<?xml version='1.0' encoding='utf-8'?>
<subtitle num="70" heading="Service Supplied by Water Companies" title_num="20" title_heading="Public Service Commission">
  <chapter num="01" heading="General">
    <regulation prefix="Regulation" num=".01" heading="Authorization of Regulations.">
      <text>The Public Utilities Article, Annotated Code of Maryland, provides that the Commission shall have the power to make such reasonable regulations as it deems necessary to carry out the provisions of this law and any other law relating to the Commission.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Application of Regulations.">
      <paragraph num="A.">
        <text>Application. These regulations apply to any water utility operating within the State, under the jurisdiction of the Commission.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Purpose. These regulations are intended to promote safe and adequate service to the public, to provide standards for uniform and reasonable practices by utilities, and to outline the responsibility of the public in requesting and receiving service from the utilities.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Exemption. If unreasonable hardship to a utility or to a customer results from the application of any of these regulations, application may be made to the Commission for the modification of the regulation or for temporary or permanent exemption from its requirements.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Modification. The adoption of these regulations does not preclude the Commission from altering or amending them, or from making such modifications with respect to their application as may be found necessary to meet exceptional conditions.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Duties Under Other Statutes. These regulations do not relieve any utility from any of its duties under the laws of this State.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Definitions.">
      <paragraph num="A.">
        <text>In this subtitle, the following terms have the meanings indicated.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Terms Defined.</text>
        <paragraph num="(1)">
          <text>“Commission” means the Public Service Commission of Maryland.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>“Customer” means a person, partnership, association, corporation, or governmental agency being provided with water service by a utility.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>“Main” means a water pipe, owned, operated, or maintained by a water company, which is used for the transmission or distribution of water, but does not include “service pipe.”</text>
        </paragraph>
        <paragraph num="(4)">
          <text>“Meter”, without other qualification, means a device or instrument which is used by a utility in measuring a quantity of water for billing purposes.</text>
        </paragraph>
        <paragraph num="(5)">
          <text>“Premises” means a tract of land or real estate, including buildings and other appurtenances on it.</text>
        </paragraph>
        <paragraph num="(6)">
          <text>“Service pipe” means the pipe which runs from the main to the customer's premises.</text>
        </paragraph>
        <paragraph num="(7)">
          <text>“Utility” means a “water company” as defined in Public Utilities Article, §1-101, Annotated Code of Maryland.</text>
        </paragraph>
        <paragraph num="(8)">
          <text>“Water plant” means plant and property owned by a water utility, used in its business operations of providing water service to its customers.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-113, 2-121, 5-101, and 5-308, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
    </annotations>
  </chapter>
  <chapter num="02" heading="Engineering">
    <regulation prefix="Regulation" num=".01" heading="Authorization for Construction.">
      <text>An individual, corporation, firm, partnership, association, company, cooperative, joint stock company or association, or any other form of business enterprise, may not commence any construction of a water system for public use without the prior authorization of the Commission, which shall be granted only upon a finding by the Commission that to do so is in the public interest.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Good Engineering Practice.">
      <text>The water plant of the utility shall be constructed, installed, maintained, and operated in accordance with accepted good engineering practice in the water industry to assure, as far as reasonably possible, continuity of service, uniformity in the quality of service furnished, and the safety of persons and property.</text>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Design and Construction Requirements.">
      <text>The design and construction of the water plant shall conform to the requirements of the Department of the Environment.</text>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Inspection of Water Plant.">
      <text>Each utility shall adopt a program of inspection of its water plant in order to determine the necessity for replacement and repair. The frequency of the various inspections shall be based on the utility's experience and accepted good practice. Each utility shall keep sufficient records to give evidence of compliance with its inspection program.</text>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Mains.">
      <paragraph num="A.">
        <text>Depth of Mains. Water mains should be installed below the frost line or be otherwise protected to minimize the possibility of freezing and shall have not less than 30 inches of cover except where this depth is not feasible due to underground obstructions or rocky or hardpan conditions.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Dead Ends. The utility should design its distribution system so as to avoid dead ends in its mains. When dead ends cannot be avoided, the mains shall be flushed as often as necessary to maintain the proper quality of the water.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Segmentation of System. Valves shall be provided at reasonable intervals in distribution mains so that, in case of breaks or repairs, a minimum number of customers will be affected. When feasible, valves shall be provided in the mains at intervals not to exceed one continuous block or 500 feet, whichever is greater, except where a dead end run is not intended to serve any intervening customers.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Grid Systems. The distribution system should be laid out in a properly segmented grid so that, in case of breaks or repairs, a minimum number of customers will be affected.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Minimum Pipe Sizes. The distribution system shall be of adequate size and designed to maintain the pressures within the range required by COMAR 20.70.07.02. The pipe used in the system should be at least 6 inches in size. In special cases pipes of the sizes listed below may be installed. However, the maximum length from any connecting main at least 6 inches in size should not exceed the following:</text>
        <paragraph num="(1)">
          <text>1-inch ------------------ 150 feet;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>1-1/2-inch --------------300 feet;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>2-inch ------------------ 500 feet.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Service Pipe.">
      <paragraph num="A.">
        <text>Utility's Service Pipe. The utility shall furnish, install, and maintain the following:</text>
        <paragraph num="(1)">
          <text>Corporation stop;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Service pipe from main to curb stop or outlet of outdoor meter setting;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Curb stop; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Curb box.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Curb Stop. Curb stops are for the exclusive use of the utility for control of the water supply to individual customers and should not be located on the customer's property. The control of the water supply by the customer shall be by means of a separate valve, located just inside the building wall.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Customer's Service Pipe. The customer shall be responsible for furnishing, installing, and maintaining the service pipe from the curb stop or outlet of outdoor meter setting to the place of consumption on his premises.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Construction Standards. The service pipe shall be constructed of approved materials and shall be installed and maintained in accordance with accepted good practice and in conformance with applicable codes or governmental regulations.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Cover and Size. All service pipes should be installed below the frost line or be otherwise protected to minimize the possibility of freezing and shall have at least 3 feet of cover. All service pipes shall be at least 3/4 inch inside diameter.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Proximity to Sewer Pipe. A water service pipe may not be laid in the same trench with sewer pipe.</text>
      </paragraph>
      <paragraph num="G.">
        <text>Valve Required. Every service pipe shall be provided with a valve and waste cock on the inside of the foundation wall adjacent to the location where the pipe passes through it, easily accessible, and fully protected from freezing. All pipes in the building shall be laid in such a way that they can be fully drained by the waste cock.</text>
      </paragraph>
      <paragraph num="H.">
        <text>Inspection. If a governmental agency requires an inspection of the customer's plumbing then the utility may not connect the service until it receives a notice from the inspecting agency certifying that the customer's plumbing is satisfactory.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".07" heading="Meters.">
      <paragraph num="A.">
        <text>Meter Installation. The utility shall furnish, install, and maintain all meters. Utilities should make available to customer's plumbers sketches of standard meter installations which show the way in which the customer's portion of the installation should be made.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Meter Location. The meter shall be set at a location designated by the utility on the delivery side of the curb stop, and may be inside the building or it may be outside, near the property line, in an appropriate box or vault. If the customer desires any change in the location or position of the meter, meter box, or vault, after they have been installed, the change in location shall be made by the utility at the expense of the customer.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".08" heading="Fire Protection.">
      <text>Specifications, location, installation, maintenance, and ownership of fire hydrants, mains, and other fire protection facilities are subject to negotiation between the utility and the applicant. Fire hydrants for public fire protection should not be connected to mains smaller than 6 inches.</text>
    </regulation>
    <regulation prefix="Regulation" num=".09" heading="Temporary Service.">
      <text>When the utility renders temporary service to a customer, it may require that the customer bear all the cost of installing and removing the service in excess of any salvage realized.</text>
    </regulation>
    <regulation prefix="Regulation" num=".10" heading="Main Extensions.">
      <paragraph num="A.">
        <text>Applications. Applications for extensions of water mains shall be made in writing.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Ownership of Extensions. Any facilities installed in connection with the extension of mains shall become the property of the utility.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Construction Specifications. The size, type, quality of materials, and their location shall be specified by the utility and the actual construction shall be done by the utility or by a constructing agency acceptable to it.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Calculating Length of Extension. In arriving at the length of main extension necessary to render service at any point, the distance from the point to the nearest main shall be considered along lines of proper construction, due consideration being given to the general layout of the system.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Electing Alternate Route. When the property of the applicant is located adjacent to a street or highway exceeding 70 feet in width, or a freeway, waterway, or railroad right-of-way, the utility may elect to install a main extension on the same side thereof as the property of the applicant, and the estimated cost in the case may be based on such an extension.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Established Grades Required. The utility may not be required to make extensions where grades have not been brought to those established by public authority.</text>
      </paragraph>
      <paragraph num="G.">
        <text>Requirements of Public Authorities. When an extension must comply with an ordinance, regulation, or specification of a public authority, the estimated cost of the extension shall be based upon the facilities needed to comply with the requirements.</text>
      </paragraph>
      <paragraph num="H.">
        <text>Utility's Portion of Extension. The utility shall extend its water mains to serve new customers, other than subdivisions, housing projects, industrial developments, etc., at its own expense, when the cost of the required total length of main extension is not in excess of three times the estimated annual revenue to be derived from the extension, which amount shall be designated the “allowance.”</text>
      </paragraph>
      <paragraph num="I.">
        <text>Estimated Annual Revenue. For the purpose of these regulations, the estimated annual revenue for residential service shall be the utility's average annual revenue per residential customer for the prior calendar year, this average to be effective on April 1st and used until the following April 1st. In unusual cases and for other classes of service, the utility may estimate the annual revenue to be derived in each case.</text>
      </paragraph>
      <paragraph num="J.">
        <text>Customer's Portion of Extension. If the estimated cost of the required total length of main extension is in excess of the “allowance” for the service connections applied for, the applicant for the service shall be required to advance to the utility before construction is commenced that portion of the estimated cost of the extension over and above the “allowance.” The amount of the advance to the utility may not include any costs of increasing the size or capacity of the utility's existing mains or any other facilities used or necessary in connection with the proposed extension, except as provided in §L, of this regulation. If the actual cost of the extension is less than the estimated cost, the utility shall promptly refund to the applicant any overpayment.</text>
      </paragraph>
      <paragraph num="K.">
        <text>Division of Customer's Portion of Extension. When more than one applicant is involved and an advance is required in payment for a main extension in excess of the “allowance,” the amount of the advance shall be divided equally among the applicants, except that some different allocation may be approved by the utility under special conditions.</text>
      </paragraph>
      <paragraph num="L.">
        <text>Extensions to New Subdivisions and other Developments. An applicant for a main extension to serve a new subdivision, tract, housing project, or industrial development shall be required to advance to the utility before construction is commenced the estimated reasonable cost of installation of the mains, from the nearest existing main at least equal in size to the main required to serve the development, including necessary service stubs or service pipelines, fittings, valves, and housings therefor, and including fire hydrants when requested by the applicant or when required by public authority, exclusive of meters. If additional facilities are required specifically to provide supply, storage, or pressure exclusively for the service requested, the cost of the facilities may be included in the advance upon approval by the Commission.</text>
      </paragraph>
      <paragraph num="M.">
        <text>Basis For Refunds. For each new customer connected to an extension on which the utility holds refundable deposits, the utility shall refund three times the estimated annual revenue to be derived from the customer. Refunds shall be made within 90 days after the new customer's service is connected and shall be made to the depositors who advanced the money for the extension. If more than one depositor is entitled to receive a refund, the total amount shall be divided in proportion to the amount of the unrefunded advance of each depositor.</text>
      </paragraph>
      <paragraph num="N.">
        <text>Disposition of Advances. Advances which may be required from applicants in payment for extensions will be held by the utility without interest. Refunds shall be made in accordance with these regulations and no depositor will have refunded to him an amount in excess of the amount of his advance. Any amount remaining unrefunded at the end of 10 years from the date the advance was received by the utility shall be retained by the utility and transferred to the Contributions in Aid of Construction account.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .03 amended effective May 14, 2001 (28:9 Md. R. 889)</annotation>
    </annotations>
  </chapter>
  <chapter num="03" heading="Records and Reports">
    <regulation prefix="Regulation" num=".01" heading="Availability of Records.">
      <text>All records required by these regulations or necessary for the administration of them shall be made available for examination by the Commission or its authorized representatives.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Retention of Records.">
      <text>Unless otherwise specified by the Commission, all records required by these regulations shall be preserved for the period of time specified in the current edition of the National Association of Regulatory Utilities Commissioners' publication, “Regulations to Govern the Preservation of Records of Electric, Gas and Water Utilities”.</text>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Tariff.">
      <text>Each utility shall file with the Commission a copy of its tariff which shall include:</text>
      <paragraph num="A.">
        <text>Rates. Each schedule of rates for service.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Rules. The utility's rules, or terms and conditions, describing the utility's policies and practices in rendering service.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Information to be Filed With the Commission.">
      <paragraph num="A.">
        <text>Special Contracts. Each utility shall file with the Commission a copy of each contract for service not covered by the utility's filed tariff.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Installation Rules. Each utility shall file with the Commission a copy of the utility's rules, if any, designed by the utility for the use of engineers, architects, contractors, etc., covering service installations.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Bill Forms. Each utility shall file with the Commission a sample of each type of customer bill form, which shall include the information normally shown on a customer's bill for service.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Map of System. Each utility shall file with the Commission a map showing the utility's water system. This map shall be revised annually unless no revision is necessary, to reflect a material change in the items listed below. The map on file should reflect the current status of the following items:</text>
        <paragraph num="(1)">
          <text>Location of pumping stations, treatment plants, and sources of supply;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Storage facilities;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Mains by size;</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Location of valves and fire hydrants;</text>
        </paragraph>
        <paragraph num="(5)">
          <text>Service area;</text>
        </paragraph>
        <paragraph num="(6)">
          <text>Names of all communities (post offices) served.</text>
        </paragraph>
      </paragraph>
      <paragraph num="E.">
        <text>Persons to Contact. Each utility shall file with the Commission the name, title, address, and telephone number of the person who should be contacted in connection with the following areas of operation, and shall notify the Commission promptly of any changes:</text>
        <paragraph num="(1)">
          <text>Management;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Customer relations (complaints);</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Engineering;</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Meter tests and repairs; and</text>
        </paragraph>
        <paragraph num="(5)">
          <text>Emergencies during non-office hours.</text>
        </paragraph>
      </paragraph>
      <paragraph num="F.">
        <text>Fatal Accident Notice. In the event of a fatal accident, prompt notice shall be given to the Commission by telephone.</text>
      </paragraph>
      <paragraph num="G.">
        <text>Accident Notice. Each utility shall file with the Commission an “Accident Notice” report, on forms provided by the Commission, within 30 days after the end of any month during which an accident occurred.</text>
      </paragraph>
      <paragraph num="H.">
        <text>Construction Reports. Each utility shall file with the Commission a notification of all proposed important additions to plant, the construction of which was started by the utility during the preceding month. For the purpose of this regulation, an important addition to plant means a single project involving the expenditure of at least $50,000, or an amount equivalent to at least 10 percent of the total water plant in service, whichever is less. The notification shall be submitted, in duplicate, on forms supplied by the Commission. One copy will be numbered for identification and returned to the utility to be completed and returned to the Commission when the construction of the project has been completed to the extent that the facility was placed in operation during the preceding month.</text>
      </paragraph>
      <paragraph num="I.">
        <text>Location of Records. Each utility shall notify the Commission of the location at which it keeps the various classes of records required by these regulations.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, 5-302, and 6-201—6-210, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .04D, F amended effective March 18, 2013 (40:5 Md. R. 412)</annotation>
    </annotations>
  </chapter>
  <chapter num="04" heading="Customer Relations">
    <regulation prefix="Regulation" num=".01" heading="Applications For Service.">
      <paragraph num="A.">
        <text>Applications. All applications for water service should be made in writing.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Application Constitutes Contract. The accepted application shall constitute a contract between the company and the applicant, obligating the applicant to pay for water service in accordance with the utility's tariff currently on file with the Commission, and to comply with this subtitle.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Termination of Service. When a customer desires to have his service terminated, he shall notify the utility and the notification should be in writing.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Information For Customers.">
      <paragraph num="A.">
        <text>System Maps or Records. Each utility shall maintain up-to-date maps, plans, or records of its entire transmission and distribution systems, with such other information as may be necessary to enable the utility to advise prospective customers and others entitled to the information, as to the facilities available for serving customers within its service area.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Selecting Rate Schedule. Each utility shall assist the customer or prospective customer in selecting the most economical rate schedule.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Notifying Customers. Each utility shall notify customers affected by a change in rates or schedule classification.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Tariff Notice. Each utility shall post a notice in a conspicuous place in each office of the utility where applications for service are received, informing the public that a copy of its tariff, as filed with the Commission, is available for inspection.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Meter Reading Instruction. Upon request, each utility shall inform its customers as to the method of reading meters.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Other Information. Each utility shall furnish such additional information as the customer may reasonably request.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Customer Deposits.">
      <text>Each utility may require from a customer a deposit to be applied against any unpaid balance due the utility for service at the time service is terminated, in accordance with the provisions of COMAR 20.30.</text>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Bill Forms.">
      <text>The bill forms shall show:</text>
      <paragraph num="A.">
        <text>Meter Reading. The reading of the meter at the end of the period for which the bill is rendered.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Meter Reading Date. The date on which the meter was read.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Units Used. The number and kind of units metered.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Rate Schedule. The applicable rate schedule, or identification of the applicable rate schedule. If the actual rates are not shown, the bill shall carry a statement to the effect that, on request, the applicable rate schedule will be made available for examination.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Amount. The gross or net amount, or both, of the bill.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Payment Date. The date by which the customer must pay the bill in order to benefit from a discount or to avoid any penalty.</text>
      </paragraph>
      <paragraph num="G.">
        <text>Estimated Bill. A distinct marking to identify an estimated bill.</text>
      </paragraph>
      <paragraph num="H.">
        <text>Additional Billing Information. Any conversions from meter reading units to billing units or any calculations to determine billing units from recording or other devices, or any other factors used in determining the bill. In lieu of this information on the bill, a statement shall be on the bill advising that the information can be obtained by contacting the utility's principal office.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Billing Records.">
      <text>The utility shall retain customer billing records for the length of time necessary to permit the utility to comply with Regulation .06 of this chapter, but not less than 3 years.</text>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Adjustment of Bills.">
      <paragraph num="A.">
        <text>Fast Meters. If a meter is tested and found to have over-registered more than 2 percent, the utility shall recalculate the bills for service of the last customer of record receiving service through the meter and shall make a refund if the amount of the adjustment exceeds $1. The refund shall be for the period that the customer received service through the meter, but for not more than the periods established below:</text>
        <paragraph num="(1)">
          <text>Known Date of Error. If the date on which the error first developed or occurred can be established, the bills for service shall be recalculated from that time.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Unknown Date of Error. If the time at which the error first developed or occurred cannot be established, it shall be assumed that the over-registration existed for a period of 3 years or a period equal to one-half of the time since the meter was last tested, whichever is less.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Slow Meters. Whenever a meter is found to be more than 2 percent slow, the utility may bill the customer one-half of the unbilled error for a period of 12 months, unless the meter has been tested within that 12-month period, in which event the utility may bill the customer one-half the unbilled error for the period since the meter was last tested. If the amount of under-registration is less than $5, the utility may not adjust the bill.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Accuracy Calculations. Billing adjustments due to fast or slow meters shall be calculated on the basis that the meter should be 100 percent accurate. For the purpose of billing adjustment, the error in registration of the meter shall be calculated and applied as specified in COMAR 20.70.06.04.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Overcharge Adjustment. When a customer has been overcharged as a result of incorrect reading of the meter, incorrect application of the rate schedule, incorrect connection of the meter, or other similar reasons, the amount of the overcharge shall be refunded or credited to the customer, except for an overcharge resulting from an incorrect reading of the meter where the amount will automatically be corrected in a subsequent billing based on a correct meter reading.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Undercharge Adjustment. When a customer has been undercharged as a result of an incorrect reading of the meter, incorrect application of the rate schedule, incorrect connection of the meter, stopped meter, or other similar reasons, the amount of the undercharge may be billed to the customer. However, the utility may deny service for non-payment only for that portion of the undercharge applicable to the 4 months immediately before the discovery of the error, unless otherwise authorized by the Commission.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".07" heading="Denial of Service Without Notice.">
      <paragraph num="A.">
        <text>The utility may discontinue service without notice for any of the following reasons, and service may not be restored until the cause for the disconnection has been corrected:</text>
        <paragraph num="(1)">
          <text>Hazardous Condition. For a condition on the customer's premises determined by the utility to be hazardous.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Adverse Effect on Service. Customer's use of equipment in such a manner as to adversely affect the utility's equipment or the utility's service to others.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Tampering with Utility Property. Customer's tampering with equipment furnished and owned by the utility.</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Unauthorized Use of Service. Customer's unauthorized use of service by any method, including diversion of water around a meter.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>A reasonable charge may be made for restoring service disconnected under this regulation, and customers who have been disconnected for unauthorized use of water or for damaging the utility's equipment may be charged the actual cost of reconnecting the service.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".08" heading="Denial of Service Requiring Notice.">
      <paragraph num="A.">
        <text>The utility may deny service for any of the following reasons provided it has notified the customer of its intent to deny service and has allowed the customer a reasonable time in which to remove the cause for denial:</text>
        <paragraph num="(1)">
          <text>Non-Compliance with Regulations. For violation of or non-compliance with this subtitle, or for violation of or non-compliance with the utility's rules on file with the Commission.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Failure on Contractual Obligations. For failure of the customer to fulfill his contractual obligations for service or facilities subject to regulation by the Commission.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Refusal of Access. For failure of the customer to permit the utility to have reasonable access to its equipment.</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Non-Payment of Bill. For non-payment of a bill for service, provided that the utility has made a reasonable attempt to effect collection and has given the customer written notice that he has at least 5 days, excluding Sundays and holidays, in which to make settlement on his account or have his service denied. Except in cases where a prior attempt to gain access has been unsuccessful or where a prior promise to pay has not been kept, the utility may not deny service on the day preceding any day on which it is not prepared to accept payment of the amount due and to reconnect service.</text>
        </paragraph>
        <paragraph num="(5)">
          <text>Failure to Provide Deposit. For failure of the customer to provide the utility with a deposit as authorized in Regulation .03 of this chapter.</text>
        </paragraph>
        <paragraph num="(6)">
          <text>Failure to Comply with Service Conditions. For failure of the customer to furnish any service equipment, permits, certificates, or rights-of-way, as shall have been specified by the utility as a condition to obtaining service, or if the equipment or permissions are withdrawn or terminated.</text>
        </paragraph>
        <paragraph num="(7)">
          <text>Waste of Water. For willful waste of water by the customer.</text>
        </paragraph>
        <paragraph num="(8)">
          <text>Restrictions on Use of Water. For failure of the customer to comply with reasonable restrictions on the use of water, as imposed under COMAR 20.70.07.05, provided that notice has been given to the customer and that written notice has been furnished to the Commission.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>When water has been turned off for any of the reasons specified in this regulation, a charge may be made for restoring service. This reconnection charge may not exceed $2 for restoring service to a residential or commercial customer, unless the utility has filed a different charge with the Commission.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".09" heading="Insufficient Reasons for Denial of Service.">
      <paragraph num="A.">
        <text>The following may not constitute sufficient cause for refusal of service to a present or prospective customer:</text>
        <paragraph num="(1)">
          <text>Failure of a prior customer to pay for service at the premises to be served;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Failure to pay for merchandise purchased from the utility;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Failure to pay for a public utility service other than water service;</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Failure to pay for a different class of service;</text>
        </paragraph>
        <paragraph num="(5)">
          <text>Failure to pay the bill of another customer as guarantor of the customer;</text>
        </paragraph>
        <paragraph num="(6)">
          <text>Failure to pay the undercharge for the period in excess of 4 months as described in Regulation .06E of this chapter; or</text>
        </paragraph>
        <paragraph num="(7)">
          <text>Failure to pay an outstanding bill that is over 7 years old, unless the:</text>
          <paragraph num="(a)">
            <text>Customer signed an agreement to pay the outstanding bill before the expiration of this period;</text>
          </paragraph>
          <paragraph num="(b)">
            <text>Outstanding bill is for service obtained by the customer by means of tampering with equipment furnished and owned by the utility or by unauthorized use of service by any method; or</text>
          </paragraph>
          <paragraph num="(c)">
            <text>Outstanding bill is for service obtained by the customer by means of an application made:</text>
            <paragraph num="(i)">
              <text>In a fictitious name,</text>
            </paragraph>
            <paragraph num="(ii)">
              <text>In the name of an individual who is not an occupant of the dwelling unit, without disclosure of the individual's actual address,</text>
            </paragraph>
            <paragraph num="(iii)">
              <text>In the name of a third party without disclosing that fact or without bona fide authority from the third party, or</text>
            </paragraph>
            <paragraph num="(iv)">
              <text>Without disclosure of a material fact or by misrepresentation of a material fact.</text>
            </paragraph>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>This regulation applies to both residential and nonresidential classes of service.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".10" heading="Right of Access.">
      <text>The authorized agents of the utility shall have the right of access to the premises supplied with water, at reasonable hours, for the purpose of reading meters, examining fixtures and pipes, observing the manner of using water, and for any other purpose which is proper and necessary in the conduct of the utility's business.</text>
    </regulation>
    <regulation prefix="Regulation" num=".11" heading="Waste of Water.">
      <paragraph num="A.">
        <text>Leakage Control. The customer should maintain his service pipe and all piping and fixtures on or in the building so that any loss of water through leakage is kept to a reasonably small amount. If the leakage becomes excessive, it may be treated as a willful waste of water.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Willful Waste. Unnecessary or excessive use of water may be treated as a willful waste of water.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".12" heading="Investigation of Complaints.">
      <text>The utility shall investigate promptly and thoroughly any complaint concerning its charges, practices, facilities, or service.</text>
    </regulation>
    <regulation prefix="Regulation" num=".13" heading="Records of Complaints.">
      <text>The utility shall keep such records of customer complaints as will enable it to review and analyze its procedures and actions as an aid in rendering improved service.</text>
    </regulation>
    <regulation prefix="Regulation" num=".14" heading="Identification of Employees.">
      <text>Every employee, whose duties require him to enter the customer's premises, should wear a distinguishing uniform, or other insignia identifying him as an employee of the utility. The minimum requirement shall be a badge or identification card, carried on his person, certifying him as an employee of the utility authorized to enter the premises to perform necessary inspections or work.</text>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-113, 2-121, and 5-101, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulations .03 and .06A amended effective January 23, 1981 (8:2 Md. R. 117)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .09 amended effective May 10, 1993 (20:9 Md. R. 780)</annotation>
    </annotations>
  </chapter>
  <chapter num="05" heading="Meter Requirements">
    <regulation prefix="Regulation" num=".01" heading="Metering of Water.">
      <paragraph num="A.">
        <text>Customer Use. Unless the authorized tariff provides for flat-rate billing for the customer class, all water sold by a utility shall be on the basis of meter measurement.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Utility Use. Wherever practicable, the use of water within the utility itself, or by administrative units associated with it, shall be metered.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Meter Reading Records.">
      <text>The meter reading sheets, cards, or records from which bills are prepared shall show the following information:</text>
      <paragraph num="A.">
        <text>Customer's name, address, and rate schedule;</text>
      </paragraph>
      <paragraph num="B.">
        <text>Identifying number or description of the meter, or both;</text>
      </paragraph>
      <paragraph num="C.">
        <text>Meter readings;</text>
      </paragraph>
      <paragraph num="D.">
        <text>Date of meter reading;</text>
      </paragraph>
      <paragraph num="E.">
        <text>If the reading has been estimated; and</text>
      </paragraph>
      <paragraph num="F.">
        <text>Any applicable multiplier or constant.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Inventory Records.">
      <text>Each utility shall maintain records of each meter or associated metering device, or both, which will identify each item as to its design, capacity, and application. The identifying information may include, as applicable: manufacturer, number, type, size, capacity, multiplier and constants.</text>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="History Records.">
      <text>Each utility shall maintain records for each meter or associated metering device, or both, which shall show the dates of installation and removal from service, together with the location.</text>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Meter Test Records.">
      <paragraph num="A.">
        <text>Each utility shall maintain test records for each meter, which shall include the following:</text>
        <paragraph num="(1)">
          <text>The date and reason for the test;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>The reading of the meter before making the test;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>The accuracy “as found” at each rate of flow; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>The accuracy “as left” at each rate of flow.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>If the test of the meter is made by using a standard meter, then the utility shall retain all data taken at the time of the test in sufficiently complete form to permit the convenient checking of the test methods and the calculations.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Meter Reading Interval.">
      <text>Meters shall be read at regular intervals as specified in the utility's tariff.</text>
    </regulation>
    <regulation prefix="Regulation" num=".07" heading="Condition of Meter.">
      <text>A meter may not be installed which is mechanically defective, has an incorrect correction factor, or which does not meet the requirements of COMAR 20.70.06.05. The capacity of the meter and the index mechanism should be consistent with the water requirements of customer.</text>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .01A amended effective May 14, 2001 (28:9 Md. R. 889)</annotation>
    </annotations>
  </chapter>
  <chapter num="06" heading="Inspections and Tests">
    <regulation prefix="Regulation" num=".01" heading="Meter Shop.">
      <paragraph num="A.">
        <text>Meter Shop. Each utility shall maintain or designate a meter shop where meters may be inspected, tested, and repaired. The shop shall be open for inspection by authorized representatives of the Commission at all reasonable times, and the facilities and equipment, as well as the methods of making measurements and tests, shall be subject to the approval of the Commission.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Accuracy of Test Equipment. The accuracy of the test equipment and of the test procedures shall be such that the overall error will not exceed 0.3 of 1 percent.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Working Standards.">
      <paragraph num="A.">
        <text>Requirements. Each meter shop maintained or designated by a utility shall have at least one calibrated tank for volumetric measurement or a tank mounted upon scales for weight measurement. The tank shall be of sufficient capacity to insure an acceptable determination of the accuracy of the utilities' meters.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Calibration. Working standards shall be checked periodically (see Regulation .09B of this chapter) by comparison with approved secondary standards.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Certificates. Each standard shall be accompanied at all times by a certificate or calibration card, duly signed and dated, on which are recorded the corrections required to compensate for errors found at the customary test points at the time of the last previous test.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Care in Handling. Extreme care shall be exercised in the use and handling of standards to assure that their accuracy is not disturbed.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Test Procedures.">
      <paragraph num="A.">
        <text>Procedure. The following procedures shall apply to the testing and adjusting of meters and associated devices:</text>
        <paragraph num="(1)">
          <text>General. The test of any unit of metering equipment shall consist of a comparison of its accuracy with the accuracy of a standard.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Adjusted to Zero. All meters and associated devices, when tested, shall be adjusted as closely as practicable to the condition of zero error.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Use of Tolerances. All tolerances are to be interpreted as maximum permissible variations from the condition of zero error. In making adjustments, no advantage of the prescribed tolerance limits may be taken.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Test Flows. For determination of minimum test flow and other normal test flows, the Commission will use as a guide the appropriate standard specifications of the American Water Works Association for the various types of meters. These flows for displacement type cold water meters are as follows:</text>
      </paragraph>
      <paragraph num="C.">
        <text>Tests to Determine Error in Registration. Meters shall be tested at the following three flows:</text>
        <paragraph num="(1)">
          <text>Minimum test flow;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Approximately 10 percent of the maximum normal flow;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Approximately 50 percent of the maximum normal flow, or at the maximum flow available at normal system pressure.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Meter Registration.">
      <paragraph num="A.">
        <text>Pre-Installation Tolerances. A meter may not be placed in service if it registers less than 90 percent of the water passed through it at the minimum test flow or over-registers or under- registers more than 1-1/2 percent at the other test flows.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Calculation of Error. The percentage by which the correct registration varies from the meter registration is derived by stopping the meter test hand at the starting point and then determining the percentage variation in registration as indicated by the working standard. The formula for determining the percentage error in registration is:</text>
      </paragraph>
      <paragraph num="C.">
        <text>Error in Registration for Billing Adjustments. The error in registration of a meter for billing adjustments shall be the algebraic average of the error in registration at the following two rates of flow:</text>
        <paragraph num="(1)">
          <text>Approximately 10 percent of maximum normal flow;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Approximately 50 percent of maximum normal flow, or at the maximum flow available at normal system pressure.</text>
        </paragraph>
      </paragraph>
      <paragraph num="D.">
        <text>Application of Error for Billing Adjustments. The meter error derived in §C, of this regulation, shall be used to calculate the correct consumption of water by applying the derived error in registration to the volume of water consumption indicated by the meter. If the meter is fast then the volume of water indicated by the meter registration shall be reduced by applying the calculated error in registration. If the meter is slow then the volume of water indicated by the meter registration shall be increased by applying the calculated error in registration.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Pre-Installation Inspections and Tests.">
      <paragraph num="A.">
        <text>Approval. A meter may not be placed in service unless:</text>
        <paragraph num="(1)">
          <text>Its type and design first has been approved by the Commission;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>It has been inspected and tested by the utility, or has been certified by the manufacturer to be correct;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Its registration is within the tolerances specified in Regulation .04A of this chapter; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>It has been sealed by the utility.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Re-Installation. When any meter is removed from service it shall be repaired if necessary so that it conforms to the registration tolerances specified in Regulation .04A before being placed in service again.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Request Tests.">
      <paragraph num="A.">
        <text>Request For Test. Upon request by a customer and at no charge, the utility shall make a test of the accuracy of registration of the meter serving the customer, provided that these tests need not be made more frequently than once in 24 months.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Customer May Observe. The customer, or his representative, may be present when the meter is tested.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Report to Customer. A report of the results of the test shall be made to the customer within a reasonable time after the completion of the test, and a record of the report, together with a complete record of the test, shall be kept on file at the office of the utility for at least 3 years.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".07" heading="Referee Tests.">
      <paragraph num="A.">
        <text>Application For Test. Upon written application to the Commission by a customer or a utility, a test will be made of the customer's meter as soon as practicable by a representative of the Commission.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Deposit For Test. The application shall be accompanied by a deposit as indicated: Water meter—$10.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Notice to Utility. On receipt of a request from a customer the Commission will notify the utility and the utility may not knowingly remove or adjust the meter until instructed by the Commission. The utility shall furnish to the Commission's representative such reasonable assistance as may be required to make the test.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Customer May Observe. The customer, or his representative, may be present when the meter is tested.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Report to Customer. A written report of the results of the test will be sent to the customer and to the utility.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Disposition of Deposit. If the meter is found to over-register more than 2 percent, calculated in accordance with Regulation .04C, the deposit shall be refunded by the Commission and the utility billed the amount of the deposit. Otherwise the deposit will be retained and disposed of according to law.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".08" heading="As Found Tests.">
      <text>Each meter shall be tested before the meter is adjusted or repaired.</text>
    </regulation>
    <regulation prefix="Regulation" num=".09" heading="Periodic Tests.">
      <text>Each utility shall make periodic tests of meters and standards to assure their accuracy. These tests shall be scheduled within the calendar year, or earlier, when the interval is stated in years, or within the calendar month, or earlier, when the interval is stated in months. The basic periodic test interval may not be longer than provided for in the following schedule: (Note: Maintenance programs suggested by manufacturers of the following meters and devices should be carefully followed.)</text>
      <paragraph num="A.">
        <text>Meters.</text>
        <paragraph num="(1)">
          <text>5/8 in. ------------------------------10 years</text>
        </paragraph>
        <paragraph num="(2)">
          <text>3/4 in. ------------------------------ 8 years</text>
        </paragraph>
        <paragraph num="(3)">
          <text>1-in. -------------------------------- 6 years</text>
        </paragraph>
        <paragraph num="(4)">
          <text>1-1/2 in. and 2-in. ------------------4 years</text>
        </paragraph>
        <paragraph num="(5)">
          <text>3-in. and 4-in. ----------------------2 years</text>
        </paragraph>
        <paragraph num="(6)">
          <text>6-in. and larger --------------------12 months</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Working Standards.</text>
        <paragraph num="(1)">
          <text>Volumetric tank ---------------------- 5 years</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Scales ------------------------------ 12 months</text>
        </paragraph>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .07B amended effective April 13, 1992 (19:7 Md. R. 747)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .08 amended effective May 14, 2001 (28:9 Md. R. 889)</annotation>
    </annotations>
  </chapter>
  <chapter num="07" heading="Quality of Service">
    <regulation prefix="Regulation" num=".01" heading="Quality of Water.">
      <paragraph num="A.">
        <text>General. Each utility shall provide water that is potable, and, insofar as practicable, free from objectionable odors, taste, color, and turbidity. Each utility shall have a permit as required by the health laws of the State, and shall comply with the laws and regulations of the Department of the Environment and local departments of health.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Water Supply. The source of supply shall be:</text>
        <paragraph num="(1)">
          <text>Free from pollution, unless the water is subsequently purified by treatment;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Reasonably adequate to provide a continuous supply of water; and</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Of such quality as to meet the standards of the Department of the Environment.</text>
        </paragraph>
      </paragraph>
      <paragraph num="C.">
        <text>Operation of Supply System.</text>
        <paragraph num="(1)">
          <text>Free of Sanitary Defects. The water supply system, including the source of supply plant, pumping plant, water treatment plant, transmission plant, and distribution plant, shall be free from sanitary defects.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Cross Connections Restricted. Any physical connection between the distribution system of a public water supply and that of any other water supply shall comply with the regulations of the Department of the Environment.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Disinfection of Facilities. All new mains, pumps, tanks, wells, and other facilities for handling potable water, and insofar as practicable, repaired mains and other facilities, shall be thoroughly disinfected before being connected to the system. The method of disinfection shall be as approved by the Department of the Environment.</text>
        </paragraph>
      </paragraph>
      <paragraph num="D.">
        <text>Testing of Water. Each utility shall cooperate with the Department of the Environment in the conduct of its water quality sampling program.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Pressure Limits.">
      <paragraph num="A.">
        <text>Allowable Pressures. Under normal conditions of use of water, the pressure at a customer's service connection shall be:</text>
        <paragraph num="(1)">
          <text>Not less than 25 psig; and</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Not more than 125 psig.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Exceptions to Pressure Requirements. Pressure outside the limits specified will not be considered a violation when the variations:</text>
        <paragraph num="(1)">
          <text>Arise from the action of the elements;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Are infrequent fluctuations not exceeding 5 minutes' duration;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Arise from service interruptions;</text>
        </paragraph>
        <paragraph num="(4)">
          <text>Are from causes beyond the control of the utility; or</text>
        </paragraph>
        <paragraph num="(5)">
          <text>Arise from variations in service elevations which are local and which can be controlled in a satisfactory manner.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Pressure Surveys and Records.">
      <paragraph num="A.">
        <text>Pressure Gauge. Each utility having more than 100 customers shall have at least one portable recording pressure gauge.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Point of Measurement. Pressure measurements should be made at the customer's service connection. If no outlet is available at this point, the measurement may be made at the nearest available outlet, making due allowance for any pressure differential between the point of customer's service connection (usually the curb or property line) and the point of measurement.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Survey by Utility. Each utility shall make a sufficient number of pressure measurements in order to determine if pressures throughout the system are in compliance with the requirements of Regulation .02.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Survey Records. Pressure records obtained under §C of this regulation shall be retained by the utility for at least 2 years and shall be available for inspection by the Commission's representatives at all times. Notation of each pressure record shall indicate the following:</text>
        <paragraph num="(1)">
          <text>The location where the pressure was taken; and</text>
        </paragraph>
        <paragraph num="(2)">
          <text>The time and date of the test.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Interruption of Service.">
      <paragraph num="A.">
        <text>Endeavor to Avoid Interruptions. Each utility shall make reasonable efforts to avoid interruptions of service but when interruptions occur, service shall be re-established within the shortest time practicable that is consistent with safety.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Notification to Commission. Each utility shall notify the Commission by telephone or telegraph of any interruption to the service of a major portion of its distribution system when the interruption lasts for more than 6 hours.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Notification to Public Officials. If an interruption affects the service to any public fire protection device, the utility shall immediately notify the public official responsible for fire protection.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Standby Pumping Equipment. When the system pressure is provided through mechanical means, emergency standby pumping equipment or other adequate facilities shall be available to maintain pressure in the mains in the event of a failure of the primary pumping facilities.</text>
      </paragraph>
      <paragraph num="E.">
        <text>Planned Interruptions. Planned interruptions shall be made at a time that will not cause unreasonable inconvenience to customers and shall be preceded, if feasible, by adequate notice to those who will be affected.</text>
      </paragraph>
      <paragraph num="F.">
        <text>Record of Interruptions. Each utility shall keep records of interruptions of service on its system and shall make an analysis of the records for the purpose of determining steps to be taken to prevent recurrence of the interruptions. The records should include the following information concerning the interruptions:</text>
        <paragraph num="(1)">
          <text>Cause;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>Date and time; and</text>
        </paragraph>
        <paragraph num="(3)">
          <text>Duration.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Restrictions on the Use of Water.">
      <paragraph num="A.">
        <text>Restrictions on Outdoor Use. The utility may impose reasonable restrictions on the outdoor use of water during periods of shortage of supply, excessive demand, or other difficulty which jeopardizes the supply of water to any group of customers.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Restrictions on Large Use Customers. The utility may impose reasonable restrictions on the use of water by customers who use large quantities of water and thereby create conditions which prevent the company from supplying satisfactory service to that customer, or to other customers.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Notification. If a utility finds that it is necessary to restrict the use of water, it shall notify its customers, and give the Commission written notice, before the restriction becomes effective. The notifications shall specify:</text>
        <paragraph num="(1)">
          <text>The reason for the restriction;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>The nature and extent of the restriction (for example, on outdoor use of water, use by certain classes of customers, and so on);</text>
        </paragraph>
        <paragraph num="(3)">
          <text>The date the restriction is to go into effect; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>The probable date of termination of the restriction.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
      <annotation type="History" subtype="Administrative History">Regulation .01 amended effective May 14, 2001 (28:9 Md. R. 889)</annotation>
    </annotations>
  </chapter>
  <chapter num="08" heading="Safety">
    <regulation prefix="Regulation" num=".01" heading="Protective Measures.">
      <paragraph num="A.">
        <text>Exercise Reasonable Care. Each utility shall exercise reasonable care to reduce the hazards to which its employees, its customers, and the general public may be subjected.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Investigation by Commission. The utility shall give reasonable assistance to the Commission in the investigation of the cause of accidents and in the determination of suitable means of preventing accidents.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Record of Accidents. Each utility shall maintain a summary of all reportable accidents arising from its operations.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Safety Program.">
      <paragraph num="A.">
        <text>Adopt Safety Program. Each utility shall adopt and execute a safety program, fitted to the size and type of its operations.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Use Suitable Tools and Equipment. Each utility should require its employees to use suitable tools and equipment in order that they may perform their work in a safe manner.</text>
      </paragraph>
      <paragraph num="C.">
        <text>Promote Safe Work Methods. Each utility should require its employees to use safe methods in performing their work.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Instruct in Artificial Respiration. Each utility should require that its employees who, in the course of their work, are subject to the hazards of asphyxiation, electrical shock, or drowning, be properly instructed in accepted methods of artificial respiration.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utility Companies Article, §§2-113, 2-121, 5-101, and 5-303, Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: July 1, 1968 (Order No. 57171)</annotation>
    </annotations>
  </chapter>
  <chapter num="09" heading="Establishing Rates for Small Water Companies">
    <regulation prefix="Regulation" num=".01" heading="Scope.">
      <text>This chapter applies to small water companies whose gross annual revenues for the most recent calendar year do not exceed $350,000.</text>
    </regulation>
    <regulation prefix="Regulation" num=".02" heading="Definitions.">
      <paragraph num="A.">
        <text>In this chapter, the following terms have the meanings indicated.</text>
      </paragraph>
      <paragraph num="B.">
        <text>Terms Defined.</text>
        <paragraph num="(1)">
          <text>“Applicant” means a small water company seeking a change in rates or rate design under the provisions of this chapter.</text>
        </paragraph>
        <paragraph num="(2)">
          <text>“Small water company” means a water company as defined in Public Utilities Article, §1-101, Annotated Code of Maryland eligible to seek a change in rates or rate design under the provisions of this chapter.</text>
        </paragraph>
        <paragraph num="(3)">
          <text>“Staff-assisted rate case” means a proceeding by which a small water company may, under the provisions of this chapter, seek a rate increase or change in rate design.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".03" heading="Waiver.">
      <text>Upon application by an applicant, the Commission may waive the application of a regulation in this chapter to an applicant that demonstrates good cause.</text>
    </regulation>
    <regulation prefix="Regulation" num=".04" heading="Development of a Staff–Assisted Rate Case for a Small Water Company.">
      <paragraph num="A.">
        <text>A Staff-assisted rate case shall be developed upon the submission of the following documents to the Commission’s Executive Director:</text>
        <paragraph num="(1)">
          <text>A letter requesting development of a staff-assisted rate case; and</text>
        </paragraph>
        <paragraph num="(2)">
          <text>A completed staff-assisted rate case application for a small water company including all necessary attachments or exhibits.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Upon receipt of all completed materials listed in §A of this regulation, the Commission’s technical staff shall send the applicant and the Maryland Office of People’s Counsel written notice that the application has been received, and the staff-assisted rate case shall be deemed submitted.</text>
      </paragraph>
      <paragraph num="C.">
        <text>If the application is not complete:</text>
        <paragraph num="(1)">
          <text>Technical staff shall give notice to the applicant in writing of any deficiencies;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>The applicant shall have a reasonable opportunity, not to exceed 90 business days, after receipt of the notice to file information to remedy the indicated deficiencies; and</text>
        </paragraph>
        <paragraph num="(3)">
          <text>If deficiencies are not resolved in a timely manner, the applicant shall be informed in writing that the application for a staff-assisted rate case has been rejected.</text>
        </paragraph>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".05" heading="Staff-Assisted Rate Case Procedures for a Small Water Company.">
      <paragraph num="A.">
        <text>The procedures for a staff-assisted rate case are:</text>
        <paragraph num="(1)">
          <text>The Commission’s Accounting Investigations Division shall audit the small water company’s books and records, including those relating to depreciation;</text>
        </paragraph>
        <paragraph num="(2)">
          <text>The Commission’s Engineering Division shall inspect the small water company’s facilities, provide a description of the various system components, evaluate the condition of the various system components, and evaluate the adequacy of service being provided;</text>
        </paragraph>
        <paragraph num="(3)">
          <text>The Commission’s Telecommunications, Gas and Water Division shall establish a rate of return applicable to rates to be proposed for the applicant based on the work of the Accounting Investigations Division and the Engineering Division; and</text>
        </paragraph>
        <paragraph num="(4)">
          <text>The work of the Commission’s technical staff shall be coordinated by the Office of Staff Counsel which, upon completion of all required work needed to propose rates, shall compile a report containing technical staff’s work papers, findings, and recommendation as to the small water company’s revenue requirement and rates which shall be forwarded to the Executive Director.</text>
        </paragraph>
      </paragraph>
      <paragraph num="B.">
        <text>Upon approval from the Executive Director, technical staff’s report shall be sent to the applicant for its review and acceptance. Following the applicant’s acceptance, the report shall be sent to the Maryland Office of People’s Counsel and any known affected community association whose members are served by the applicant for the purpose of determining whether the proposed rates contained in technical staff’s report can be agreed upon.</text>
      </paragraph>
    </regulation>
    <regulation prefix="Regulation" num=".06" heading="Stipulation and Settlement.">
      <paragraph num="A.">
        <text>The applicant, the Maryland Office of People’s Counsel, the Commission’s technical staff, and any other interested persons shall engage in negotiations for the purpose of reaching a settlement agreement.</text>
      </paragraph>
      <paragraph num="B.">
        <text>If an agreement is reached, it shall be reduced to writing in the form of a stipulation and settlement with such exhibits as are appropriate.</text>
      </paragraph>
      <paragraph num="C.">
        <text>A stipulation and settlement derived under §A of this regulation shall be filed with the Commission together with a summary letter from technical staff and the technical staff report.</text>
      </paragraph>
      <paragraph num="D.">
        <text>Upon filing as described by §C of this regulation, the stipulation and settlement shall be assigned a case number and treated as any other case which is filed with the Commission.</text>
      </paragraph>
      <paragraph num="E.">
        <text>If no agreement is reached under §A of this regulation, the applicant may file a request for a revision of its retail rates under Public Utilities Article, §§4-203(a) and 4-204, Annotated Code of Maryland.</text>
      </paragraph>
    </regulation>
    <annotations>
      <annotation type="Authority">Public Utilities Article, §§2-113, 2-121, and 4-203(c), Annotated Code of Maryland</annotation>
      <annotation type="History" subtype="Administrative History">Effective date: April 22, 2019 (46:8 Md. R. 402)</annotation>
    </annotations>
  </chapter>
</subtitle>