<regulation prefix="Regulation" num=".45" citation="COMAR 10.07.02.45" title_num="10" subtitle_num="07" chapter_num="02" heading="Physical Plant — Ventilation.">
  <paragraph num="A.">
    <text>Unless otherwise indicated, all general requirements apply to both new construction and an existing nursing home.</text>
  </paragraph>
  <paragraph num="B.">
    <text>An existing nursing home shall provide for adequate ventilation through windows or mechanical means or a combination of both.</text>
  </paragraph>
  <paragraph num="C.">
    <text>A new nursing home shall adhere to the requirements of this chapter.</text>
  </paragraph>
  <paragraph num="D.">
    <text>Ventilation System Details.</text>
    <paragraph num="(1)">
      <text>All air-supply and air-exhaust systems shall be mechanically operated.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>The ventilation rates shown in Table 1 under §D(10) of this regulation shall be considered the minimum acceptable rates and may not be construed as precluding the use of higher ventilation rates.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>All fans serving exhaust systems shall be located at the discharge end of the system.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Outdoor air intakes shall be located:</text>
      <paragraph num="(a)">
        <text>As far as practical but not less than 25 feet from:</text>
        <paragraph num="(i)">
          <text>Exhaust outlets of ventilating systems;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Combustion equipment stacks;</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Medical-surgical vacuum systems;</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>Plumbing vent stacks; or</text>
        </paragraph>
        <paragraph num="(v)">
          <text>Areas that may collect vehicular exhaust and other noxious fumes; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>As high as practical, so that the bottom of the outdoor air intake is:</text>
        <paragraph num="(i)">
          <text>At least 6 feet above ground level; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>At least 3 feet above roof level.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>The ventilation systems shall be designed and balanced to provide the pressure relationships as shown in Table 1 under §D(10) of this regulation.</text>
    </paragraph>
    <paragraph num="(6)">
      <text>The bottoms of ventilation openings may not be not less than 3 inches above the floor of any room.</text>
    </paragraph>
    <paragraph num="(7)">
      <text>Corridors may not be used to supply air to or exhaust air from any room, except that air from corridors may be used to ventilate bathrooms, toilet rooms, janitors’ closets, and small electrical or telephone closets opening directly on corridors.</text>
    </paragraph>
    <paragraph num="(8)">
      <text>Filters.</text>
      <paragraph num="(a)">
        <text>A central ventilation or air conditioning system shall be equipped with filters having efficiencies no less than those specified in Table 2 under §D(11) of this regulation.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The filter bed shall be located upstream of the air conditioning equipment, unless a prefilter is employed.</text>
      </paragraph>
      <paragraph num="(c)">
        <text>If a prefilter is employed, the prefilter shall be upstream of the equipment and the main filter bed may be located further downstream.</text>
      </paragraph>
      <paragraph num="(d)">
        <text>A filter or filter efficiency shall comply with the standards of the Guidelines for Design and Construction of Residential Health, Care, and Support Facilities.</text>
      </paragraph>
      <paragraph num="(e)">
        <text>A filter frame shall be durable and carefully dimensioned and shall have an airtight fit with the enclosing duct work.</text>
      </paragraph>
      <paragraph num="(f)">
        <text>A joint between filter segments and the enclosing duct work shall be gasketed or sealed to provide a positive seal against air leakage.</text>
      </paragraph>
      <paragraph num="(g)">
        <text>A manometer shall be installed across each filter bed serving central air systems.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(9)">
      <text>Air Ducts.</text>
      <paragraph num="(a)">
        <text>Air-handling duct systems shall meet the requirements applicable to nursing homes cited in NFPA 99 Health Care Facilities Code.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Fire and smoke dampers shall be constructed, located, and installed in accordance with the requirements of NFPA 101 Life Safety Code.</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Air ducts that pass through a required smoke barrier shall be provided with a smoke damper at the barrier.</text>
      </paragraph>
      <paragraph num="(d)">
        <text>Smoke dampers shall activate by smoke detectors located in the ducts at the smoke barrier, or by the smoke detectors used to close smoke barrier doors.</text>
      </paragraph>
      <paragraph num="(e)">
        <text>Smoke dampers shall be controlled to close automatically to prevent flow of smoke-laden air in either direction.</text>
      </paragraph>
      <paragraph num="(f)">
        <text>Smoke dampers shall be equipped with automatic remote control reset devices, except that manual reopening will be permitted if smoke dampers are accessible.</text>
      </paragraph>
      <paragraph num="(g)">
        <text>All devices shall be interlocked with the fire alarm system.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(10)">
      <text>Table 1. This table refers to the pressure relationships and ventilation of certain areas of a nursing home other than chronic disease hospitals.</text>
    </paragraph>
    <paragraph num="(11)">
      <text>Table 2. This table refers to the filter efficiencies for central ventilation and air conditioning systems in a nursing home other than chronic disease hospitals.</text>
    </paragraph>
    <paragraph num="(12)">
      <text>Exhaust Hoods. All hoods over cooking surfaces shall comply with the requirements as provided in COMAR 10.15.03.</text>
    </paragraph>
  </paragraph>
</regulation>