<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".04" citation="COMAR 09.17.02.04" title_num="09" subtitle_num="17" chapter_num="02" heading="Monitors and Indicators.">
  <paragraph num="A.">
    <text>For a boiler, a computerized monitoring system shall qualify as a "24-hour computerized monitoring system and automatic controls," in accordance with Business Occupations and Professions Article, Title 6.5, Annotated Code of Maryland, if it meets the requirements of this regulation.</text>
  </paragraph>
  <paragraph num="B.">
    <text>For a boiler operating at 30 to 299 horsepower, the system shall monitor and indicate:</text>
    <paragraph num="(1)">
      <text>Stack flue gas temperature;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Burner status, including “on” and “off” indicators;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>One of the following, as applicable:</text>
      <paragraph num="(a)">
        <text>For steam boilers:</text>
        <paragraph num="(i)">
          <text>Pressure; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Water level; or</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>For hot water boilers, temperature.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>For a boiler operating at 300 horsepower or more, the system shall monitor, indicate, and record:</text>
    <paragraph num="(1)">
      <text>Stack flue gas temperature;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Burner status, including “on” and “off” indicators;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>One of the following, as applicable:</text>
      <paragraph num="(a)">
        <text>For steam boilers:</text>
        <paragraph num="(i)">
          <text>Pressure; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Water level; or</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>For hot water boilers:</text>
        <paragraph num="(i)">
          <text>Pressure; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Temperature.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>