<regulation prefix="Regulation" num=".06" citation="COMAR 26.10.03.06" title_num="26" subtitle_num="10" chapter_num="03" heading="Piping Installation.">
  <paragraph num="A.">
    <text>An owner and an operator of a UST system shall comply with the installation requirements of this regulation.</text>
  </paragraph>
  <paragraph num="B.">
    <text>Install piping in accordance with the requirements of this regulation.</text>
  </paragraph>
  <paragraph num="C.">
    <text>Place underground piping on a 6-inch bedding of appropriate backfill material as described in Regulation .04 of this chapter.</text>
  </paragraph>
  <paragraph num="D.">
    <text>Maintain the following clearances when installing piping:</text>
    <paragraph num="(1)">
      <text>Twice the nominal diameter of the pipe but at least 4 inches between all piping;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>At least 6 inches between piping and electrical conduits related to the UST system;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>At least 6 inches between piping and excavation zone sidewalls; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>At least 18 inches between piping and the surface of the ground.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Unless otherwise approved by the Department, ensure piping rises 1/8 of an inch for each lateral foot from the UST to the piping endpoint.</text>
  </paragraph>
  <paragraph num="F.">
    <text>Follow the manufacturer specifications and installation requirements when installing piping.</text>
  </paragraph>
  <paragraph num="G.">
    <text>In accordance with manufacturer specifications, use a UL listed flexible connector to connect piping as follows:</text>
    <paragraph num="(1)">
      <text>Except for a direct fill line, to connect a pipe carrying a regulated substance to a UST at the end of a piping run; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>To connect a pipe carrying a regulated substance to a dispenser system.</text>
    </paragraph>
  </paragraph>
  <paragraph num="H.">
    <text>Unless otherwise approved by the Department, an owner and an operator of a UST system may not use a flexible connector to connect piping carrying petroleum vapor or a regulated substance at any other point in the piping system not listed in §G of this regulation.</text>
  </paragraph>
  <paragraph num="I.">
    <text>Place a UL listed shear valve on pressurized product piping dispensing motor fuel, and properly anchor the shear valve at the dispenser.</text>
  </paragraph>
  <paragraph num="J.">
    <text>Install appurtenances such as water or air piping in a separate piping trench;</text>
  </paragraph>
  <paragraph num="K.">
    <text>Ensure vent lines above the ground surface are:</text>
    <paragraph num="(1)">
      <text>Constructed with at least schedule 40 steel;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Protected from traffic;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Properly anchored; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Protected from weather and debris.</text>
    </paragraph>
  </paragraph>
  <paragraph num="L.">
    <text>Ensure the vents of a UST system storing a flammable or combustible liquid meet the following conditions:</text>
    <paragraph num="(1)">
      <text>If the UST system stores a flammable liquid, the vents terminate 12 feet above the ground surface and 2 feet above an attached building; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>If the UST system stores a combustible liquid, the vents terminate at least 3 feet above the ground surface.</text>
    </paragraph>
  </paragraph>
</regulation>