Plain Text Law

Regulation .07 Gas-Fired Installations.

Regulation .07 Gas-Fired Installations.Copy Citation

A.
A burner in a gas-fired installation shall be tested and certified by the American Gas Association.
B.
A gas-fired boiler shall have a vent or flue that terminates at an acceptable location outside the building.
C.
The size of the vent or flue shall be:
(1)
That recommended by the boiler manufacturer;
(2)
At least 4 inches in diameter or equivalent area; and
(3)
If the horizontal run exceeds 10 feet, at least 6 inches in diameter or equivalent area.