<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".33" citation="COMAR 09.12.01.33" title_num="09" subtitle_num="12" chapter_num="01" heading="Model Steam Boilers.">
  <paragraph num="A.">
    <text>Model steam boilers are subject to the requirements of Regulations .01, .01-1, .05, .08, .09, .14—.16, .19, and .27—.31 of this chapter.</text>
  </paragraph>
  <paragraph num="B.">
    <text>Repealed.</text>
  </paragraph>
  <paragraph num="C.">
    <text>A model steam boiler may not be operated in Maryland unless it has a valid:</text>
    <paragraph num="(1)">
      <text>Maryland inspection certificate; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Inspection or operating certificate issued by another state having standards equivalent to the requirements of this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Inspection Certificate.</text>
    <paragraph num="(1)">
      <text>Unless sooner suspended or revoked, an inspection certificate expires 1 year from date of issuance.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>An inspection certificate shall specify the maximum operating pressure of the model steam boiler, determined in accordance with this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Initial Test.</text>
    <paragraph num="(1)">
      <text>Before an initial test of a model steam boiler:</text>
      <paragraph num="(a)">
        <text>An owner shall provide the inspector with:</text>
        <paragraph num="(i)">
          <text>Construction drawings,</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Material specifications,</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Welding and brazing information,</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>Stress calculations, in accordance with §H of this regulation,</text>
        </paragraph>
        <paragraph num="(v)">
          <text>The calculated factor of safety,</text>
        </paragraph>
        <paragraph num="(vi)">
          <text>Requested maximum operating pressure,</text>
        </paragraph>
        <paragraph num="(vii)">
          <text>The name and qualifications of the manufacturer and assembler, and</text>
        </paragraph>
        <paragraph num="(viii)">
          <text>The name and qualifications of the designer, if available; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>An inspector shall verify that the design of the model steam boiler is in accordance with the documents provided.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Before being put into operation, a new model steam boiler shall be tested hydrostatically to a pressure of at least two times the maximum operating pressure.</text>
    </paragraph>
  </paragraph>
  <paragraph num="F.">
    <text>Inspection.</text>
    <paragraph num="(1)">
      <text>A model steam boiler shall be tested:</text>
      <paragraph num="(a)">
        <text>Annually; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>After repair or modification.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>An owner requesting an inspection of a model steam boiler shall supply test equipment, including:</text>
      <paragraph num="(a)">
        <text>Water source, pump, pressure lines, and master test gage; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Plugs, gags, or caps to replace safety valves or other appurtenances, if needed to prevent damage by the required test pressure.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>An inspector:</text>
      <paragraph num="(a)">
        <text>Shall conduct an external inspection and, to the extent possible, an internal inspection, to ascertain the physical condition of the model steam boiler before the hydrostatic test is conducted;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Shall witness the hydrostatic test;</text>
      </paragraph>
      <paragraph num="(c)">
        <text>May require that:</text>
        <paragraph num="(i)">
          <text>A model steam boiler be placed in operation so the inspector can make further observations and check safety valve operation, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>An accumulation test be conducted in accordance with Regulation .24J(1)(a) of this chapter; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(d)">
        <text>If the test is completed successfully, shall sign the test report and file it with the chief boiler inspector.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>A hydrostatic test:</text>
      <paragraph num="(a)">
        <text>Except as otherwise provided by this regulation, shall be applied at 1-1/2 times the maximum operating pressure;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>May be conducted using a model steam boiler's feed pump and pressure gage, if the:</text>
        <paragraph num="(i)">
          <text>Range of the gage is sufficient, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Gage has been calibrated in accordance with this regulation; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>May not be approved if the model steam boiler:</text>
        <paragraph num="(i)">
          <text>Shows leakage, bulging or displacement of a sheet, firebox, barrel, or other surface exposed to pressure, or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>While pressure is being increased or is at the maximum level, experiences a serious leak, unusual sound, or sudden drop in pressure.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="G.">
    <text>Equipment.</text>
    <paragraph num="(1)">
      <text>Safety Valve.</text>
      <paragraph num="(a)">
        <text>A model steam boiler shall have two or more safety valves.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Each safety valve shall be set at or below the maximum operating pressure.</text>
      </paragraph>
      <paragraph num="(c)">
        <text>A model steam boiler shall:</text>
        <paragraph num="(i)">
          <text>Have sufficient safety valve capacity to discharge all steam the model steam boiler can generate, without allowing pressure to rise more than 6 percent above the maximum operating pressure; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Comply with the requirements of the ASME Code, Section I, Paragraph PG-70.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Steam Gage. If a steam gage:</text>
      <paragraph num="(a)">
        <text>Has sufficient range:</text>
        <paragraph num="(i)">
          <text>It may be left in place during a test,</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>A record shall be made of its readings and compared with the master test gage, and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>If test readings conflict, the steam gage shall be recalibrated or replaced;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Does not have sufficient range for test pressure:</text>
        <paragraph num="(i)">
          <text>The steam gage shall be removed and calibrated with the test gage or with a dead weight tester, and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>A test gage shall be used to conduct the test.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="H.">
    <text>Maximum operating pressure, as designated on the inspection certificate:</text>
    <paragraph num="(1)">
      <text>For a model steam boiler on a locomotive, shall be that necessary to move the locomotive, considering cylinder dimension and weight on driving wheels;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>For other model steam boilers, shall be that necessary for optimum operation of the engine; and</text>
    </paragraph>
    <paragraph num="(3)">
      <text>May not exceed the maximum allowable working pressure.</text>
    </paragraph>
  </paragraph>
  <paragraph num="I.">
    <text>Maximum Allowable Working Pressure.</text>
    <paragraph num="(1)">
      <text>Maximum allowable working pressure on:</text>
      <paragraph num="(a)">
        <text>The shell of a model steam boiler shall be computed by the formula: (s X t X c)/r = maximum allowable working pressure, PSIG, where:</text>
        <paragraph num="(i)">
          <text>s = maximum allowable material stress, PSI,</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>t = minimum thickness of the shell wall, in inches,</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>c = constant, which for a seamless shell shall be 1.0, and for a welded shell shall be 0.8, and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>r = outside radius of the shell, in inches;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>A stayed surface shall be computed by the formula: (t squared X s X c)/p squared = Maximum allowable working pressure, PSIG, where:</text>
        <paragraph num="(i)">
          <text>c = constant, which for welded or silver soldered stay bolts without heads shall be 2.1, and for welded or silver soldered stay bolts with heads shall be 2.8,</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>p = stay bolt pitch, in inches, using the largest dimension if the spacing is not square,</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>s = maximum allowable material stress, PSI, and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>t = minimum thickness of the wall, in inches;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>A stay bolt shall be computed by the formula: (a X s)/(h X v) = maximum allowable working pressure, PSIG, where:</text>
        <paragraph num="(i)">
          <text>a = cross sectional area of stay bolt, root of thread, if threaded, in square inches,</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>h = stay bolt horizontal spacing, in inches,</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>s = maximum allowable material stress, PSI, and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>v = stay bolt vertical spacing, in inches.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>The calculated factor of safety shall be computed by the formula: ((maximum allowable ASME Code calculated working pressure, PSIG)/(maximum operation pressure, PSIG)) X (ASME Code factor of safety) = calculated factor of safety</text>
    </paragraph>
    <paragraph num="(3)">
      <text>The maximum allowable material stress shall be, for:</text>
      <paragraph num="(a)">
        <text>Carbon steel:</text>
        <paragraph num="(i)">
          <text>Ultimate tensile strength: 50,000 PSI;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>ASME Code factor of safety: 4;</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Allowable working stress: 12,500 PSI; and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>A temperature allowance is not required for pressures up to 250 PSI. Allowable stress values for pressures above 250 PSI shall comply with the requirements of the ASME Code, Section I, Part PG-23.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Copper:</text>
        <paragraph num="(i)">
          <text>Ultimate tensile strength: 30,000 PSI;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>ASME Code factor of safety: 5; and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Allowable working stress, with temperature allowance:</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>