<section number="9-107.01" name="Wiring Methods and Materials; Article 310 — Conductors for General Wiring" law="code" slug="sec-9-107.01" node_id="PTIITI17PULOLAPRGECOMA_SUBTITLE_9EL_DIV1ELCO_SD2AMNAELCO_S9-107.01WIMEMAAR31COGEWI">
  <level label="a">
    <text>The following amendments, additions, and/or deletions are made to Article 310 of the National Electrical Code:</text>
    <level label="1">
      <text>The following paragraph is added to Section 310.10, "Uses Permitted:" (C) Aluminum or copper-clad aluminum conductors. Aluminum or copper-clad aluminum conductors shall be permitted only for service and feeder use and shall not be smaller than #2 AWG.</text>
    </level>
    <level label="2">
      <text>The following exception is added to Section 310.10, "Uses Permitted:" Listed Cable assemblies #2 aluminum or copper-clad aluminum conductors AWG and larger installed in single-family and multifamily dwellings, having grounding conductors sized in accordance with Section 250.122, "Size of Equipment Grounding Conductors," shall be excluded from the requirements set forth in (a)(l), above.</text>
    </level>
  </level>
</section>