<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".43" citation="COMAR 10.07.14.43" title_num="10" subtitle_num="07" chapter_num="14" heading="Water Supply.">
  <paragraph num="A.">
    <text>Approved Source. A facility shall be served by water from an approved public water supply. If an approved public water supply is not available, a private water supply may be accepted if it is approved by the local jurisdiction in which the program is located or a private certified vendor to be submitted with an initial licensure application.</text>
  </paragraph>
  <paragraph num="B.">
    <text>Adequacy. The water supply shall be adequate in quantity and delivered under sufficient pressure to satisfactorily serve all fixtures in the facility.</text>
  </paragraph>
  <paragraph num="C.">
    <text>Hot Water Temperature. Hot water accessible to residents shall be blended externally to the hot water generator, by either individual point-of-use control valves of the anti-scald or thermostatic mixing valve type, to a maximum temperature of 120°F and a minimum temperature of 100°F at the fixture.</text>
  </paragraph>
</regulation>