<?xml version='1.0' encoding='utf-8'?>
<section number="4-258" name="Electrical Power and Lighting Systems (Mandatory); C405.2.1 Occupant Sensor Controls" law="code" slug="sec-4-258" node_id="PTIITI17PULOLAPRGECOMA_SUBTITLE_4BU_DIV1BUCO_SD5INENCOCO_S4-258ELPOLISYMAC4OCSECO">
  <text>Section C405.2.1 Occupant sensor controls shall be installed in all classrooms, conference/meeting rooms, employee lunch and break rooms, private offices, restrooms, storage rooms, janitorial closets, enclosed stairways, and other spaces 300 square feet (28m2) or less enclosed by floor-to-ceiling height partitions. These automatically turn off lights within 30 minutes of all occupants leaving the space, and shall turn the lighting on to not more than 50 percent power.</text>
</section>