  <level label="a">
    <text>Except as provided in subsections (g) and (h) of this section, the Department shall require that each assisted living program facility that provides services to 50 or more individuals have an emergency electrical power generator on the premises.</text>
  </level>
  <level label="b">
    <text>The Department shall require that each facility provide emergency electrical power as provided in this section.</text>
  </level>
  <level label="c">
    <level label="1">
      <text>The emergency power source shall be a generating set and prime mover located on the facility premises with automatic transfer.</text>
    </level>
    <level label="2">
      <text>An emergency power system shall meet the following requirements:</text>
      <level label="i">
        <text>In the event of failure of the normal electric service, the emergency electrical power shall be activated immediately;</text>
      </level>
      <level label="ii">
        <text>The emergency generator set shall come to full speed and load acceptance within 10 seconds; and</text>
      </level>
      <level label="iii">
        <text>The emergency generator shall have the capability of 48 hours of operation from fuel stored on–site.</text>
      </level>
    </level>
    <level label="3">
      <level label="i">
        <text>The emergency power system shall be tested one time each month.</text>
      </level>
      <level label="ii">
        <text>The emergency power system test shall require that the generator be exercised for a minimum of 30 minutes under normal emergency facility connected load.</text>
      </level>
      <level label="iii">
        <text>The test shall be recorded in a permanent log book maintained for that purpose.</text>
      </level>
    </level>
  </level>
  <level label="d">
    <text>The emergency power system shall provide lighting in the following areas of the facility:</text>
    <level label="1">
      <text>Areas of egress and protection as required by the State Fire Prevention Code and Life Safety Code 101 adopted by the State Fire Prevention Commission;</text>
    </level>
    <level label="2">
      <text>Nurses’ station;</text>
    </level>
    <level label="3">
      <text>Drug distribution station or unit dose station;</text>
    </level>
    <level label="4">
      <text>An area for emergency telephone use;</text>
    </level>
    <level label="5">
      <text>Boiler or mechanical room;</text>
    </level>
    <level label="6">
      <text>Kitchen;</text>
    </level>
    <level label="7">
      <text>Emergency generator location and switch gear location;</text>
    </level>
    <level label="8">
      <text>Elevator, if operable on emergency power;</text>
    </level>
    <level label="9">
      <text>Areas where life support equipment is used;</text>
    </level>
    <level label="10">
      <text>If applicable, common areas or areas of refuge; and</text>
    </level>
    <level label="11">
      <text>If applicable, toilet rooms of common areas or areas of refuge.</text>
    </level>
  </level>
  <level label="e">
    <text>Emergency electrical power shall be provided for the following:</text>
    <level label="1">
      <text>Nurses’ call system;</text>
    </level>
    <level label="2">
      <text>At least one telephone in order to make and receive calls;</text>
    </level>
    <level label="3">
      <text>Fire pump;</text>
    </level>
    <level label="4">
      <text>Sewerage pump and sump pump;</text>
    </level>
    <level label="5">
      <text>If required for evacuation purposes, an elevator;</text>
    </level>
    <level label="6">
      <text>If necessary, heating equipment needed to maintain a minimum temperature of 70 degrees Fahrenheit (24 degrees Celsius) in all common areas or areas of refuge;</text>
    </level>
    <level label="7">
      <text>Life support equipment; and</text>
    </level>
    <level label="8">
      <text>Nonflammable medical gas systems.</text>
    </level>
  </level>
  <level label="f">
    <level label="1">
      <text>If the emergency power system does not provide heat to all patient rooms or toilet rooms in the event of a loss of electricity from the main source of power, the facility shall provide common areas or areas of refuge for all patients.</text>
    </level>
    <level label="2">
      <text>The Department shall adopt regulations regarding the requirements for designating parts of the facility as common areas or areas of refuge.</text>
    </level>
  </level>
  <level label="g">
    <text>An assisted living program facility shall be exempt from the requirements of this section if the facility can safely transfer residents through an enclosed corridor to a building that is equipped with an electrical power generator that satisfies the requirements of this section.</text>
  </level>
  <level label="h">
    <level label="1">
      <text>The Department may grant a facility a waiver from the requirements of this section if the facility:</text>
      <level label="i">
        <text>Provides evidence to the Department that the requirements of this section will create an undue financial burden on the facility and will require the facility to cease operation; and</text>
      </level>
      <level label="ii">
        <text>Discloses to the residents of the facility that the facility does not have an emergency electrical power generator that meets the requirements of this section.</text>
      </level>
    </level>
    <level label="2">
      <text>Subject to paragraph (3) of this subsection, a waiver granted under paragraph (1) of this subsection may not exceed a period of 3 years.</text>
    </level>
    <level label="3">
      <text>The Department may extend a waiver granted under paragraph (1) of this subsection for an additional period of 2 years beyond the period specified in paragraph (2) of this subsection.</text>
    </level>
  </level>