Sec. 9-109.01. Special Conditions; Article 700 — Emergency Systems
Codified through Bill No. CB-018-2026, adopted May 12, 2026, effective July 24, 2026. Source: Municode, Supplement 2026 Update 2. Editorial notes and legislative history omitted.
Prince George's County, Md., Code § 9-109.01 (2026)
Sec. 9-109.01. Special Conditions; Article 700 — Emergency SystemsLinkCopy Citation
(a)
The following amendments, additions, and/or deletions are made to Article 700 of the National Electrical Code:
(1)
Section 700.5(A) is amended by the addition of the following sentence:
(A)
All Emergency Systems such as panelboards, motor control centers, load centers, disconnects, transformer and Transfer equipment shall be separated from normal power distribution system by a wall or wall(s) with a minimum fire rating of two (2) hour(s).