<regulation prefix="Regulation" num=".21" citation="COMAR 09.12.01.21" title_num="09" subtitle_num="12" chapter_num="01" heading="Power Boiler — Existing Installation: Boiler Feed System.">
  <paragraph num="A.">
    <text>A boiler shall have a feed supply which permits it to be fed at any time while under pressure.</text>
  </paragraph>
  <paragraph num="B.">
    <text>A boiler having more than 500 square feet of water-heating surface shall have at least two means of feeding, as follows:</text>
    <paragraph num="(1)">
      <text>One means shall be an approved feed pump, injector, or inspirator;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>The other source may be directly from a water main, at a pressure 6 percent greater than the set pressure of the safety valve having the highest setting.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>A boiler conforming to the ASME Code, PG-61.1, and fired by gaseous, liquid, or solid fuel in suspension may have a single feed supply provided that means are furnished for the immediate shutoff of heat input if the water feed is interrupted.</text>
  </paragraph>
  <paragraph num="D.">
    <text>Feedwater shall be fed into a boiler so that it will not be introduced:</text>
    <paragraph num="(1)">
      <text>Near a riveted joint of a shell or furnace sheet; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Directly against a surface exposed to:</text>
      <paragraph num="(a)">
        <text>A product of combustion, or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Direct radiation from the fire.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Feed Pipe.</text>
    <paragraph num="(1)">
      <text>Feed pipe shall have a:</text>
      <paragraph num="(a)">
        <text>Check valve near the boiler; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Valve or cock between the check valve and the boiler.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>When two or more boilers are fed from a common source, the branch to each boiler shall have a valve between the check valve and source of supply.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>The inlet of a globe valve on a feed pipe shall be under the disc of the valve.</text>
    </paragraph>
  </paragraph>
  <paragraph num="F.">
    <text>Returns.</text>
    <paragraph num="(1)">
      <text>When a return is fed back to a boiler by gravity, each return line shall have, as close as practicable to the boiler, a:</text>
      <paragraph num="(a)">
        <text>Check valve; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Stop valve placed between the boiler and the check valve.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>It is recommended that no stop valve be placed in the supply and return pipe connection of a single boiler installation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="G.">
    <text>Deaerating Heater. When a deaerating heater is:</text>
    <paragraph num="(1)">
      <text>Not used, the recommended minimum temperature for feedwater is 120°F to avoid creating localized stress.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Used, the recommended minimum feedwater temperature is 215°F, so that dissolved gases can be released completely.</text>
    </paragraph>
  </paragraph>
</regulation>