<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".07" citation="COMAR 09.17.02.07" title_num="09" subtitle_num="17" chapter_num="02" heading="Automatic Shutdown.">
  <text>A computerized monitoring system shall be equipped with an automatic burner shutdown mechanism that will activate when:</text>
  <paragraph num="A.">
    <text>Stack flue gas reaches high temperature; and</text>
  </paragraph>
  <paragraph num="B.">
    <text>One of the following occurs, as applicable:</text>
    <paragraph num="(1)">
      <text>For a steam boiler:</text>
      <paragraph num="(a)">
        <text>Steam reaches high pressure; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Water reaches Low or high level;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>For a hot water boiler operating at 30 to 299 horsepower, water reaches high temperature; or</text>
    </paragraph>
    <paragraph num="(3)">
      <text>For a hot water boiler operating at 300 or more horsepower, water reaches:</text>
      <paragraph num="(a)">
        <text>High pressure;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>High temperature; or</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Low level.</text>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>