<regulation prefix="Regulation" num=".13" citation="COMAR 09.12.01.13" title_num="09" subtitle_num="12" chapter_num="01" heading="Hot Water Boiler—Existing Installation: Safety Relief Valve.">
  <paragraph num="A.">
    <text>Number of Valves.</text>
    <paragraph num="(1)">
      <text>A hot water heating boiler shall have at least one safety relief valve which is:</text>
      <paragraph num="(a)">
        <text>Officially rated; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Set to relieve at or below the maximum allowable working pressure of the boiler.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>A hot water supply boiler shall have at least one safety relief valve which is:</text>
      <paragraph num="(a)">
        <text>Officially rated;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Automatically reseating; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Set to relieve at or below the maximum allowable working pressure of the boiler.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>A safety relief valve with an officially rated capacity shall have pop action when tested by steam.</text>
  </paragraph>
  <paragraph num="C.">
    <text>When more than one safety relief valve is used on a hot water heating or hot water supply boiler, each additional valve shall be:</text>
    <paragraph num="(1)">
      <text>Officially rated; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Set at a maximum of:</text>
      <paragraph num="(a)">
        <text>6 PSI above the maximum allowable working pressure of the boiler, for a boiler having a maximum allowable working pressure of 60 PSI or less, or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>10 percent above the maximum allowable working pressure, for a boiler having a maximum allowable working pressure exceeding 60 PSI.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>A safety relief valve shall be:</text>
    <paragraph num="(1)">
      <text>Spring loaded; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Arranged so that it cannot be reset at a pressure higher than the maximum permitted by this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>A material that can fail because of deterioration or vulcanization when subject to saturated steam temperature corresponding to capacity test pressure may not be used for any part.</text>
  </paragraph>
  <paragraph num="F.">
    <text>Size.</text>
    <paragraph num="(1)">
      <text>Except as otherwise provided by this regulation, the standard pipe size of a safety relief valve may not be:</text>
      <paragraph num="(a)">
        <text>Smaller than 3/4 inch; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Larger than 4-1/2 inches.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>A boiler having a heat input of 15,000 BTU per hour or less may have a rated safety relief valve of 1/2 inch standard pipe size.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>An inlet opening shall have an inside diameter approximately equal to, or greater than, the seat diameter.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>The minimum opening through any part of a valve shall be at least 1/2 inch in diameter or the equivalent area.</text>
    </paragraph>
  </paragraph>
  <paragraph num="G.">
    <text>Subject to the requirements of §I of this regulation, the minimum steam relief capacity of a pressure relief device on a boiler, in pounds per hour, shall be the greater of the capacity determined:</text>
    <paragraph num="(1)">
      <text>By dividing by 1,000 the maximum BTU output at the boiler nozzle, obtained by firing any fuel for which the unit is installed; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>In accordance with Table 09.12.01.11G.</text>
    </paragraph>
  </paragraph>
  <paragraph num="H.">
    <text>When operating conditions change or additional boiler heating surface is installed:</text>
    <paragraph num="(1)">
      <text>Valve capacity shall be increased, if necessary, to:</text>
      <paragraph num="(a)">
        <text>Meet the new conditions, and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Comply with this regulation; and</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>If there is no intervening valve, any additional valves required because of changed conditions may be installed on the outlet piping.</text>
    </paragraph>
  </paragraph>
  <paragraph num="I.">
    <text>The safety relief valve capacity for a boiler shall be sufficient to ensure that, with fuel burning equipment operated at maximum capacity, pressure cannot exceed:</text>
    <paragraph num="(1)">
      <text>6 PSI above the maximum allowable working pressure of the boiler, for a boiler having a maximum allowable working pressure of 60 PSI or less; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>10 percent above the maximum allowable working pressure, for a boiler having a maximum allowable working pressure greater than 60 PSI.</text>
    </paragraph>
  </paragraph>
  <paragraph num="J.">
    <text>If there is any doubt as to the capacity of a safety relief valve, an accumulation test shall be conducted in accordance with the ASME Code, Section VI, Recommended Rules for the Care and Operation of Heating Boilers.</text>
  </paragraph>
  <paragraph num="K.">
    <text>A valve of any type may not be placed:</text>
    <paragraph num="(1)">
      <text>Between a safety relief valve and a boiler; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>On a discharge pipe between a safety relief valve and the atmosphere.</text>
    </paragraph>
  </paragraph>
  <paragraph num="L.">
    <text>Discharge Pipe.</text>
    <paragraph num="(1)">
      <text>A discharge pipe shall be:</text>
      <paragraph num="(a)">
        <text>At least full-size; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Fitted with an open drain to prevent water from lodging in the upper part of a safety relief valve or in the discharge pipe.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>If a safety relief valve discharge pipe has an elbow, the:</text>
      <paragraph num="(a)">
        <text>Elbow shall be located near the safety relief valve outlet; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Discharge pipe shall be securely anchored and supported.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="M.">
    <text>Safety relief valve discharges shall be located or piped so as not to endanger workers.</text>
  </paragraph>