<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".02" citation="COMAR 09.12.01.02" title_num="09" subtitle_num="12" chapter_num="01" heading="Access and Egress.">
  <paragraph num="A.">
    <text>Clearance.</text>
    <paragraph num="(1)">
      <text>Except for a water heater or a modular boiler system, a new or replacement boiler installed in a new or existing building shall be installed consistent with:</text>
      <paragraph num="(a)">
        <text>Or exceeding, the manufacturer's recommendations for clearance; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The space requirements of §A(6) of this regulation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>In the event manufacturer recommendations for clearance are not provided, a new or replacement boiler installed in a new or existing building, shall:</text>
      <paragraph num="(a)">
        <text>Have at least 3 feet between:</text>
        <paragraph num="(i)">
          <text>The top of the boiler and the ceiling, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Each side of the boiler and the adjacent wall or other structure; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Comply with the conditions of §A(6) of this regulation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>The distance between or around a new or replacement boiler in a modular boiler system installed in a new or existing building shall be in accordance with the manufacturer's recommendations while ensuring:</text>
      <paragraph num="(a)">
        <text>There are 3 feet between each side of the perimeter of the boiler system and the adjacent wall or structure; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The conditions in §A(6) of this regulation are met.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>The distance between or around a water heater installed in a new or existing building shall be in accordance with the manufacturer's recommendations while ensuring the conditions of §A(6) of this regulation are met.</text>
    </paragraph>
    <paragraph num="(5)">
      <text>A boiler or pressure vessel having a manhole shall have 5 feet clearance from the manhole opening to any wall, ceiling, or piping that prevents entrance through the manhole.</text>
    </paragraph>
    <paragraph num="(6)">
      <text>A boiler or pressure vessel shall be located to provide adequate space for:</text>
      <paragraph num="(a)">
        <text>Proper operation of the boiler or pressure vessel and its appurtenances;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Inspection of all surfaces, tubes, water-walls, economizers, piping, valves, and other equipment; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Required maintenance and the repair and replacement of tubes.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Ladders and Runways.</text>
    <paragraph num="(1)">
      <text>When necessary to afford safe access, a steel runway or platform of standard construction shall be installed across the tops of adjacent boilers or pressure vessels, or at another convenient level.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>When a valve or appurtenance requiring frequent manipulation cannot be reached or operated from the floor, a platform or other safe means of operation shall be provided.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>A platform or runway shall:</text>
      <paragraph num="(a)">
        <text>Be at least 24 inches wide;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Have standard handrails and toe boards; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Provide at least 7 feet, 6 inches overhead clearance.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>A runway shall:</text>
      <paragraph num="(a)">
        <text>Have at least two means of exit, located remotely from each other; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Be connected to floor level by:</text>
        <paragraph num="(i)">
          <text>A permanent stairway, or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>An inclined ladder.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Each elevation in a boiler room shall have at least two exits, located remotely from each other, if the room:</text>
    <paragraph num="(1)">
      <text>Exceeds 500 square feet floor area; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Contains one or more boilers having a fuel-burning capacity of 1,000,000 Btu per hour, or equivalent electrical heat input.</text>
    </paragraph>
  </paragraph>
</regulation>