<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".20" citation="COMAR 09.12.01.20" title_num="09" subtitle_num="12" chapter_num="01" heading="Power Boiler — Existing Installation: Age Limit.">
  <paragraph num="A.">
    <text>Nonstandard Construction.</text>
    <paragraph num="(1)">
      <text>Except as otherwise provided in this regulation, the age limit of a boiler of nonstandard construction installed before the Act became effective shall be 30 years.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>A boiler of nonstandard construction installed before the Act became effective, not having a lap-riveted longitudinal joint, may continue to operate for more than 30 years without reduction in working pressure after a:</text>
      <paragraph num="(a)">
        <text>Thorough internal and external inspection; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Hydrostatic pressure test at 1-1/2 times the allowable working pressure, held for a period of at least 30 minutes, during which no distress or leakage develops.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>A boiler having a lap-riveted longitudinal joint, which operates at a pressure greater than 50 PSI, has an age limit of 20 years.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>The chief boiler inspector may authorize a reasonable time for replacement, not to exceed 1 year.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Standard Construction.</text>
    <paragraph num="(1)">
      <text>The age limit of a boiler of standard construction installed before July 1, 1969 shall be determined by a:</text>
      <paragraph num="(a)">
        <text>Thorough internal and external inspection; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Hydrostatic pressure test conducted at 1-1/2 times the maximum allowable working pressure, with water temperature between 70°F and 140°F and not less than the nil ductility temperature of the material.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>A boiler that exhibits no distress or leakage under test conditions may continue in operation at the same working pressure.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>The shell or drum of a boiler having a lap-seam crack along a longitudinal riveted joint in either a butt seam or a lap joint may not be used under steam pressure.</text>
  </paragraph>
</regulation>