<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".06" citation="COMAR 09.17.02.06" title_num="09" subtitle_num="17" chapter_num="02" heading="Alarm.">
  <text>A computerized monitoring system shall be equipped with an alarm that will activate when:</text>
  <paragraph num="A.">
    <text>The stack flue gas reaches a high temperature;</text>
  </paragraph>
  <paragraph num="B.">
    <text>The burner status indicator indicates the burner is “off”;</text>
  </paragraph>
  <paragraph num="C.">
    <text>The flame safety control status indicates a “flame failure”; and</text>
  </paragraph>
  <paragraph num="D.">
    <text>One of the following occurs, as applicable:</text>
    <paragraph num="(1)">
      <text>For steam boilers, the:</text>
      <paragraph num="(a)">
        <text>Steam reaches low or high pressure; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Water reaches low or high level;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or</text>
    </paragraph>
    <paragraph num="(3)">
      <text>For a hot water boiler operating at 300 or more horsepower the water reaches low or high:</text>
      <paragraph num="(a)">
        <text>Pressure;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Temperature; or</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Level.</text>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>