Regulation .01-1 Incorporation by Reference.
Regulation .01-1 Incorporation by Reference.LinkCopy Citation
A.
The following documents are incorporated by reference to the extent that they are referenced in this chapter:
(1)
ASME 2019 Boiler and Pressure Vessel Code, an International Code; and
(2)
National Board Inspection Code — NBIC, 2019 Edition.
B.
The following documents are incorporated by reference in their entirety:
(1)
ASME B31.1 — 2018 Edition, Power Piping (American Society of Mechanical Engineers);
(2)
ASME B31.3 — 2018 Edition, Process Piping (American Society of Mechanical Engineers);
(3)
ASME CSD-1 — 2018 Edition, Controls and Safety Devices for Automatically Fired Boilers (American Society of Mechanical Engineers) as amended in §C of this regulation; and
(4)
NFPA 85, Boiler and Combustion Systems Hazards Code — 2019 Edition (National Fire Protection Association).
C.
Controls and Safety Devices for Automatically Fired Boilers (CSD-1) (American Society of Mechanical Engineers).
(1)
The requirements of ASME CSD-1 in effect at the time a boiler is installed apply to:
(a)
Power boilers regardless of fuel input;
(b)
Other boilers with a fuel input of greater than 2,500,000 Btu per hour and less than 12,500,000 Btu per hour; and
(c)
Other boilers with a fuel input of 2,500,000 Btu per hour or less, except that Section CF of CSD-1 does not apply to these boilers.
(2)
The following are exempt from the requirements of ASME CSD-1:
(a)
Water heaters stamped either “H” or “HLW” and used as potable water heaters, if the water temperature is less than 210°F and the water pressure is less than 160 PSIG;
(b)
Miniature boilers, except as required in Regulation .37 of this chapter;
(c)
Kitchen equipment boilers, except as required in Regulation .38 of this chapter; and
(d)
Historical boilers.