Regulation .06 Alarm.
Regulation .06 Alarm.LinkCopy Citation
A computerized monitoring system shall be equipped with an alarm that will activate when:
A.
The stack flue gas reaches a high temperature;
B.
The burner status indicator indicates the burner is “off”;
C.
The flame safety control status indicates a “flame failure”; and
D.
One of the following occurs, as applicable:
(1)
For steam boilers, the:
(a)
Steam reaches low or high pressure; or
(b)
Water reaches low or high level;
(2)
For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or
(3)
For a hot water boiler operating at 300 or more horsepower the water reaches low or high:
(a)
Pressure;
(b)
Temperature; or
(c)
Level.