<?xml version='1.0' encoding='utf-8'?>
<subtitle num="17" heading="Board of Stationary Engineers" title_num="09" title_heading="Maryland Department of Labor">
  <chapter num="01" heading="General Regulations">
    <regulation prefix="Regulation" num=".01" heading="Responsibilities of Licensee.">
      <text>A licensee shall be familiar with and comply with the laws and regulations governing the provision of stationary engineer services.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Application for Licensure.">
      <text>An applicant who has successfully completed a license examination shall apply for licensure, and pay all applicable fees, within 2 years of successfully completing the license examination in order for the applicant’s test results to remain valid.</text>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Boiler Certification.">
      <text>If a boiler certification is required, a licensee shall:</text>
      <paragraph num="A.">
        <text>Display conspicuously a current and valid license of each individual assigned to oversee a boiler:</text>
        <paragraph num="(1)">
          <text>Near the regulated machinery; or</text>
        </paragraph>
        <paragraph num="(2)">
          <text>With the certificate of inspection for the regulated machinery;</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Affix a current photograph to the license; and</text>
      </paragraph>
      <paragraph num="C.">
        <text>Have available at all times valid government-issued photographic identification.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Failure to Respond.">
      <paragraph num="A.">
        <text>If an applicant or licensee receives from the Board a written communication requesting a response, the applicant or licensee shall respond in writing within 30 days of the date of the mailing.</text>
      </paragraph>
      <paragraph num="B.">
        <text>The Board shall send a written communication by first-class mail to the last address furnished to the Board by the applicant or licensee.</text>
      </paragraph>
      <paragraph num="C.">
        <text>It is the responsibility of an applicant or licensee to notify the Board in writing if there has been a change in an applicant’s or licensee’s address.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Failure to respond as required by this regulation may be considered by the Board to be a violation of Business Occupations and Professions Article, §6.5-314(a)(1)(ix), Annotated Code of Maryland.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Business Occupations and Professions Article, §§6.5-205, 6.5-304, 6.5-305, 6.5-306, 6.5-311, and 6.5-314(a)(1)(iv), Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: August 5, 2013 (40:15 Md. R. 1229)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .02 amended effective May 22, 2017 (44:10 Md. R. 472)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .04 adopted effective February 25, 2019 (46:4 Md. R. 190)</annotation>
    </annotations>
  </chapter>
  <chapter num="02" heading="Computerized Monitoring System">
    <regulation prefix="Regulation" num=".01" heading="Scope.">
      <text>This chapter governs the duties of licensed stationary engineers and is to be read in conjunction with Maryland Boiler and Pressure Vessel Safety Act, Public Safety Article, Title 12, Subtitle 9, Annotated Code of Maryland.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Definitions.">
      <paragraph num="A.">
        <text>In this chapter, the following terms have the meaning indicated.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Terms Defined.</text>
        <paragraph num="(1)">
          <text>“Competent authority” means:</text>
          <paragraph num="(a)">
            <text>The boiler manufacturer; or</text>
          </paragraph>
          <paragraph num="(b)">
            <text>If the boiler manufacturer is unavailable or defers to a jurisdictional authority:</text>
            <paragraph num="(i)">
              <text>A person designated by the Commissioner of Labor and Industry as a Deputy Boiler Inspector or a Special Boiler Inspector; or</text>
            </paragraph>
            <paragraph num="(ii)">
              <text>A professional engineer who has experience in the design, operation, and maintenance and repair of boilers.</text>
            </paragraph>
          </paragraph>
        </paragraph>
        <paragraph num="(2)">
          <text>“High level” means the level above normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>“High pressure” means the pressure above normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(4)">
          <text>“High temperature” means the temperature above normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(5)">
          <text>“Low level” means the level below normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(6)">
          <text>“Low pressure” means the pressure below normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(7)">
          <text>“Low temperature” means the temperature below normal considered unsafe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(8)">
          <text>“Normal level” means the level considered safe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(9)">
          <text>“Normal pressure” means the pressure considered safe for the operation of the boiler by a competent authority.</text>
        </paragraph>
        <paragraph num="(10)">
          <text>“Normal temperature” means the temperature considered safe for the operation of the boiler by a competent authority.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Incorporation by Reference.">
      <text>Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1), published by the American Society of Mechanical Engineers, which has been incorporated by reference in COMAR 09.12.01.01-1, is incorporated by reference in this chapter.</text>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Monitors and Indicators.">
      <paragraph num="A.">
        <text>For a boiler, a computerized monitoring system shall qualify as a "24-hour computerized monitoring system and automatic controls," in accordance with Business Occupations and Professions Article, Title 6.5, Annotated Code of Maryland, if it meets the requirements of this regulation.</text>
      </paragraph>
      <paragraph num="B.">
        <text>For a boiler operating at 30 to 299 horsepower, the system shall monitor and indicate:</text>
        <paragraph num="(1)">
          <text>Stack flue gas temperature;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Burner status, including “on” and “off” indicators;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>One of the following, as applicable:</text>
          <paragraph num="(a)">
            <text>For steam boilers:</text>
            <paragraph num="(i)">
              <text>Pressure; and</text>
            </paragraph>
            <paragraph num="(ii)">
              <text>Water level; or</text>
            </paragraph>
          </paragraph>
          <paragraph num="(b)">
            <text>For hot water boilers, temperature.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="C.">
        <text>For a boiler operating at 300 horsepower or more, the system shall monitor, indicate, and record:</text>
        <paragraph num="(1)">
          <text>Stack flue gas temperature;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Burner status, including “on” and “off” indicators;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>One of the following, as applicable:</text>
          <paragraph num="(a)">
            <text>For steam boilers:</text>
            <paragraph num="(i)">
              <text>Pressure; and</text>
            </paragraph>
            <paragraph num="(ii)">
              <text>Water level; or</text>
            </paragraph>
          </paragraph>
          <paragraph num="(b)">
            <text>For hot water boilers:</text>
            <paragraph num="(i)">
              <text>Pressure; and</text>
            </paragraph>
            <paragraph num="(ii)">
              <text>Temperature.</text>
            </paragraph>
          </paragraph>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Automatic Controls.">
      <text>A computerized monitoring system shall be equipped with automatic controls in accordance with whichever is more restrictive of the Maryland Boiler and Pressure Vessel Safety Act, Public Safety Article, Title 12, Subtitle 9, Annotated Code of Maryland or ASME CSD-1.</text>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Alarm.">
      <text>A computerized monitoring system shall be equipped with an alarm that will activate when:</text>
      <paragraph num="A.">
        <text>The stack flue gas reaches a high temperature;</text>
      </paragraph>
      <paragraph num="B.">
        <text>The burner status indicator indicates the burner is “off”;</text>
      </paragraph>
      <paragraph num="C.">
        <text>The flame safety control status indicates a “flame failure”; and</text>
      </paragraph>
      <paragraph num="D.">
        <text>One of the following occurs, as applicable:</text>
        <paragraph num="(1)">
          <text>For steam boilers, the:</text>
          <paragraph num="(a)">
            <text>Steam reaches low or high pressure; or</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Water reaches low or high level;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(2)">
          <text>For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or</text>
        </paragraph>
        <paragraph num="(3)">
          <text>For a hot water boiler operating at 300 or more horsepower the water reaches low or high:</text>
          <paragraph num="(a)">
            <text>Pressure;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Temperature; or</text>
          </paragraph>
          <paragraph num="(c)">
            <text>Level.</text>
          </paragraph>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".07" heading="Automatic Shutdown.">
      <text>A computerized monitoring system shall be equipped with an automatic burner shutdown mechanism that will activate when:</text>
      <paragraph num="A.">
        <text>Stack flue gas reaches high temperature; and</text>
      </paragraph>
      <paragraph num="B.">
        <text>One of the following occurs, as applicable:</text>
        <paragraph num="(1)">
          <text>For a steam boiler:</text>
          <paragraph num="(a)">
            <text>Steam reaches high pressure; or</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Water reaches Low or high level;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(2)">
          <text>For a hot water boiler operating at 30 to 299 horsepower, water reaches high temperature; or</text>
        </paragraph>
        <paragraph num="(3)">
          <text>For a hot water boiler operating at 300 or more horsepower, water reaches:</text>
          <paragraph num="(a)">
            <text>High pressure;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>High temperature; or</text>
          </paragraph>
          <paragraph num="(c)">
            <text>Low level.</text>
          </paragraph>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".08" heading="Manual Reset.">
      <paragraph num="A.">
        <text>Subject to §B of this regulation, manual reset following an automatic shutdown as set forth in Regulation .07 of this chapter requires that a licensee or the licensee's designee shall physically inspect the boiler and appurtenances prior to restart.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Notwithstanding §A of this regulation, the licensee shall be responsible for the safe operation of a boiler at all times in accordance with Business Occupations and Professions Article, §6.5-302, Annotated Code of Maryland.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".09" heading="Miscellaneous Provisions.">
      <text>The Board may accept an alternate computerized monitoring system if the system is equipped with features that provide a comparable level of safety, monitoring, and control to those required by this regulation, in the opinion of the Board.</text>
    </regulation>
    <annotations>
      <annotation type="Authority">Article 4, §4-1, Public Laws of Baltimore City</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: December 27, 2010 (37:26 Md. R. 1786)</annotation>
    </annotations>
  </chapter>
  <chapter num="03" heading="Fees">
    <regulation prefix="Regulation" num=".01" heading="Purpose.">
      <text>This chapter is intended to carry out the provisions of Business Occupations and Professions Article, Title 12, Annotated Code of Maryland, and Business Regulation Article, §§2-106.9 and 2-106.10, Annotated Code of Maryland. In particular, it is intended to set various fees in order to cover the actual documented direct and indirect costs of fulfilling the statutory and regulatory duties of the State Board of Master Electricians, the State Board of Stationary Engineers, the State Board of Plumbing, and the State Board of Heating, Ventilation, Air-Conditioning, and Refrigeration Contractors.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Definitions.">
      <paragraph num="A.">
        <text>In this chapter, the following terms have the meanings indicated.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Terms Defined.</text>
        <paragraph num="(1)">
          <text>“Board” means the State Board of Stationary Engineers.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>“License fee” means the fee paid by an applicant or licensee, as applicable, in connection with the issuance and renewal of a license and the issuance of a limited license and a reciprocal license.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>“Mechanical boards” means collectively the:</text>
          <paragraph num="(a)">
            <text>State Board of Master Electricians;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>State Board of Stationary Engineers;</text>
          </paragraph>
          <paragraph num="(c)">
            <text>State Board of Plumbing; and</text>
          </paragraph>
          <paragraph num="(d)">
            <text>State Board of Heating, Ventilation, Air-Conditioning, and Refrigeration Contractors.</text>
          </paragraph>
        </paragraph>
        <paragraph num="(4)">
          <text>“Secretary” means the Secretary of Labor.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Fees and Costs.">
      <paragraph num="A.">
        <text>The Secretary and the mechanical boards have agreed to average their direct and indirect costs, based on the calculation of costs performed by the Secretary in consultation with the mechanical boards. Based on these calculations, the Board sets the following nonrefundable fees as of January 1, 2024:</text>
        <paragraph num="(1)">
          <text>Original and Renewal License:</text>
          <paragraph num="(a)">
            <text>Grade 1 — $73;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Grade 2 — $56;</text>
          </paragraph>
          <paragraph num="(c)">
            <text>Grade 3 — $56;</text>
          </paragraph>
          <paragraph num="(d)">
            <text>Grade 4 — $39; and</text>
          </paragraph>
          <paragraph num="(e)">
            <text>Grade 5 — $39.</text>
          </paragraph>
        </paragraph>
        <paragraph num="(2)">
          <text>Application — $28.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Reinstatement — $112.50.</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Letter of Good Standing — $50.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>The Secretary and the mechanical boards have agreed to average their direct and indirect costs, based on the calculation of costs performed by the Secretary in consultation with the mechanical boards. Based on these calculations, the Board sets the following nonrefundable fees as of January 1, 2025:</text>
        <paragraph num="(1)">
          <text>Original and Renewal License:</text>
          <paragraph num="(a)">
            <text>Grade 1 — $82;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Grade 2 — $63;</text>
          </paragraph>
          <paragraph num="(c)">
            <text>Grade 3 — $63;</text>
          </paragraph>
          <paragraph num="(d)">
            <text>Grade 4 — $43; and</text>
          </paragraph>
          <paragraph num="(e)">
            <text>Grade 5 — $43.</text>
          </paragraph>
        </paragraph>
        <paragraph num="(2)">
          <text>Application — $31.50.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Reinstatement — $126.</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Letter of Good Standing — $50.</text>
        </paragraph>
      </paragraph>
      <paragraph num="C.">
        <text>An applicant for an examination or reexamination shall pay an examination or reexamination fee directly to the testing service chosen by the Board to develop or administer the examination, as such fees are established by the testing service selected by the Board.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Business Occupations and Professions Article, §§6.5-205(a)(1), 6.5-207, 6.5-304, 6.5-306, 6.5-312, and 6.5-313; Business Regulation Article, §§2-106.2, 2-106.9 and 2-106.10; Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: August 27, 2018 (45:17 Md. R. 802)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .03 amended effective April 15, 2024 (51:7 Md. R. 332)</annotation>
    </annotations>
  </chapter>
</subtitle>