  <section article="gps" article_name="Public Safety" number="9-101" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>In this subtitle the following words have the meanings indicated.</text>
    </level>
    <level label="b">
      <text>“Long–life battery” means a nonrechargeable, nonreplaceable primary battery that is capable of operating a smoke alarm for at least 10 years in the normal condition.</text>
    </level>
    <level label="c">
      <text>“Sleeping area” means a space that includes one or more sleeping rooms and a hall or common area immediately adjacent to any sleeping room.</text>
    </level>
    <level label="d">
      <text>“Sleeping room” means an enclosed room with a bed arranged to be used as a bedroom.</text>
    </level>
    <level label="e">
      <text>“Smoke alarm” means a single or multiple station device that detects visible or invisible products of combustion and includes a built–in internal alarm signal.</text>
    </level>
    <level label="f">
      <text>“Smoke detector” means a system–connected smoke sensing device tied to a fire alarm control panel or a household fire warning panel.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-102" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <level label="1">
        <text>In this section, “high–rise building” means a building where the floor of an occupiable story is greater than 75 feet above the lowest level of fire department vehicle access.</text>
      </level>
      <level label="2">
        <text>“High–rise building” does not include:</text>
        <level label="i">
          <text>a structure or building used exclusively for open–air parking; or</text>
        </level>
        <level label="ii">
          <text>a building used exclusively for agricultural purposes.</text>
        </level>
      </level>
    </level>
    <level label="b">
      <text>This subtitle applies throughout the State, including Baltimore City.</text>
    </level>
    <level label="c">
      <level label="1">
        <text>An automatic smoke alarm shall be provided in each sleeping area within each residential occupancy, including one– and two–family dwellings, lodging or rooming houses, hotels, dormitories, and apartment buildings, as defined in NFPA 101: Life Safety Code as adopted by the State Fire Prevention Commission.</text>
      </level>
      <level label="2">
        <level label="i">
          <text>Beginning July 31, 2025, smoke detectors shall be installed in accordance with location and spacing requirements established by the National Fire Protection Association in each interior public corridor in a residential rental high–rise building.</text>
        </level>
        <level label="ii">
          <text>A county may not require upgrades to fire safety systems not specified in subparagraph (i) of this paragraph as a condition of issuing a permit for the installation of smoke detectors required under subparagraph (i) of this paragraph.</text>
        </level>
      </level>
      <level label="3">
        <level label="i">
          <text>In this paragraph, “substantial renovation” means permanent alterations that:</text>
          <level label="1">
            <text>are intended to enhance the value of a building;</text>
          </level>
          <level label="2">
            <text>cost an amount equal to or greater than 40% of the value of the building as assessed by the State Department of Assessments and Taxation; and</text>
          </level>
          <level label="3">
            <text>meet the criteria for substantial renovation under any applicable local law.</text>
          </level>
        </level>
        <level label="ii">
          <text>Beginning October 1, 2026, automatic fire sprinklers shall be installed in accordance with NFPA Life Safety Code and NFPA standards in each residential rental high–rise building that is undergoing a substantial renovation that receives building permits on or after October 1, 2026.</text>
        </level>
        <level label="iii">
          <text>In determining whether a proposed substantial renovation is intended to enhance the value of a building exclusive of land value, a county may consider building improvements completed over a 4–year time period from the date of the initial building permit.</text>
        </level>
        <level label="iv">
          <text>A substantially renovated residential rental high–rise building shall also have the following fire protection and life safety features:</text>
          <level label="1">
            <text>smoke alarms in every sleeping area;</text>
          </level>
          <level label="2">
            <text>stairwells enclosed with at least 2–hour fire resistance rated construction with at least 90–minute fire resistance rated, self–closing, and self–latching doors;</text>
          </level>
          <level label="3">
            <text>at least 20–minute fire resistance rated corridor doors with appropriately rated corridor walls;</text>
          </level>
          <level label="4">
            <text>smokeproof exit enclosures via natural ventilation, mechanical ventilation incorporating a vestibule, or pressurizing the stair enclosure;</text>
          </level>
          <level label="5">
            <text>at least two smoke compartments on each floor; and</text>
          </level>
          <level label="6">
            <text>inadequate fire pumps replaced when necessary.</text>
          </level>
        </level>
      </level>
    </level>
    <level label="d">
      <text>Smoke alarms shall:</text>
      <level label="1">
        <text>be installed in accordance with NFPA 72: National Fire Alarm and Signaling Code as referenced by the State Fire Prevention Code;</text>
      </level>
      <level label="2">
        <text>be listed and labeled by a nationally recognized testing laboratory to comply with Underwriters Laboratories (UL) 217, “Standard for safety for single and multiple station smoke alarms”;</text>
      </level>
      <level label="3">
        <text>be suitable for sensing visible or invisible products of combustion; and</text>
      </level>
      <level label="4">
        <text>sound an alarm suitable to warn the occupants.</text>
      </level>
    </level>
    <level label="e">
      <text>Local jurisdictions may adopt smoke alarm regulations that are more stringent than the provisions of this subtitle.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-103" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>This section applies only to new residential units constructed on or after July 1, 2013.</text>
    </level>
    <level label="b">
      <text>At least one smoke alarm shall be installed in each sleeping room, in the hallway or common area outside of sleeping rooms, and in the hallway or common area on each level within a residential dwelling unit, including basements and excluding unoccupied attics, garages, and crawl spaces.</text>
    </level>
    <level label="c">
      <text>If two or more smoke alarms are required within a residential unit, the smoke alarms shall be arranged so that activation of any one smoke alarm causes alarm activation of all other required smoke alarms within the residential unit.</text>
    </level>
    <level label="d">
      <text>Each smoke alarm required by this section shall operate on an alternating current (AC) primary source of electric power with a battery backup or an approved alternate secondary power source.</text>
    </level>
    <level label="e">
      <text>In one– and two–family dwellings, a smoke detector installed as a part of an approved household fire alarm system is an acceptable alternative to the AC powered–battery backup smoke alarm required by this section, if the smoke detector is installed and located as specified in subsection (b) of this section.</text>
    </level>
    <level label="f">
      <text>A smoke detector installed as a part of an approved fire alarm system is an acceptable alternative to the AC powered–battery backup smoke alarm required by this section, if the smoke detector is installed and located as specified in subsection (b) of this section.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-104" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <level label="1">
        <text>At least one smoke alarm shall be provided in each residential sleeping area.</text>
      </level>
      <level label="2">
        <text>Smoke alarms required in one– and two–family dwellings constructed before July 1, 1975, shall be battery powered or alternating current (AC) primary electric powered units.</text>
      </level>
      <level label="3">
        <text>Smoke alarms required in one– and two–family dwellings constructed between July 1, 1975, and June 30, 1990, shall be alternating current (AC) primary electric powered units.</text>
      </level>
      <level label="4">
        <text>Smoke alarms required in multifamily residential occupancies including apartments, lodging or rooming houses, dormitories, and hotels shall be alternating current (AC) primary electric powered units.</text>
      </level>
      <level label="5">
        <text>Smoke alarms required in a residential occupancy constructed on or after July 1, 1990, shall be alternating current (AC) primary electric powered units with battery backup or an approved alternate secondary power source.</text>
      </level>
    </level>
    <level label="b">
      <text>At least one smoke alarm shall be installed in each level of a residential occupancy constructed on or after January 1, 1989, including basements and excluding unoccupied attics, garages, and crawl spaces.</text>
    </level>
    <level label="c">
      <text>If two or more smoke alarms are required within a residential unit constructed on or after January 1, 1989, the smoke alarms shall be arranged so that activation of any one smoke alarm causes alarm activation of all other required smoke alarms within the residential unit.</text>
    </level>
    <level label="d">
      <level label="1">
        <text>Subject to paragraph (2) of this subsection, smoke alarm placement in a one– or two–family dwelling shall be upgraded to comply with paragraph (3) of this subsection in existing residential occupancies when any one of the following occurs:</text>
        <level label="i">
          <text>the existing smoke alarms exceed 10 years from the date of manufacture;</text>
        </level>
        <level label="ii">
          <text>the existing smoke alarms fail to respond to operability tests or otherwise malfunction;</text>
        </level>
        <level label="iii">
          <text>there is a change of tenant in a residential unit and the residential unit has not previously been equipped in accordance with this subtitle with sealed long–life battery smoke alarms with silence/hush button features within the 10 years preceding the change of tenant; or</text>
        </level>
        <level label="iv">
          <text>a building permit is issued for an additional residential unit or alteration to a residential unit.</text>
        </level>
      </level>
      <level label="2">
        <text>Smoke alarm placement shall be upgraded to comply with paragraph (3) of this subsection in all existing residential occupancies on or before January 1, 2018.</text>
      </level>
      <level label="3">
        <text>Upgraded smoke alarm placement shall include the following:</text>
        <level label="i">
          <text>a minimum of one smoke alarm on each level of the residential unit, including basements and excluding unoccupied attics, garages, and crawl spaces;</text>
        </level>
        <level label="ii">
          <text>smoke alarms shall be alternating current (AC) primary powered units with battery backup, except as follows:</text>
          <level label="1">
            <text>smoke alarms in one– and two–family dwellings constructed before July 1, 1975, may be battery operated; and</text>
          </level>
          <level label="2">
            <text>smoke alarms required in new locations by this section, if smoke alarms did not previously exist, may be battery operated; and</text>
          </level>
        </level>
        <level label="iii">
          <text>if battery operated smoke alarms are permitted, only sealed, tamper resistant units incorporating a silence/hush button and using long–life batteries may be used.</text>
        </level>
      </level>
    </level>
    <level label="e">
      <text>In one– and two–family dwellings, a smoke detector installed as a part of an approved household fire alarm system is an acceptable alternative to the AC powered–battery backup smoke alarms required by this section, if the smoke detectors are installed and located as specified in subsection (a) of this section.</text>
    </level>
    <level label="f">
      <text>A smoke detector installed as a part of an approved fire alarm system is an acceptable alternative to the AC powered–battery backup smoke alarms required by this section, if the smoke detectors are installed and located as specified in subsection (a) of this section.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-105" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>Each sleeping room occupied by a deaf, deafblind, or hard of hearing individual shall be provided with a smoke alarm suitable to alert the deaf, deafblind, or hard of hearing individual.</text>
    </level>
    <level label="b">
      <level label="1">
        <text>On written request on behalf of a tenant who is deaf, deafblind, or hard of hearing, a sleeping room occupied by a deaf, deafblind, or hard of hearing individual shall be provided with an approved notification appliance designed to alert deaf, deafblind, or hard of hearing individuals.</text>
      </level>
      <level label="2">
        <text>The landlord shall provide a notification appliance that, when activated, provides a signal that is sufficient to warn the deaf, deafblind, or hard of hearing tenant in those sleeping rooms.</text>
      </level>
      <level label="3">
        <text>The landlord may not require that a tenant:</text>
        <level label="i">
          <text>pay for the purchase or installation of a notification appliance; or</text>
        </level>
        <level label="ii">
          <text>provide any supporting documentation or other form of evidence with a written request for a notification appliance.</text>
        </level>
      </level>
    </level>
    <level label="c">
      <text>Hotels and motels shall have available at least one approved notification appliance for the deaf, deafblind, or hard of hearing individual for each 50 units or fraction of 50 units.</text>
    </level>
    <level label="d">
      <text>Hotels and motels shall post in a conspicuous place at the registration desk a permanent sign that states the availability of smoke alarm notification appliances for the deaf, deafblind, or hard of hearing individual.</text>
    </level>
    <level label="e">
      <level label="1">
        <text>Hotels and motels may require a refundable deposit for notification appliances for the deaf, deafblind, or hard of hearing individual.</text>
      </level>
      <level label="2">
        <text>The amount of the deposit may not exceed the value of the notification appliance.</text>
      </level>
    </level>
    <level label="f">
      <text>A landlord may not require reimbursement from a tenant for the cost of a smoke alarm required under this section.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-106" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>Smoke alarm requirements shall be enforced by the State Fire Marshal, a county or municipal fire marshal, a fire chief, the Baltimore City Fire Department, or any other designated authority having jurisdiction.</text>
    </level>
    <level label="b">
      <level label="1">
        <text>The building permit applicant is responsible for the proper installation of required smoke alarms in residential occupancies constructed on or after July 1, 2013.</text>
      </level>
      <level label="2">
        <text>If a building permit is not required, the general contractor shall bear the responsibility described in paragraph (1) of this subsection.</text>
      </level>
    </level>
    <level label="c">
      <text>The landlord or property owner is responsible for the installation, repair, maintenance, and replacement of smoke alarms required by this subtitle.</text>
    </level>
    <level label="d">
      <text>Occupants of a residential occupancy may not remove or tamper with a required smoke alarm or otherwise render the smoke alarm inoperative.</text>
    </level>
    <level label="e">
      <level label="1">
        <text>Testing of smoke alarms is the responsibility of the occupant of the residential unit.</text>
      </level>
      <level label="2">
        <level label="i">
          <text>A tenant shall notify the landlord in writing of the failure or malfunction of a required smoke alarm.</text>
        </level>
        <level label="ii">
          <text>The written notification required under subparagraph (i) of this paragraph shall be delivered by certified mail, return receipt requested to the landlord, or by hand delivery to the landlord or the landlord’s agent, at the address used for the payment of rent.</text>
        </level>
        <level label="iii">
          <text>If the delivery of the notification is made by hand as described in subparagraph (ii) of this paragraph, the landlord or the landlord’s agent shall provide to the tenant a written receipt for the delivery.</text>
        </level>
        <level label="iv">
          <text>The landlord shall provide written acknowledgment of the notification and shall repair or replace the smoke alarm within 5 calendar days after the notification.</text>
        </level>
      </level>
    </level>
    <level label="f">
      <level label="1">
        <text>If a residential unit does not contain alternating current (AC) primary electric power, battery operated smoke alarms or smoke alarm operation on an approved alternate source of power may be permitted.</text>
      </level>
      <level label="2">
        <text>Battery operated smoke alarms shall be sealed, tamper resistant units incorporating a silence/hush button and using long–life batteries.</text>
      </level>
    </level>
    <level label="g">
      <text>A smoke alarm may be combined with a carbon monoxide alarm if the device complies with:</text>
      <level label="1">
        <text>this subtitle;</text>
      </level>
      <level label="2">
        <text>Title 12 of this article; and</text>
      </level>
      <level label="3">
        <text>Underwriters Laboratories (UL) Standards 217 and 2034.</text>
      </level>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-106.1" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>This section does not apply to:</text>
      <level label="1">
        <text>a fire alarm, a smoke detector, a smoke alarm, or an ancillary component that is:</text>
        <level label="i">
          <text>electronically connected as a part of a listed centrally monitored or supervised alarm system; or</text>
        </level>
        <level label="ii">
          <text>capable of sending and receiving notifications by:</text>
          <level label="1">
            <text>a low–power radio frequency wireless communication signal; or</text>
          </level>
          <level label="2">
            <text>a wireless local area networking capability; or</text>
          </level>
        </level>
      </level>
      <level label="2">
        <text>any other device that the State Fire Marshal designates as exempt through the regulatory process.</text>
      </level>
    </level>
    <level label="b">
      <text>On or after October 1, 2018, a person may not sell a battery operated smoke alarm in the State for compliance with this subtitle unless the smoke alarm is a sealed, tamper resistant unit incorporating a silence/hush button and using one or more long–life batteries.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-107" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <text>Failure to comply with this subtitle may not be used as a policy defense in the settlement of a property insurance claim.</text>
  </section>
  <section article="gps" article_name="Public Safety" number="9-108" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>If the State Fire Marshal or other designated authority with jurisdiction finds the absence of operating, required smoke detectors, the State Fire Marshal or other authority shall issue a smoke alarm installation order to the responsible landlord, owner, or occupant.</text>
    </level>
    <level label="b">
      <text>The responsible person shall comply with a smoke alarm installation order within 5 calendar days.</text>
    </level>
  </section>
  <section article="gps" article_name="Public Safety" number="9-109" title_number="9" title_name="Fire Protection and Prevention" subtitle_number="1" subtitle_name="Smoke Detection Systems">
    <level label="a">
      <text>A person may not knowingly violate this subtitle.</text>
    </level>
    <level label="b">
      <level label="1">
        <text>Except as provided in paragraph (2) of this subsection, a person who violates this section is guilty of a misdemeanor and on conviction is subject to imprisonment not exceeding 10 days or a fine not exceeding $1,000 or both.</text>
      </level>
      <level label="2">
        <text>A person who violates § 9–106.1 of this subtitle is subject to a fine not exceeding $1,000.</text>
      </level>
    </level>
  </section>