<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".01-1" citation="COMAR 09.12.01.01-1" title_num="09" subtitle_num="12" chapter_num="01" heading="Incorporation by Reference.">
  <paragraph num="A.">
    <text>The following documents are incorporated by reference to the extent that they are referenced in this chapter:</text>
    <paragraph num="(1)">
      <text>ASME 2019 Boiler and Pressure Vessel Code, an International Code; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>National Board Inspection Code — NBIC, 2019 Edition.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>The following documents are incorporated by reference in their entirety:</text>
    <paragraph num="(1)">
      <text>ASME B31.1 — 2018 Edition, Power Piping (American Society of Mechanical Engineers);</text>
    </paragraph>
    <paragraph num="(2)">
      <text>ASME B31.3 — 2018 Edition, Process Piping (American Society of Mechanical Engineers);</text>
    </paragraph>
    <paragraph num="(3)">
      <text>ASME CSD-1 — 2018 Edition, Controls and Safety Devices for Automatically Fired Boilers (American Society of Mechanical Engineers) as amended in §C of this regulation; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>NFPA 85, Boiler and Combustion Systems Hazards Code — 2019 Edition (National Fire Protection Association).</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Controls and Safety Devices for Automatically Fired Boilers (CSD-1) (American Society of Mechanical Engineers).</text>
    <paragraph num="(1)">
      <text>The requirements of ASME CSD-1 in effect at the time a boiler is installed apply to:</text>
      <paragraph num="(a)">
        <text>Power boilers regardless of fuel input;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Other boilers with a fuel input of greater than 2,500,000 Btu per hour and less than 12,500,000 Btu per hour; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Other boilers with a fuel input of 2,500,000 Btu per hour or less, except that Section CF of CSD-1 does not apply to these boilers.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>The following are exempt from the requirements of ASME CSD-1:</text>
      <paragraph num="(a)">
        <text>Water heaters stamped either “H” or “HLW” and used as potable water heaters, if the water temperature is less than 210°F and the water pressure is less than 160 PSIG;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Miniature boilers, except as required in Regulation .37 of this chapter;</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Kitchen equipment boilers, except as required in Regulation .38 of this chapter; and</text>
      </paragraph>
      <paragraph num="(d)">
        <text>Historical boilers.</text>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>