<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".03" citation="COMAR 20.50.12.03" title_num="20" subtitle_num="50" chapter_num="12" heading="Poorest Performing Feeder Standard.">
  <paragraph num="A.">
    <text>Poorest Performing Feeder Standard for Feeders Assigned to Maryland.</text>
    <paragraph num="(1)">
      <text>A utility shall report in its annual performance report CAIDI, SAIDI, and SAIFI indices for all feeders assigned to Maryland that are identified by the utility as having the poorest feeder reliability.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>For each utility, each index shall be calculated and reported in the annual performance report using all interruption data, and all interruption data minus the following exclusions:</text>
      <paragraph num="(a)">
        <text>Source loss, including any outage that occurs on the feeder by an event occurring external to the feeder;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Major outage events; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Planned outages.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>For each utility, the feeders with poorest reliability shall be all feeders having circuit reliability performance 250 percent or more above the utility’s System-Wide SAIFI and SAIDI, which shall be calculated in accordance with the exclusions identified in §A(2) of this regulation.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>No feeder shall appear in a utility’s list of poorest performing feeders during three consecutive 12-month reporting periods, unless the utility has undertaken reasonable remediation measures to improve the performance of the feeder.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Poorest Performing Feeder Standard for Feeders Not Assigned to Maryland.</text>
    <paragraph num="(1)">
      <text>For each feeder not assigned to Maryland that serves more than ten Maryland customers, the utility shall report the feeder in its annual performance report and the feeder’s CAIDI, SAIDI, and SAIFI indices, if the feeder would have been included on the poorest performing feeder list but for the fact that the feeder is not assigned to Maryland.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>For each feeder included in §B(1) of this regulation, the utility shall report the number of customers located in Maryland and the number of customers located in a bordering jurisdiction.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>For each feeder reported in §B(1) of this regulation, the utility shall implement reasonable remediation measures to improve the performance of the feeder portion serving Maryland customers, which measures shall be described by the utility in its annual performance report. If implementing a remediation plan is not reasonable, the utility shall provide an explanation of its decision in its annual performance plan.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>The reliability indices and method for identifying the performance of feeders under this provision shall be consistent with §A(2), (3), and (4) of this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Evaluation of Remedial Actions. For the feeders that are identified as having the poorest performance, the utility shall provide the following information:</text>
    <paragraph num="(1)">
      <text>In the annual performance report in which the feeders are identified as requiring reasonable remediation measures, a brief description of the actions taken or proposed, if any, to improve reliability and the actual or expected completion date of the action; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>In the five subsequent annual performance reports, the performance of the feeder shall be reported with its performance ranking.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Feeders Assigned to Maryland.</text>
    <paragraph num="(1)">
      <text>All feeders of a utility that serve only Maryland customers are assigned to Maryland.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>For a utility that has one or more feeders that serve a Maryland customer and at least one customer in a bordering jurisdiction:</text>
      <paragraph num="(a)">
        <text>The feeders used in determining the utility’s system-wide SAIDI and SAIFI performance results as reported to the Commission by the utility’s 2010 annual reliability report shall be assigned to Maryland unless otherwise directed by the Commission;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The utility may not change the assignment list without Commission approval; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>For a new feeder added to the utility's system, or an existing feeder that is modified, that serves more than ten Maryland customers and at least one customer in a bordering jurisdiction, the utility shall file notice with the Commission advising of the feeder's assignment.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>If a utility fails to satisfy the standard in §A(4) of this regulation with respect to a feeder assigned to Maryland, it shall provide a corrective action plan, preferably in its annual performance report but by no later than April 1.</text>
  </paragraph>
</regulation>