<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".23" citation="COMAR 09.12.01.23" title_num="09" subtitle_num="12" chapter_num="01" heading="Power Boiler — Existing Installation: Other Equipment.">
  <paragraph num="A.">
    <text>Blowoff Connection.</text>
    <paragraph num="(1)">
      <text>A boiler shall have a blowoff pipe, fitted with a valve or cock, connected directly to the lowest water space. The following apply:</text>
      <paragraph num="(a)">
        <text>A cock shall be of the gland or guard type, suitable for the pressure allowed;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A globe valve may not be used.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Settings.</text>
      <paragraph num="(a)">
        <text>The setting around a blowoff pipe shall permit free expansion and contraction.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>To the maximum extent practicable, setting openings shall be sealed without restricting the movement of the blowoff piping.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Blowoff piping exposed to furnace heat shall be:</text>
      <paragraph num="(a)">
        <text>Protected by firebrick or other heat-resisting material; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Constructed so that the piping can be inspected readily.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>When the maximum allowable working pressure exceeds 100 PSIG:</text>
      <paragraph num="(a)">
        <text>A blowoff pipe shall have two valves or a valve and cock of at least extra-heavy type;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Blowoff piping shall:</text>
        <paragraph num="(i)">
          <text>Be at least extra-heavy non-galvanized steel, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Run full size without reducers or bushings.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>A fitting between the boiler and a blowoff valve shall be steel.</text>
    </paragraph>
    <paragraph num="(6)">
      <text>A replacement blowoff pipe or fitting shall be installed in accordance with the ASME Code requirements for new installations.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Steam Gage.</text>
    <paragraph num="(1)">
      <text>A steam boiler shall have a steam gage which:</text>
      <paragraph num="(a)">
        <text>Has a dial range of at least 1-1/2 times the maximum allowable working pressure;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Is connected to:</text>
        <paragraph num="(i)">
          <text>The steam space or steam connection to the water column, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>A siphon or equivalent device of sufficient capacity to keep the gage tube filled with water;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>Is arranged so that the gage can be shut off from the boiler only by a cock with a tee or lever handle:</text>
        <paragraph num="(i)">
          <text>Placed near the gage, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>With the handle parallel to the pipe in which it is located, when the cock is open.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>When a steam gage connection longer than 8 feet is necessary, a shutoff valve near the boiler may be used if the:</text>
      <paragraph num="(a)">
        <text>Valve is:</text>
        <paragraph num="(i)">
          <text>The outside-screw-and-yolk type, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Locked open; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Line is:</text>
        <paragraph num="(i)">
          <text>Of ample size, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Permits free blowing.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>A boiler shall have a 1/4 inch nipple and globe valve:</text>
      <paragraph num="(a)">
        <text>Connected to the steam space; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Used only to attach a test gage while the boiler is in operation, to measure the accuracy of the boiler steam gage.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Stop Valves.</text>
    <paragraph num="(1)">
      <text>Except for safety valve and water column connections, each steam outlet from a boiler shall have a stop valve as near as practicable to the boiler.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Drainage.</text>
      <paragraph num="(a)">
        <text>When a stop valve is located so water can accumulate, ample drains shall be provided.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Drainage shall be piped to a safe location and may not be discharged on the top of the boiler or its setting.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Common Steam Mains.</text>
      <paragraph num="(a)">
        <text>When boilers having manholes are connected to a common steam main, the steam connection from each boiler shall be fitted with two stop valves having an ample free blow drain between them.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The discharge of the drain shall be:</text>
        <paragraph num="(i)">
          <text>Visible to the operator while manipulating the valves; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Piped clear of the boiler setting.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>A stop valve arrangement having one automatic non-return valve beside the boiler, and a second valve of the outside-screw-and-yoke-type, is recommended.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Water Level Indicator.</text>
    <paragraph num="(1)">
      <text>Except for a damper regulator, feedwater regulator, low-water fuel cutout, drain, steam gage, or other apparatus that does not permit the escape of an appreciable amount of steam or water, no outlet connection shall be placed on piping that connects a water column to a boiler.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>A water column shall have a valved drain of at least 3/4 inch pipe size.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>The drain shall be piped to a safe location.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Gage Cocks.</text>
      <paragraph num="(a)">
        <text>Except as otherwise provided by this regulation, a boiler shall have at least three gage cocks within the visible length of the water glass.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A boiler shall have at least two gage cocks if the boiler:</text>
        <paragraph num="(i)">
          <text>Has two water glasses on the same horizontal line; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Is 36 inches or less in diameter, and has a heating surface of 100 square feet or less.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>When a water gage glass is more than 30 feet above the boiler operating floor, remote water-level indicating or recording gages installed above the operating floor at eye level are recommended.</text>
    </paragraph>
  </paragraph>
</regulation>