<chapter num="07" heading="Quality of Service" title_num="20" subtitle_num="50">
  <regulation prefix="Regulation" num=".01" heading="Standard Frequency.">
    <text>The standard frequency for alternating current distribution systems shall be either 60 cycles per second or 25 cycles per second.</text>
  </regulation>
  <regulation prefix="Regulation" num=".02" heading="Voltage Limits.">
    <paragraph num="A.">
      <text>Secondary Voltages. The voltage at the utility's service terminals, as installed for each customer, shall be maintained within the Limits specified in the table below. If a utility adopts any standard voltage not included in the table, it shall advise the Commission in order that the Commission may establish appropriate voltage limits. When 3-phase service is provided, the utility shall exercise reasonable care to assure that the phase voltages are balanced.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Primary Voltages. The following limits shall apply where the utility supplies service at primary voltage:</text>
      <paragraph num="(1)">
        <text>Industrial Customers. For service rendered principally for industrial or power purposes, the voltage may not exceed 7-1/2 percent above or 7-1/2 percent below the standard nominal voltages as filed in the utility's rules.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Sales For Resale. For service rendered to public utilities and others for resale, the nominal voltage shall be as mutually agreed upon by the parties concerned. The allowable voltage may not exceed 7-1/2 percent above or 7-1/2 percent below the agreed upon nominal voltage without the express approval of the Commission.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Special Contract Exceptions. The limitations in §§B(1) and B(2), of this regulation, do not apply to special contracts in which the customer specifically agrees to accept service with unregulated voltage.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Exceptions to Voltage Requirements. It will not be considered a violation when voltages outside of the prescribed limits are caused by any of the following:</text>
      <paragraph num="(1)">
        <text>Action of the elements;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Service interruptions;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Temporary separation of parts of the system from the main system;</text>
      </paragraph>
      <paragraph num="(4)">
        <text>Infrequent fluctuations not exceeding 5 minutes' duration; or</text>
      </paragraph>
      <paragraph num="(5)">
        <text>Other causes beyond the control of the utility.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".03" heading="Voltmeters.">
    <paragraph num="A.">
      <text>Requirements. Each utility shall have the following voltmeters for the purposes indicated:</text>
      <paragraph num="(1)">
        <text>Secondary Standard. Each utility shall have at least one secondary standard indicating voltmeter to be used in checking the accuracy of working standard voltmeters.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Working Standards. Each utility shall have at least two working standard indicating voltmeters to be used in checking the voltage on the utility's electric system and in checking the accuracy of recording voltmeters.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Recording Voltmeters. Each utility shall have at least two portable recording voltmeters to be used to record the voltage on the utility's electric system.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Accuracy. The voltmeters shall be of sufficient quality to meet the accuracy standards prescribed below:</text>
      <paragraph num="(1)">
        <text>Secondary Standard. The secondary standard indicating voltmeter shall have a stated accuracy within 0.25 percent of full scale. This instrument shall be maintained within its stated accuracy.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Working Standards. The working standard indicating voltmeters shall have a stated accuracy within 0.75 percent of full scale.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Recording Voltmeters. The portable recording voltmeters shall have a stated accuracy within 1.5 percent of full scale.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Calibration. The accuracy of the voltmeters shall be checked as indicated below:</text>
      <paragraph num="(1)">
        <text>Secondary Standard. Secondary standards shall be checked at intervals not exceeding 3 years at the National Bureau of Standards, or at a laboratory acceptable to the Commission.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Working Standards. Working standards shall be checked at intervals not exceeding 3 years by comparison with a secondary standard in the utility's meter shop.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Certificates. Each standard shall be accompanied at all times by a certificate or calibration card, duly signed and dated, on which are recorded the corrections required to compensate for errors found at the customary test points at the time of the last calibration test.</text>
    </paragraph>
    <paragraph num="E.">
      <text>Care In Handling. Extreme care shall be exercised in the handling of standards and other instruments to assure that their accuracy is not disturbed.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".04" heading="Voltage Surveys and Records.">
    <paragraph num="A.">
      <text>Voltage Surveys. Each utility shall make voltage measurements, using recording voltmeters, in order to determine if voltages are in compliance with the requirements contained in Regulation .02.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Point of Measurement. Voltage measurements shall be made at the utility's service terminals. For single phase service, the measurement shall be made between the grounded conductor and the ungrounded conductors. For 3 phase service, the measurement shall be made between the phase wires.</text>
    </paragraph>
    <paragraph num="C.">
      <text>Voltage Records. All voltmeter records obtained under §A, above, shall be retained by the utility for at least 2 years and shall be available for inspection by the Commission's representatives. Notations on each chart shall indicate the following:</text>
      <paragraph num="(1)">
        <text>Location where the voltage was taken;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Time and date of the test;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Results of the comparison of the recording voltmeter with an indicating voltmeter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Record of Corrective Action. If action is taken to correct the voltage conditions, the chart which records the voltage subsequent to the change shall be attached to the first chart so that the conditions before and after the change may be reviewed.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".05" heading="Interruption of Service.">
    <paragraph num="A.">
      <text>Endeavor to Avoid Interruptions. Each utility shall make reasonable efforts to avoid interruptions of service, but when interruptions occur, service shall be re-established within the shortest time practicable, consistent with safety.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Report to Commission.</text>
      <paragraph num="(1)">
        <text>Each utility shall promptly report to the Commission's Engineering Division and Consumer Affairs Division:</text>
        <paragraph num="(a)">
          <text>The onset of a major outage event;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>A sustained interruption, to firm-service customers, initiated by the utility in response to unacceptable system voltages; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>A sustained interruption, to firm-service customers, initiated by the utility in response to thermal overloads of electric plant.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>The utility's report required by §B(1) of this regulation shall include a general description of the areas experiencing a sustained interruption and the expected system restoration times, if available.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>The utility making the report required by §B(1) of this regulation shall also provide periodic updates to the Consumer Affairs Division.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Planned Interruptions. Planned interruptions shall be made at a time that will not cause unreasonable inconvenience to customers and shall be preceded, if feasible, by adequate notice to those who will be affected.</text>
    </paragraph>
    <paragraph num="D.">
      <text>Record of Interruptions. Each utility shall keep records of interruptions of service on its primary distribution system and shall make an analysis of the records for the purpose of determining steps to be taken to prevent recurrence of the interruptions. The records should include the following information concerning the interruptions:</text>
      <paragraph num="(1)">
        <text>Cause;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Date and time; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Duration.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Momentary Interruption Record. A utility shall maintain information which it collects on momentary interruptions for 5 years.</text>
    </paragraph>
    <paragraph num="F.">
      <text>Unattended Substations. The record for each unattended substation shall show interruptions which required attention to restore service, with the estimated time of interruption.</text>
    </paragraph>
  </regulation>
  <annotations>
    <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
    <annotation type="History" subtype="Administrative History">Effective date: May 22, 1942 (Order No. 38330)</annotation>
    <annotation type="History" subtype="Administrative History">Chapter revised effective May 18, 1960 (Order No. 54348)</annotation>
    <annotation type="History" subtype="Administrative History">Chapter revised effective June 1, 1965 (Order No. 55819)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .03C amended effective June 6, 2005 (32:11 Md. R. 983)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .05 amended effective April 15, 2002 (29:7 Md. R. 622)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .05B amended effective May 28, 2012 (39:10 Md. R. 661)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .06 adopted effective April 15, 2002 (29:7 Md. R. 622)</annotation>