued indicating that no work shall be performed during the hours of 9:00 p.m. to 7:00 a.m., unless work is performed pursuant to Section 4-120 of this Subtitle.
(m)
A new Section R105.1.2, After Hours Permit. Any request to work pursuant to a permit beyond permitted construction hours shall be made by application to the Code Official and shall be subject to noise regulations of Prince George's County Code and in accordance with the fee schedule established in Sec. 2-253.63. No after-hours permit shall be issued for work in an area zoned "residential" under the Zoning Regulations then in effect, or in an area within 500 feet (152 400 mm) of such residential zone, or within 500 feet (152 400 mm) of a building with sleeping quarters, unless the Code Official determines that not issuing such permit would pose a threat to public safety, health and welfare.
(n)
A new R105.1.3 Post Construction Permit. Any owner cited for unpermitted construction shall be required to obtain a "Post Construction Permit" to complete and certify that the unpermitted construction is in compliance with the Code or to remove the unpermitted work. The Post Construction Permit fee must be paid in addition to any other fees required to obtain permits. Post construction plans submitted for approval must be certified by a Maryland Registered Professional Engineer (PE) or a Maryland Licensed Architect.
Prince George's County, Md., Code § 4-244.01 (2026)
Sec. 4-244.01. Scope and Administration: Section R105, PermitsLinkCopy Citation
(a)
A new Section R105.6, Suspension or Revocation and Reissuance of Permits. The Director or the Director's designee is authorized to suspend or revoke a permit issued under the provisions of this Code as follows: (1) whenever the permit is issued in error, (2) incorrectly, (3) inaccurately, (4) in an incomplete manner, (5) for any reason that is necessary to maintain the health, safety and welfare of the public, (6) in violation of any ordinance, regulation or any of the provisions of this Code, and (7) the Director or the Director's designee, in consultation with the Police Department and the Fire/EMS Department, shall have the authority to deny, suspend, or revoke any application or permit under the provisions of this Division and upon a violation of this Division. In addition, the failure to have utility lines located on site through the Utility Service Protection Center ("Miss Utility") and any nonmember utilities prior to starting any excavation deeper than twelve (12) inches will result in permit revocation.
(1)
A permit under which no work has commenced and an inspection has not been performed within one hundred eighty (180) days after issuance shall expire and become null and void; provided, however, that the Director or the Director's designee may extend the time herein not to exceed an additional one hundred eighty (180) days upon sufficient justification shown.
(2)
A permit under which work has been started and later suspended or discontinued shall expire and become null and void six (6) months after the work has stopped. Work will be considered suspended or discontinued when the builder fails to prosecute the work so as to ensure completion within a reasonable period of time considering the type of construction involved. The Director or the Director's designee may extend the time herein not to exceed an additional twelve (12) months upon sufficient justification shown.
(3)
A permit issued in error or not in compliance with County Code at time of issuance may be suspended by the Director or the Director's designee.
(4)
When a permit has expired for failure to commence work, it may be renewed within a period of thirty (30) days from the date of expiration if the conditions under which the permit was originally issued have remained unchanged and there has been no change in law or ordinance that would adversely affect the permit. A fee shall be collected for each renewal; however, no permit may be renewed more than two (2) times.
(5)
Whenever the Director or the Director's designee determines by inspection that work started on any building or structure for which a permit has been issued has been suspended for a period of six (6) months, the owner of the property upon which the structure is located, or other person or agent in control of said property, shall, within thirty (30) days from the receipt of written notice from the Department, obtain a new or renewal permit to complete the required work and diligently pursue the work to completion, or shall remove work not completed or demolish the incomplete structures or buildings within sixty (60) days from the date of the printed notice.
(6)
Permits suspended for failure to comply with the County Code or ordinances may be reinstated by the Director or the Director's designee upon compliance or approved validation.
(7)
A permit issued for property within the area of a pending Sectional Map Amendment, as provided for in Subtitle 27 of this Code, that is rezoned to a less intense zone, shall expire if a completed building foundation for a use not permitted in the less intense zone has not been constructed pursuant to a validly issued permit prior to District Council approval of the Sectional Map Amendment. The determination of the Director or the Director's designee made in accordance with Subsection R105.5.1 of this Subtitle shall not be appealable to the Board of Appeals.
(8)
The Director or the Director's designee may reissue a permit subject to all applicable laws or regulations in effect at the time the permit was originally issued, for a period not to exceed one (1) year after expiration provided that:
(A)
The County Executive, by Executive Order, has made a finding of severe economic factors adversely affecting real estate development and construction in the County during a specified period and the County Council has been notified by the County Executive of such finding at least seven (7) days prior to issuance of the Executive Order;
(B)
There is a reasonable showing that these economic factors contributed to the expiration of the permit;
(C)
There has been no change in the zoning of the property which would affect the issuance of the permit; and
(D)
A processing fee has been paid in an amount equal to the amount that would be required if the permit was renewed.
(b)
A new Subsection R105.6.1, Revocation of Permits. In addition, the failure to locate utility lines on site, prior to starting any excavation deeper than twelve (12) inches, by not contacting in due time the Utility Service Protection Center, "Miss Utility," and nonmember utilities, as known, and having such utilities locate lines on site, shall be cause - irrespective of whether or not a utility line is ruptured - for revocation of the permit. In order to continue work for which a permit has been revoked, a new application shall be required as specified in Section R105, Permits of IRC.
(c)
Section R105.7 - Posting of permit. The permit, or a copy thereof, shall be kept on the work site and conspicuously displayed at a location visible from the street until the completion of work for which the permit is issued.
Prince George's County, Md., Code § 4-244.02 (2026)
Sec. 4-244.02. Scope and Administration: Section R106.1, Submittal DocumentsLinkCopy Citation
(a)
Section R106.1.1.2, Location of Underground Utility Lines Prior to Commencement of Work. For all work that requires excavation deeper than twelve (12) inches, the permit holder (permittee) accepting the permit agrees to contact the Utility Service Protection Center, "Miss Utility," and nonmember utility companies, as known, in due time and prior to beginning any excavation work for the purpose of having each utility company locate its lines on site. In the event that the permittee fails to obtain the services of the utilities, then in such event, and irrespective of whether or not a utility line is ruptured, the Director or the Director's designee may revoke the building or grading permit, or both. In such event, all fees paid to the County shall be forfeited and, in order to continue work, a new application with requisite fee for a permit shall be filed. Drawings shall be reexamined to determine that all utilities have been located and verified by the utility companies having knowledge of the location of such underground utilities. However, in the event any or all of the respective utility companies fail to furnish the requisite information to the permittee within a reasonable period of time as determined by the Director or the Director's designee under all of the circumstances, then, in such event, the foregoing revocation provisions shall not apply.
(b)
Section R106.1.1.3. Acknowledgement of Final Grade. Builders and developers shall place on record with each utility company a written acknowledgment that final grade has been achieved to within six (6) inches. Utility lines shall not be installed until such acknowledgment has been received by the utilities.
(c)
A new Section R106.3.3.1, Approval of Partial Plans. The code official is authorized to issue a partial permit for the construction of foundations or any other part of a building or structure before the entire plans and specifications for the whole building or structure have been submitted, provided adequate information and detailed statements have been filed complying with all pertinent requirements of the County Building Code. Issuance of a partial permit by the code official does not constitute assurance that a permit for the entire structure will be granted. The holder of such partial permit for the foundations or other part of a building or structure will proceed with the building operation at the holder's own risk and without assurance that a permit for the entire structure will be granted.
(d)
Transitory Provisions
(1)
Applicable Codes. The laws and regulations in force on the date that a new edition of the Construction Codes are adopted pursuant to the sections below.
(2)
Existing Valid Permit. Work authorized by a permit issued before the effective date of the new edition of the Construction Codes shall be allowed to be carried to completion, subject to the conditions of Sections R105.5 and R105.6.
(3)
Existing Filed Application. Applications for permits for which the application filing deposit has been paid before the effective date of the new edition of the Construction Codes shall be allowed to be processed to issuance of the permit, and any work authorized thereby shall be allowed to be carried to completion, under the edition of the Construction Codes in effect on the date said applications were filed, subject to the following conditions:
(a)
Each such application shall have been filed accompanied by plans and other information conforming to Section R106, sufficiently complete to allow processing of the permit without substantial change or deviation;
(b)
Each such permit shall be paid in full and taken out by the applicant within one year after the effective date of the new edition of the Construction Codes;
(c)
All work authorized by such permit shall be carried to completion under the terms of the permit; and
(d)
Permits granted under Section Transitory Provisions shall not be extended if permitted to expire, pursuant to Section R105.5, or if revoked pursuant to Sections R105.6 and R105.6.1.
(4)
Existing Design Contracts. Buildings and other structures under contract for design on the effective date of the new edition of the Construction Codes, for which no permit applications have been filed, shall be allowed to be filed, processed to issuance of permit, and any work authorized thereby shall be allowed to be carried to completion, under the previous edition of the Construction Codes, subject to the following conditions:
(a)
The applicant shall file the permit application, accompanied by plans and other information conforming to Sections R106 of the new edition of the Construction Codes, sufficiently complete to allow processing of the permit without substantial change or deviation, within one year after the effective date of the new edition of the Construction Codes;
(b)
The applicant shall submit a copy of the design contract, with a notarized affidavit stating that the submitted copy is a true and accurate copy of the contract for the design of the building or other structure, that the contract was in effect on or before the effective date of the Construction Codes, and that the design submitted with the permit application was made under such contract;
(c)
The permit shall be obtained, and the permit fee paid in full by the applicant within one year after the filing date;
(d)
All work authorized by such permit shall be carried to completion under the terms of the permit; and
(5)
Violations or Infractions. The laws and regulations in force on the date that a new edition of the Construction Codes is adopted and shall apply with respect to violations or infractions committed prior to said date, whether the prosecutions or adjudications of those violations of infractions are begun before or after said date.
Prince George's County, Md., Code § 4-245 (2026)
Sec. 4-245. Building Planning; Section R-313, Automatic Fire Sprinkler SystemLinkCopy Citation
(a)
R-313.1 Section, Automatic Sprinkler System Requirement for New One- and Two-Family Dwellings and Industrialized Buildings (Modular and Manufactured Homes to be utilized as a new One- and Two-Family Dwelling). This Section, R-313.1, supersedes Section R-313 of the IRC. An automatic sprinkler system shall be provided throughout new one- and two-family dwellings, including industrialized (modular) and manufactured homes, installed as manufactured homes after December 31, 2010. The following reductions in construction requirements are permitted when a one- or two-family dwelling is fully sprinklered:
(1)
A basement exit to grade is not required;
(2)
A second exit from the dwelling is not required;
(3)
Trusses are not required to be provided with a fire-resistive ceiling membrane; and
(4)
Fire separations may be reduced from two (2) hours to one (1) hour rating and may be constructed with combustible framing. The one (1) hour rated fire separation wall need not be able to withstand collapse of construction on either side under fire conditions.
(b)
Section R-313.2, Connection from Sprinkler Systems. Sprinklers systems designed in accordance with NFPA 13D shall be supplied and protected from backflow in accordance with the WSSC Plumbing and Fuel Gas Code. Repairs to detached one- and two-family dwellings and townhomes not more than three stories above grade plane which, because of lack of maintenance or structural damage due to fire, explosion, or natural causes, which, in the opinion of the Director of the Director's designee, exceed fifty percent (50%) of the building shall have an approved automatic fire sprinkler system installed throughout the building as part of the scope of repairs completed. Additions to existing structures which exceed one hundred percent (100%) of the total floor (square footage) of the existing structures will cause the altered structure (addition plus existing structure) to be fully sprinklered.
(c)
Section R-313.4, Sprinklers for Additions. All enclosed or habitable additions to an existing sprinklered one- or two-family dwelling, including industrialized (modular and manufactured) homes must also be fully sprinklered.
(d)
Section R-313.5, Location and Performance of Fire Hydrants. Every building of more than one thousand (1,000) square feet in an area shall be provided with sufficient fire hydrants located such that no exterior portion of the building is located more than five hundred (500) feet from a fire hydrant. The distance shall be measured as a hose line would be laid along paved streets, through parking lot entrances, and around obstructions, in accordance with the determination of the authority having jurisdiction. For multiple single-family dwellings (townhouses), provide a fire hydrant within five hundred (500) feet of all exterior portions of the building, as hose is laid. Each hydrant shall provide a minimum of one thousand (1,000) gpm at a residual pressure of twenty (20) psi.
Exception: An approved alternate water supply source may be acceptable in areas not served by a public water supply. In addition, a fire hydrant is not required to be situated within two hundred (200) feet of any required fire department connection that is intended to supply an automatic fire sprinkler system that has been retrofitted into an existing building of any use group, provided that the area of the building has not been increased in size or the use group classification has not been changed to require an automatic fire suppression system under any other provision of this Division.
(e)
Section R-313.6, Booster Pump for Automatic Sprinklers. Where a booster pump is required for the water supply to the automatic sprinklers, the pump driver shall follow the requirements of this Section.
(f)
Section R-313.6.1, Water Pressure and Volume Boost with Standard Drip Proof Pump Drive. Water pressure and volume boost with standard drip proof pump drive shall be installed as follows:
(1)
Circuit breaker switch must be within the visual line-of-sight of the pump. A sub-panel may be provided within the line-of-sight of the pump, if the main panel is in a remote location to the pump.
(2)
Passive electrical supervision to the pump will be accomplished through the following wiring diagram of either the main or subpanel. See figure R-328.6.1.
(g)
Section R-313.6.2, Water Pressure and Volume Boost with Totally Enclosed, Fan Cooled Pump Driver. Water pressure and volume boost with totally enclosed fan cooled pump driver shall be installed as follows:
(1)
Circuit breaker switch must be within the visual line-of-sight of the pump. A sub-panel may be provided within the line-of-sight of the pump, if the main panel is in a remote location to the pump.
(2)
Passive electrical supervision to the pump will be accomplished through the following wiring diagram of either the main or subpanel. See figure R-313.6.1.
(h)
Section R-313.6.3, Any Pump with a Stored Water Supply. Any pump with a stored water supply shall be installed as follows:
(1)
Circuit breaker switch must be within the visual line-of-sight of the pump. A sub-panel may be provided within the line-of-sight of the pump, if the main panel is in a remote location to the pump.
(2)
Passive electrical supervision to the pump will be accomplished through the following wiring diagram of either the main or subpanel. See Figure R-313.6.1
Figure R-328.6.1
(i)
Section R-313.6.4, Combination Use Standard Wiring Method. Any pump on a single circuit shall be installed to be within visual sight of the pump.
(j)
Section R-313.6.5, Mounting Considerations for Any Pump Serving a Residential Sprinkler System. Any pump serving a residential sprinkler system shall be installed as follows:
(1)
Wall or floor mounted;
(2)
Accessible for inspection or service;
(3)
Ensure not located in hazardous area;
(4)
Install as per manufacturer's requirements.
Prince George's County, Md., Code § 4-246 (2026)
Sec. 4-246. Building Planning; Section R-302, Fire Resistant ConstructionLinkCopy Citation
(a)
Section R-302.2.5 is amended to read as follows: "Parapets." Parapets constructed in accordance with Section R-302.2.4 shall be provided for townhouses as an extension of common exterior or walls in accordance with the following:
(1)
Where roof surfaces adjacent to the wall or walls are at the same elevation, the parapet shall extend not less than thirty (30) inches above the roof surfaces; and
(2)
Where roof structures adjacent to the wall or walls are at different elevations and the higher roof is not more than thirty (30) inches above the lower roof, the parapet shall extend not less than Thirty (30) inches above the lower roof surface.
Exception: A parapet is not required in Subsections (1) and (2) of this Section when townhouses are provided with residential sprinkler systems installed in accordance with Section 903 of the IBC, or when the roof is covered with a minimum Class C roof covering and the roof decking or sheathing is of noncombustible materials or approved fire-retardant treated wood for a distance of four (4) feet on each side of the wall or walls, or one layer of five-eighths (5/8) inch, or Type X gypsum board is installed directly beneath the roof decking or sheathing for a distance of four (4) feet on each side of the wall or walls.
(3)
A parapet is not required where roof surfaces adjacent to the wall or walls are at different elevations and the higher roof is more than thirty (30) inches above the lower roof. The common wall construction from the lower roof to the underside of the higher roof deck shall not have less than a one (1) hour fire-resistive rating. The wall shall be rated for exposure from both sides.
(b)
Section R305.1: The Exceptions are amended to include Exception 5: The Director or designee shall approve, in writing, any ceiling height above finished floor.
Prince George's County, Md., Code § 4-246.01 (2026)
Sec. 4-246.01. ReservedLinkCopy Citation
Prince George's County, Md., Code § 4-247 (2026)
Sec. 4-247. Swimming Pools, Spas and Hot Tubs: Section R-327, Barrier RequirementsLinkCopy Citation
Section R-327.1, Outdoor Swimming Pool. An outdoor swimming pool, including an in-ground, above-ground or on-ground pool, hot tub or spa shall be surrounded by a barrier which shall comply with the following: The top of the barrier shall be at least six (6) feet above grade measured on the side of the barrier which faces away from the swimming pool.
Prince George's County, Md., Code § 4-248 (2026)
Sec. 4-248. ReservedLinkCopy Citation
Prince George's County, Md., Code § 4-249 (2026)
Sec. 4-249. Foundations; Section R-403, FootingsLinkCopy Citation
(a)
The following amendments, additions, and/or deletions are to Section R-403 of the IRC:
(1)
At a minimum, every other vertical reinforcement shall have a footing dowel or use engineer design per IRC code. The lap length at the top of the footing shall be adequate to develop the full tension capacity of the reinforcement.
(2)
Footing design shall be based on minimum soil load bearing capacity of 1,500 psf. See IRC Table 403.1(1) to 403.1(3). Footings in accordance with the engineering design are acceptable if a geotechnical report including the soil load bearing capacity is provided for each lot.
(3)
Section R-403.1.4, Minimum Depth. All exterior footings and foundation systems shall extend below the frost line. The bottom of all exterior footings shall be placed at thirty (30) inches below the finished grade.
(a)
Exception: An exception to Section R-403.1.4 can be granted by the Director or designee for accessible access.
(4)
Section R-403.1.6, "the maximum spacing of one-half (½) inch diameter anchor bolts is amended to be four (4) feet."
(5)
Section R-403.2, titled "Footings for wood foundations" is deleted.
Prince George's County, Md., Code § 4-250 (2026)
Sec. 4-250. Foundations; Section R-404, Foundations and Retaining WallsLinkCopy Citation
(a)
The following amendments, additions, and/or deletions are made to Section R-404 of the International Residential Code:
(1)
Section R-404.1.1, Design Loads. In addition to other applicable loads, the basement walls shall be designed for the at-rest pressure (lateral soil load) as described in Table 1610.1 of the 2021 International Building Code.
(2)
Section R-404.1.2, Design of Concrete Masonry. Design of concrete masonry unit (CMU) walls shall conform to the Building Code Requirements for Masonry Structures (ACI 530/TMS 402) Chapters 1, 2 and 3. Minimum horizontal joint reinforcement consisting of not less than two continuous wires each with a minimum cross-sectional area of 0.017 square inch (9 gage) shall be provided in horizontal bed joints spaced not more than every second course vertically. For basement walls subjected to lateral earth pressure, minimum vertical reinforcement shall consist of one No. 5 rebar (ASTM A615 grade 60) spaced not more than sixteen (16) inches (for nominal 8", 10" or 12" walls). Cells having vertical reinforcement shall be filled with concrete or masonry grout meeting the requirement of ASTM C476. Vertical steel reinforcement shall be placed not more than 2 inches from the inside face of the walls.
(3)
Section R-404.1.3, Design of Concrete Walls. Design of concrete walls subjected to lateral earth pressure shall conform to the Building Code Requirements for Reinforced Concrete (ACI 318) Chapter 10. Minimum reinforcement in each direction shall not be less than that required by Chapter 7 (i.e. for ASTM A615 grade 60, No. 4@14" for 8-inch thick, No. 4@12" for 10-inch thick, and No. 4@10" for 12-inch-thick wall). For design of concrete walls subjected to lightly loaded lateral earth pressure (4 feet or less of unbalanced backfill) or concrete walls with insignificant stress components (for example, stresses reduced by mean of wall stiffeners) the ACI 318 Chapter 22 may be used to determine the amount of reinforcement required. Engineered wall design is acceptable for wing walls per ACI-318 code.
(b)
For walls that are proposed to serve as floods walls, the permittee shall secure approval from the US Army Corps of Engineers prior to submittal to Prince George's County for building permit. The applicant shall submit evidence of approval.
(c)
The following requirements shall be met for retaining wall permits, not including cantilevered retaining walls for basements, which are covered by the 2021 IBC, Chapter 18.
(1)
The Height of a retaining wall is measured from lowest ground elevation on the lower or bottom side of wall to the highest elevation on the top of the retaining wall structure, at any given cross section of the wall.
(2)
Soil investigation is required at a minimum rate of one soil test boring per 100 linear ft of the retaining wall length.
(3)
Timber retaining walls are not allowed.
(4)
In general, on residential developments, the height of retaining walls shall be minimized preferably to less than 6 feet, for ease of maintenance. This also applies to the cumulative height of tiered retaining walls.
(5)
Retaining walls shall be located on common homeowner or business park association parcels, to the maximum extent practical. Retaining walls shall not be located in the public storm drain or storm water management easements. Retaining walls shall not be located in the County public road right of way, except for abutment walls for bridges.
(6)
For Segmental Retaining walls (SRW) including Mechanically Stabilized Earth Walls (MSEW) higher than 2 feet, and other proprietary products, the applicant shall include in the permit submittal the manufacturer's information and specifications, and a valid evaluation report from a DPIE approved listing agency. The permittee shall submit an acceptance letter for the geotechnical aspects only of the wall design from the Geotechnical Engineer of Record (GER) if the GER is not the wall designer.
(7)
Declaration of Easements for Retaining Walls
(i)
Retaining walls and tiered walls with a cumulative height of 6 feet or greater are required to have a permanent easement in front of and behind the wall. The easement dimension shall not be less than 10 feet wide on the low side of the wall.
(ii)
On the high side of the wall, the easement shall contain the select backfill zone, including soil reinforcement including geogrids, tiebacks, anchors, and footings.
(iii)
The easement dimension on the high side of the wall shall not be less than 10 feet wide.
(iv)
Grading and retaining wall permit plans shall reflect the limits of the retaining wall easements and the horizontal extent of soil reinforcement, footing, and select backfill zone.
(v)
The following site elements shall not be located inside retaining wall easements:
(aa)
Buried utilities (except as noted in (9)(aa) and (9)(bb) below
(bb)
Building additions
(cc)
Porches
(dd)
Structures
(ee)
Pools
(ff)
Decks
(gg)
Stormwater management devices and storm drain pipe
(hh)
Trees
(vi)
The following site elements are permissible inside retaining wall easements:
(aa)
Storm drain outfall pipe located perpendicular to the wall, if there is no alternative but to penetrate through the wall. The storm drain shall have a drop manhole on the high side of the wall, and the storm drain pipe under the footing of the retaining wall shall be encased in an outer pipe sleeve that is at least 12 inches larger in size than the conveying storm drain pipe.
(bb)
Storm drain inlets and pipes necessary to capture the swale immediately above the wall. These storm drain systems must be designed shallow enough to be built above the soil reinforcement (not deeper than 2 feet).
(cc)
Sheds
(dd)
Fences - fence posts shall be located a minimum of 3 feet from the face of wall.
(ee)
Patios
(ff)
Pergolas
(gg)
Benches
(hh)
Sidewalks
(ii)
Trails
(jj)
Signage
(kk)
Landscaping (not including trees)
(ll)
Private roads and parking lots — guardrails and traffic barriers shall be provided and located between the wall and the roadway, a minimum of 3 feet from the face of the wall.
(vii)
Above features in (9)(cc, dd, ee, ff, gg, hh, ii, kk and ll) are only allowable within retaining wall easements if the Declaration of Easement language obligates the owner/maintainer of these features to remove and replace these elements, as may be required for wall maintenance or reconstruction.
(viii)
The retaining wall Declaration of Easement shall specify maintenance responsibility.
(ix)
The Declaration of Easement shall restrict future construction of unacceptable elements.
(x)
Retaining walls that span across multiple residential lots shall be maintained by the Homeowner's Association.
(8)
Retaining wall plans shall show wall drainage systems and select backfill behind the wall, filter fabric between the select backfill and adjacent soils, structural elements, and reinforcement type and size.
(9)
Retaining walls shall be designed to meet the minimum safety factor of 1.5 against sliding and overturning.
(10)
Retaining wall plans shall show in site plan view, wall profile view, and wall sections the extent of select backfill, soil reinforcement, filter fabric, and other pertinent information. The design professionals (structural, civil, geotechnical) shall fully coordinate select backfill and soil reinforcement with all site features.
(11)
Retaining walls shall be located with the toe of the wall a minimum of 25 feet from creeks, streams, and swales, as these locations have the potential for eroding and undermining retaining wall structures. The design engineer shall submit a scour analysis for streams and swales in close proximity to retaining walls. If the scour analysis requires, the retaining wall permit documents shall be designed with a foundation system capable of withstanding the scour, for example deep foundation system and/or armoring of the stream, as required.
(12)
Segmental retaining walls (SRWs), including the leveling pads, shall not be placed below the 100-year floodplain elevation, due to concerns with scour and migration of soil backfill.
(13)
For retaining wall permits, a global stability analysis shall be signed and sealed by a licensed geotechnical engineer and must be provided for the following conditions:
(aa)
Walls with cumulative height taller than 10 ft;
(bb)
Walls with cumulative height taller than 6 ft and with back slope steeper than 3 horizontal to 1 vertical;
(cc)
Walls on or adjacent to unstable soils, such as over-consolidated clay; or
(dd)
When deemed necessary by DPIE or the Geotechnical Engineer of record (GER).
(ee)
The retaining wall calculations shall achieve a 1.5 minimum factor of safety for global stability.
(ff)
The global stability analysis is also required for a series of tiered retaining walls, for which the cumulative height of all walls exceeds the heights described in (17) above.
(14)
Retaining walls shall be drained by a system that includes:
(aa)
Perforated drainage pipes at the toe of the wall. Toe drainage pipes shall be connected to a solid storm drain or discharge to grade;
(bb)
An upright drainage layer behind the wall façade that ties into the toe drainage behind the wall bottom. This drainage layer can consist of gravel or a prefabricated geo-composite if recommended by the design engineer;
(cc)
Filter fabric between the gravel and soil; and
(dd)
Perforated two (2)-inch minimum diameter PVC weep holes, through the wall, for the entire length of the wall, and at a maximum spacing of 20 feet.
(15)
Within the select backfill zone, the upper soil layer shall consist of 4 inches of topsoil and 12 inches of impervious clay soil or an impermeable geo-membrane below the topsoil. The purpose of this is to limit surface water infiltration into the select backfill zone of the retaining wall.
(16)
To prevent surface storm water from flowing over the top wall of wall, a swale is required immediately behind the wall. The swale may be located at least 12 inches behind the high side of the wall, with a depth of at least 6 inches. The swale shall have 4 inches of topsoil at the surface and 12" of impervious lean clay soil or an impermeable geo-membrane below the topsoil. If the length of land adjacent to and perpendicular to the wall is negligible, for example less than 5 feet wide, such that surface sheet flow down the slope and towards the wall is minimal, then the swale above the wall is not required. All concentrated flows shall be intercepted into a storm drain system and conveyed thru the wall.
(17)
If the groundwater elevation is 2 feet or less below the retaining wall leveling pad or is expected to rise seasonally to the bottom of the leveling pad or higher, a blanket drain is required below the retaining wall, near the bottom of the leveling pad.
(18)
If an identified water source such as groundwater or springs are located on the high side of a retaining wall, a drainage blanket and chimney drains at least 6" thick are required. The drainage blanket shall extend laterally from the wall to the chimney drain at a rising slope of 3%. The chimney drain shall rise to the elevation of the groundwater source, and shall have a heel drain pipe with a minimum four (4) inch diameter at its bottom. Blanket and chimney drains are also required if surface drainage runoff or subsurface water may otherwise flow to the wall, which frequently comes from unconfirmed or unidentified water sources. The blanket shall extend back from the wall to cover the entire select backfill and to reach the possible water source. The chimney height shall be seventy (70) percent of the wall height, with a heel drain pipe.
(19)
Soil reinforcement and/or other slope stabilization measures, such as caissons, piles, piers, deep dynamic compaction, or other means shall be shown to scale on the site grading plans in profile and plan views.
(20)
Retaining walls that retain multiple lots shall pass final inspection successfully before structures on all retained lots can receive final inspection.
Prince George's County, Md., Code § 4-250.01 (2026)
Sec. 4-250.01. Foundations; Section R-404.2, titled "Wood Foundation Walls."LinkCopy Citation
This Section is deleted in its entirety.
Prince George's County, Md., Code § 4-251 (2026)
Sec. 4-251. Foundations; Section R-405, Foundation DrainageLinkCopy Citation
(a)
The following amendments, additions, and/or deletions are made to Section R-405 of the International Residential Code:
(1)
Section R-405.1.2, Subsoil Drainage Systems. Subsoil drains shall be required for all buildings having basements, cellars, crawl spaces, or floors below grade. Subsoil drains shall be located inside and outside of the foundation and shall be installed at or below the area to be protected. Drains shall discharge by gravity or mechanical means into an approved drainage system.
(2)
Section R-405.2.3, Sump Pumps and Pits. Where subsoil drains do not discharge by gravity, the drains shall discharge to an accessible sump pit with an automatic electric pump. A battery back-up or water-powered back-up sump pump will also be provided. The sump pit shall be a minimum of twenty-four (24) inches in diameter or eighteen (18) inches square and twenty-four (24) inches in depth, and be provided with a fitted cover. The sump pump shall have adequate capacity to discharge all water coming into the sump as it accumulates but in no case shall the capacity of the pump be less than fifteen (15) gallons per minute. The discharge from the pump shall be a minimum of one and one-fourth (1¼) inches and shall have a union in the discharge piping to make the pump accessible for servicing. Subsoil drains and sump pump discharge may discharge to a properly graded open area provided the point of discharge is ten (10) feet from any property line or Building Restriction Line (BRL). Where a continuously flowing spring or high groundwater table is encountered during the design stage, basement floors shall be designed at least two and one-half (2.5) feet above the groundwater's highest detected level. Alternatively pre-approved methods of permanent dewatering shall be provided, and the groundwater level shall be verified again before construction. If such condition is encountered by the County and subsoil drains are pre-approved by the County; these drains must be piped to a storm drain or approved outfall where they shall be fitted. When piped to a storm drain all drainage lines shall include an accessible backwater valve. Residential sump pumps are not to be relied on for lowering high groundwater table.
(3)
Section R-405.1.4, Areaway Drains. All open subsurface space adjacent to a building serving as an exit or entrance shall be provided with a drain or drains. Such areaway drains shall be of approved material in accordance with Chapter 30 of this Code and not less than 2 inches in diameter and shall discharge by gravity or mechanical means in accordance with R-405.1.2. Areaway drains for areas exceeding 800 square feet shall be sized in accordance with Section 1113 of the 2021 International Plumbing Code.
(4)
Section R-405.1.5, Window Well Drains. Window well areaways shall have drains. Window well areaways 10 square feet or less may discharge to the subsoil drain through a 2-inch minimum diameter pipe. Drains for window well areaways greater than 10 square feet shall be installed in accordance with Section R-405.1.3.
(5)
Section R-405.1.6, Foundation Weep Holes. Where subsoil drains are required by Section R-405.1.1, foundations of hollow core masonry shall have foundation weep holes. Weep holes shall be placed a maximum of 4-foot o/c intervals and shall discharge into the aggregate of the interior subsoil drainage system.
(6)
Section R-405.1.7, Site Grading. The ground immediately adjacent to the foundation shall be sloped away from the building at a slope that conforms with the County Grading Code 32-151. Consideration shall be given to the possible additional settlement of the backfill when establishing the final ground level adjacent to the foundation.
(7)
Section R-405.2, titled "Wood foundations" is deleted in its entirety.
Prince George's County, Md., Code § 4-252 (2026)
Sec. 4-252. Floors; Section R-502, Wood Floor FramingLinkCopy Citation
(a)
The following addition is made to Section R-502 of the International Residential Code:
(1)
Section R-502.7. Floor joists adjacent and parallel to the exterior foundation wall shall be provided with full-depth solid blocking, not less than two (2) inches nominal in thickness, placed perpendicular to the joist at spacing not more than four (4) feet. The blocking shall be nailed to the floor sheathing, the joist and the exterior rim joist/board.
Prince George's County, Md., Code § 4-253 (2026)
Sec. 4-253. Engineered Floor Truss Systems; Section R-502.8.3, Protection of Structural MembersLinkCopy Citation
(a)
Section R-502.8.3, Protection of Truss Framing Members. All combustible truss framing members which comprise a portion of a nonrated floor assembly shall be protected by the installation of a ceiling. The ceiling material shall not be less than one-half (1/2) inch gypsum board or an approved equivalent alternative material. The ceiling must be adequately supported by direct mechanical fastening to the structural framing or be suspended by not less than No. 12 MSG galvanized steel wire or by an equivalent method. Where combustible truss joist framing is used as a portion of a required rated floor-ceiling assembly, the structural members shall be protected in accordance with an appropriate tested and listed design.
Exceptions:
(1)
Buildings protected throughout, excluding crawlspaces less than forty-two (42) inches in depth by an automatic sprinkler system; and
(2)
Crawl spaces of not more than forty-two (42) inches in depth, measured from the top of the floor surface above to the surface of the crawl space floor.
Prince George's County, Md., Code § 4-254 (2026)
Sec. 4-254. Wall Construction; Section R602.10 Wall BracingLinkCopy Citation
Section R602.10.9.2 Braced wall panel supported by floor joists, beams or girders (see section R602.10.8). When the interior braced wall panel, not supported by continuous braced wall or foundation wall below, is used in conjunction/combination with the exterior braced walls, the design of this braced wall system (interior and exterior) including the design of the supporting joists, beams and girders, column and foundation shall be in accordance with accepted engineering practice.
Prince George's County, Md., Code § 4-255 (2026)
Sec. 4-255. Administration and Enforcement; Sec R113. ViolationsLinkCopy Citation
(a)
Section R113.2 of the IRC is amended to read as follows:
"Notice of Violation"
R113.2.1 Issuance of Notice of Violation
The Building Official is authorized to serve a notice of violation or order on the person responsible for the erection, construction, alteration, extension, repair, moving, removal, demolition or occupancy of a building or structure in violation of the provisions of this code, or in violation of a detail statement or a plan approved thereunder, or in violation of a permit or certificate issued under the provisions of this code. Such order shall direct the discontinuance of the illegal action or condition and the abatement of the violation.
R113.2.2 Administrative Lien
Upon issuance of a notice of violation, the Building Official may place an administrative lien on the property that shall serve as notice to prospective purchasers, lessees, or other transferees. The Building Official may release the administrative lien upon abatement or correction of the underlying violation(s) giving rise to the notice of violation or upon verification that the prospective purchaser, lessee, or other transferee has been notified of the existence of the Stop Work Order.
(b)
Section R113.4 of the IRC is amended to read as follows: "Violation Penalties"
R113.4.1 Civil Penalties: Any person, firm, association, partnership, corporation, or combination thereof who shall violate a provision of the International Residential Code (IRC), or of this Subtitle, or fail to comply with any of the requirements thereof, violates a lawful order issued thereunder, or any person who shall erect, construct, alter, or repair a building or structure or mechanical or electrical system without all required permits or in violation of an approved plan or directive of the Building Official, or of a permit or certificate issued under the provisions of this Subtitle or the IRC, may be liable for a civil fine in accordance with the provisions of this section. A civil fine imposed under this subsection is in addition to any other sanction provided by law.
A civil fine may be assessed in conjunction with a written notice of violation or through the issuance of a civil citation or an administrative citation in accordance with the provisions of this Subtitle.
R113.4.1.1 Civil Fine Imposed Through Notice of Violation: When a civil fine is imposed through a notice of violation, the notice of violation shall state the amount of the civil fine and a description of the circumstances giving rise to the assessment. A civil fine imposed through a notice of violation shall be one thousand dollars ($1,000) per violation. Each day that a violation continues shall be deemed a separate offense. A civil fine assessed through a notice of violation shall be due and payable within 30 days after the Building Official issues the written notice.
R113.4.1.1.1 Appeal of Civil Fine Issued Through Notice of Violation: A written notice of violation assessing a civil fine under this section shall be a final decision of the Director or the Director's designee.
R113.4.1.1.2 Recording of Civil Fine as tax lien: If a civil fine imposed through a notice of violation has not been paid within 30 days after the written notice of violation, the Director may cause the written notice of violation to be recorded with the Director of Finance for Prince George's County. Recordation of the notice of violation shall constitute a lien on the subject property and shall be collected in the same manner as other County real estate taxes. The filing of an appeal of a civil fine shall not affect the recordation of a tax lien under this subsection. Upon receiving notice that a duly adjudicated appeal has resulted in a decision in favor of an appellant regarding a civil fine imposed under this subsection, the Director of Finance shall release the tax lien.
R113.4.1.2 Civil Fine Imposed Through Civil Citation
R113.4.1.2.1 In the event that a responsible party does not comply with a notice of violation within the time period provided, including any period allowed by appeal, and upon verification by the Director or the Director's designee that the violation still exists, the Director or the Director's designee may issue upon the responsible parties a civil citation pursuant to Subtitle 28, Division 3, of this Code.
R113.4.1.2.2 Separate Violation: Each day the violation continues is deemed a separate offense and is subject to an additional citation and fine in the same dollar amount as the repeat citation(s).
R113.4.1.2.3 Civil Citation in addition to other sanctions: A civil citation imposed under this subsection is in addition to any other sanction provided by law.
R113.4.1.3 Administrative Citation
R113.4.1.3.1 In lieu of issuing a civil citation pursuant to Section R113.4.1.2 above, upon verification of a violation of this Section, the Director or Director's designee may issue upon the responsible parties an administrative citation as that term is defined in Section 13-1121.
R113.4.1.3.2 In addition to any other matters that the Director prescribes, the issuance of an administrative citation shall comply in all respects with the requirements of Sec. 13-1125 of this Code.
R113.4.1.3.3 Administrative citations issued under this subtitle shall be adjudicated in accordance with the provisions outlined in Sections 13-1126, 13-1127, 13-1128, 13-1129, 13-1130, 13-1131, and 13-1132 of this Code.
R113.4.1.3.4 A civil fine imposed through an administrative citation under this section shall be five hundred dollars ($500.00) per violation and shall be due and payable within 30 days after the citation is issued. Each day that a violation continues shall be deemed a separate offense.
(c)
Section R.113.5 is added and shall read as follows:
113.5 Disclosure Requirements:
113.5.1 Disclosure to Prospective Transferee: When the owner of a dwelling unit or structure has received a notice of violation issued under this Subtitle, the owner shall provide a copy of the notice of violation to a prospective purchaser, lessee, or other transferee.
113.5.2 Recordation: The Director may record a notice of violation issued under this Subtitle among the land records in the Circuit Court for Prince George's County.
Prince George's County, Md., Code § 4-255.01 (2026)
Sec. 4-255.01. Administration and Enforcement; Sec R114. Stop Work OrderLinkCopy Citation
(a)
Section R114.1 of the IRC is amended to read as follows:
R114.1.1 Issuance of Stop Work Order
Upon notice from the Building Official that work on any building or structure is being executed contrary to the provisions of this code or in an unsafe and dangerous manner, such work shall be immediately stopped. The Stop Work Order shall be in writing and shall be given to the owner of the property involved, the owner's authorized agent or the person performing the work. Upon issuance of a Stop Work Order, the cited work shall immediately cease. The Stop Work Order shall state the reason for the order and the conditions under which the cited work will be permitted to resume. Stop Work Order will be in full force until all fees and penalties are paid and permits have been secured for all illegal and/or unpermitted construction.
R.114.1.2 Administrative Lien
Upon issuance of a Stop Work Order, the Building Official may place an administrative lien on the property that shall serve as notice to prospective purchasers, lessees, or other transferees. The Building Official shall release the administrative lien upon abatement or correction of the underlying violation(s) giving rise to the Stop Work Order or upon verification that the prospective purchaser, lessee, or other transferee has been notified of the existence of the Stop Work Order.
(b)
Section R114.2 of the IRC is amended to read as follows: Unlawful Continuance
R114.2.1 Civil Penalties: Any person, firm, association, partnership, or corporation, or combination thereof, who shall continue work in violation of the provisions of a Stop Work Order or shall remove or cause to be removed a Stop Work Order sign still in effect and operation, may be liable for a civil fine in accordance with the provisions of this section. A civil fine imposed under this subsection is in addition to any other sanction provided by law. A civil fine may be assessed in conjunction with a written notice of violation or through the issuance of a civil citation or an administrative citation in accordance with the provisions of this Subtitle.
R114.2.1.1 Civil Fine Imposed Through Notice of Violation: When a civil fine is imposed through a notice of violation, the notice of violation shall state the amount of the civil fine and a description of the circumstances giving rise to the assessment. A civil fine imposed through a notice of violation shall not exceed one thousand dollars ($1,000) per violation. Each day that a violation continues shall be deemed a separate offense. A civil fine assessed through a notice of violation shall be due and payable within 30 days after the Building Official issues the written notice.
R114.2.1.1.1 Appeal of Civil Fine Issued Through Notice of Violation: A written notice of violation assessing a civil fine under this section shall be a final decision of the Director or the Director's designee as is contemplated.
R114.2.1.1.2 Recording of Civil Fine as tax lien: If a civil fine imposed through a notice of violation has not been paid within 30 days after the written notice of violation, the Director may cause the written notice of violation to be recorded with the Director of Finance for Prince George's County. Recordation of the notice of violation shall constitute a lien on the subject property and shall be collected in the same manner as other County real estate taxes. The filing of an appeal of a civil fine shall not affect the recordation of a tax lien under this subsection. Upon receiving notice that a duly adjudicated appeal has resulted in a decision in favor of an appellant regarding a civil fine imposed under this subsection, the Director of Finance shall release the tax lien.
R114.2.1.2 Civil Fine Imposed Through Civil Citation
R114.2.1.2.1 In the event that a responsible party does not comply with a notice of violation within the time period provided, including any period allowed by appeal, and upon verification by the Director or the Director's designee that the violation still exists, the Director or the Director's designee may issue upon the responsible parties a civil citation pursuant to Subtitle 28, Division 3, of this Code.
R114.2.1.2.2 Separate Violation: Each day the violation continues is deemed a separate offense and is subject to an additional citation and fine in the same dollar amount as the repeat citation(s).
R114.2.1.2.3 Civil Citation in addition to other sanctions: A civil citation imposed under this subsection is in addition to any other sanction provided by law.
R114.2.1.3 Administrative Citation
R114.2.1.3.1 In lieu of issuing a civil citation pursuant to Section 114.2.1.2 above, upon verification of a violation of this Section, the Director or Director's designee may issue upon the responsible parties an administrative citation as that term is defined in Section 13-1121.
R114.2.1.3.2 In addition to any other matters that the Director prescribes, the issuance of an administrative citation shall comply in all respects with the requirements of Sec. 13-1125 of this Code.
R114.2.1.3.3 Administrative citations issued under this subtitle shall be adjudicated in accordance with the provisions outlined in Sections 13-1126, 13-1127, 13-1128, 13-1129, 13-1130, 13-1131, and 13-1132 of this Code.
R114.4.1.3.4 A civil fine imposed through an administrative citation under this section shall be five hundred dollars ($500.00) per violation and shall be due and payable within 30 days after the citation is issued. Each day that a violation continues shall be deemed a separate offense.
(c)
Section R.114.3 is added and shall read as follows:
114.3 Disclosure Requirements:
114.3.1 Disclosure to Prospective Purchaser or Lessee: When a stop work order has been issued under this Subtitle and remains effective at the time of a prospective transfer or lease, the owner shall provide notice of the stop work order to a prospective purchaser or lessee.
114.3.2 Recordation: The Director shall record evidence of a stop work order issued under this Subtitle among the land records in the Circuit Court for Prince George's County.
Prince George's County, Md., Code § 4-255.02 (2026)
Sec. 4-255.02. Roof Assemblies; Section R903 Weather ProtectionLinkCopy Citation
Section R903.4.2 is added to read as follows: "Gutters and Downspouts." Unless constructed with parapet walls and coping, all exterior walls shall be provided with gutters and downspouts or leaders to dispose of roof drainage to comply with the International Plumbing Code.