<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".11" citation="COMAR 09.12.01.11" title_num="09" subtitle_num="12" chapter_num="01" heading="Heating Boiler — Existing Installation: Safety Valve.">
  <paragraph num="A.">
    <text>A steam boiler shall have at least one safety valve which is:</text>
    <paragraph num="(1)">
      <text>Officially rated;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Of the spring pop type; and</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Adjusted and sealed to discharge at a pressure not greater than 15 PSI.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>A seal shall be attached in a manner to prevent the valve from being disassembled without breaking the seal.</text>
  </paragraph>
  <paragraph num="C.">
    <text>A safety valve shall be arranged so that it cannot be reset to relieve at a pressure higher than the maximum allowable working pressure of the boiler.</text>
  </paragraph>
  <paragraph num="D.">
    <text>Body Drain.</text>
    <paragraph num="(1)">
      <text>The manufacturer shall provide a body drain connection below seat level.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>A body drain may not be plugged during or after field installation.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>If a valve exceeds 2 inch pipe size, the drain hole shall be tapped at least 3/8 inch pipe size.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>A valve less than 2 inches pipe size shall have a drain hole at least 1/4 inch in diameter.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Valve Size.</text>
    <paragraph num="(1)">
      <text>A safety valve for a steam boiler shall be:</text>
      <paragraph num="(a)">
        <text>At least 3/4 inches, unless the boiler and radiating surfaces are a self-contained unit; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Not larger than 4 1/2 inches.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>An inlet opening shall have an inside diameter at least equal to the seat diameter.</text>
    </paragraph>
  </paragraph>
  <paragraph num="F.">
    <text>The minimum relief capacity of a valve or valves is governed by the capacity marking on the boiler.</text>
  </paragraph>
  <paragraph num="G.">
    <text>Valve Capacity.</text>
    <paragraph num="(1)">
      <text>Subject to the requirements of §H, below, the minimum valve capacity in pounds per hour is the greater of the capacity determined:</text>
      <paragraph num="(a)">
        <text>By dividing the maximum BTU output at the boiler nozzle, obtained by firing any fuel for which the unit is installed, by 1,000; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>In accordance with the following table:</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>The minimum safety valve or safety relief valve relief capacity for an electric boiler shall be 3-1/2 pounds per hour per kilowatt input.</text>
    </paragraph>
  </paragraph>
  <paragraph num="H.">
    <text>The safety valve capacity for a steam boiler shall be sufficient to ensure that when fuel burning equipment is operated at maximum capacity, the pressure cannot exceed the maximum allowable working pressure by more than 5 PSI.</text>
  </paragraph>
  <paragraph num="I.">
    <text>When operating conditions change, or additional boiler heating surface is installed:</text>
    <paragraph num="(1)">
      <text>Valve capacity shall be increased, if necessary, to:</text>
      <paragraph num="(a)">
        <text>Meet the new conditions, and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Comply with the requirements of this regulation;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Provided there is no intervening valve, any additional valves required because of changed conditions may be installed on the outlet piping.</text>
    </paragraph>
  </paragraph>
  <paragraph num="J.">
    <text>If there is any doubt as to the capacity of a safety valve, an accumulation test shall be conducted in accordance with the ASME Code, Section VI, Recommended Rules for the Care and Operation of Heating Boilers.</text>
  </paragraph>
  <paragraph num="K.">
    <text>A valve of any type may not be placed:</text>
    <paragraph num="(1)">
      <text>Between a safety valve and a boiler; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>On a discharge pipe between a safety valve and the atmosphere.</text>
    </paragraph>
  </paragraph>
  <paragraph num="L.">
    <text>Discharge Pipe.</text>
    <paragraph num="(1)">
      <text>A discharge pipe shall be:</text>
      <paragraph num="(a)">
        <text>At least full-size; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Fitted with an open drain to prevent water from lodging in the upper part of a safety valve or in the discharge pipe.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>If a safety valve discharge pipe has an elbow, the:</text>
      <paragraph num="(a)">
        <text>Elbow shall be located near the safety valve outlet; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Discharge pipe shall be securely anchored and supported.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="M.">
    <text>Safety valve discharges shall be located or piped so as not to endanger workers.</text>
  </paragraph>
</regulation>