<?xml version='1.0' encoding='utf-8'?>
<chapter num="02" heading="Computerized Monitoring System" title_num="09" subtitle_num="17">
  <regulation prefix="Regulation" num=".01" heading="Scope.">
    <text>This chapter governs the duties of licensed stationary engineers and is to be read in conjunction with Maryland Boiler and Pressure Vessel Safety Act, Public Safety Article, Title 12, Subtitle 9, Annotated Code of Maryland.</text>
  </regulation>
  <regulation prefix="Regulation" num=".02" heading="Definitions.">
    <paragraph num="A.">
      <text>In this chapter, the following terms have the meaning indicated.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Terms Defined.</text>
      <paragraph num="(1)">
        <text>“Competent authority” means:</text>
        <paragraph num="(a)">
          <text>The boiler manufacturer; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the boiler manufacturer is unavailable or defers to a jurisdictional authority:</text>
          <paragraph num="(i)">
            <text>A person designated by the Commissioner of Labor and Industry as a Deputy Boiler Inspector or a Special Boiler Inspector; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>A professional engineer who has experience in the design, operation, and maintenance and repair of boilers.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>“High level” means the level above normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>“High pressure” means the pressure above normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(4)">
        <text>“High temperature” means the temperature above normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(5)">
        <text>“Low level” means the level below normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(6)">
        <text>“Low pressure” means the pressure below normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(7)">
        <text>“Low temperature” means the temperature below normal considered unsafe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(8)">
        <text>“Normal level” means the level considered safe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(9)">
        <text>“Normal pressure” means the pressure considered safe for the operation of the boiler by a competent authority.</text>
      </paragraph>
      <paragraph num="(10)">
        <text>“Normal temperature” means the temperature considered safe for the operation of the boiler by a competent authority.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".03" heading="Incorporation by Reference.">
    <text>Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1), published by the American Society of Mechanical Engineers, which has been incorporated by reference in COMAR 09.12.01.01-1, is incorporated by reference in this chapter.</text>
  </regulation>
  <regulation prefix="Regulation" num=".04" heading="Monitors and Indicators.">
    <paragraph num="A.">
      <text>For a boiler, a computerized monitoring system shall qualify as a "24-hour computerized monitoring system and automatic controls," in accordance with Business Occupations and Professions Article, Title 6.5, Annotated Code of Maryland, if it meets the requirements of this regulation.</text>
    </paragraph>
    <paragraph num="B.">
      <text>For a boiler operating at 30 to 299 horsepower, the system shall monitor and indicate:</text>
      <paragraph num="(1)">
        <text>Stack flue gas temperature;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Burner status, including “on” and “off” indicators;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>One of the following, as applicable:</text>
        <paragraph num="(a)">
          <text>For steam boilers:</text>
          <paragraph num="(i)">
            <text>Pressure; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Water level; or</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>For hot water boilers, temperature.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>For a boiler operating at 300 horsepower or more, the system shall monitor, indicate, and record:</text>
      <paragraph num="(1)">
        <text>Stack flue gas temperature;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Burner status, including “on” and “off” indicators;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Flame safety control status, including “normal” and “flame failure” indicators; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>One of the following, as applicable:</text>
        <paragraph num="(a)">
          <text>For steam boilers:</text>
          <paragraph num="(i)">
            <text>Pressure; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Water level; or</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>For hot water boilers:</text>
          <paragraph num="(i)">
            <text>Pressure; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Temperature.</text>
          </paragraph>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".05" heading="Automatic Controls.">
    <text>A computerized monitoring system shall be equipped with automatic controls in accordance with whichever is more restrictive of the Maryland Boiler and Pressure Vessel Safety Act, Public Safety Article, Title 12, Subtitle 9, Annotated Code of Maryland or ASME CSD-1.</text>
  </regulation>
  <regulation prefix="Regulation" num=".06" heading="Alarm.">
    <text>A computerized monitoring system shall be equipped with an alarm that will activate when:</text>
    <paragraph num="A.">
      <text>The stack flue gas reaches a high temperature;</text>
    </paragraph>
    <paragraph num="B.">
      <text>The burner status indicator indicates the burner is “off”;</text>
    </paragraph>
    <paragraph num="C.">
      <text>The flame safety control status indicates a “flame failure”; and</text>
    </paragraph>
    <paragraph num="D.">
      <text>One of the following occurs, as applicable:</text>
      <paragraph num="(1)">
        <text>For steam boilers, the:</text>
        <paragraph num="(a)">
          <text>Steam reaches low or high pressure; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Water reaches low or high level;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>For a hot water boiler operating at 300 or more horsepower the water reaches low or high:</text>
        <paragraph num="(a)">
          <text>Pressure;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Temperature; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Level.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".07" heading="Automatic Shutdown.">
    <text>A computerized monitoring system shall be equipped with an automatic burner shutdown mechanism that will activate when:</text>
    <paragraph num="A.">
      <text>Stack flue gas reaches high temperature; and</text>
    </paragraph>
    <paragraph num="B.">
      <text>One of the following occurs, as applicable:</text>
      <paragraph num="(1)">
        <text>For a steam boiler:</text>
        <paragraph num="(a)">
          <text>Steam reaches high pressure; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Water reaches Low or high level;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>For a hot water boiler operating at 30 to 299 horsepower, water reaches high temperature; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>For a hot water boiler operating at 300 or more horsepower, water reaches:</text>
        <paragraph num="(a)">
          <text>High pressure;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>High temperature; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Low level.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".08" heading="Manual Reset.">
    <paragraph num="A.">
      <text>Subject to §B of this regulation, manual reset following an automatic shutdown as set forth in Regulation .07 of this chapter requires that a licensee or the licensee's designee shall physically inspect the boiler and appurtenances prior to restart.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Notwithstanding §A of this regulation, the licensee shall be responsible for the safe operation of a boiler at all times in accordance with Business Occupations and Professions Article, §6.5-302, Annotated Code of Maryland.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".09" heading="Miscellaneous Provisions.">
    <text>The Board may accept an alternate computerized monitoring system if the system is equipped with features that provide a comparable level of safety, monitoring, and control to those required by this regulation, in the opinion of the Board.</text>
  </regulation>
  <annotations>
    <annotation type="Authority">Article 4, §4-1, Public Laws of Baltimore City</annotation>
    <annotation type="History" subtype="Administrative History">Effective date: December 27, 2010 (37:26 Md. R. 1786)</annotation>
  </annotations>
</chapter>