<section number="9-109.01" name="Special Conditions; Article 700 — Emergency Systems" law="code" slug="sec-9-109.01" node_id="PTIITI17PULOLAPRGECOMA_SUBTITLE_9EL_DIV1ELCO_SD2AMNAELCO_S9-109.01SPCOAR70EMSY">
  <level label="a">
    <text>The following amendments, additions, and/or deletions are made to Article 700 of the National Electrical Code:</text>
    <level label="1">
      <text>Section 700.5(A) is amended by the addition of the following sentence:</text>
      <level label="A">
        <text>All Emergency Systems such as panelboards, motor control centers, load centers, disconnects, transformer and Transfer equipment shall be separated from normal power distribution system by a wall or wall(s) with a minimum fire rating of two (2) hour(s).</text>
      </level>
    </level>
  </level>