  <regulation prefix="Regulation" num=".01" heading="Performance Standards for New or Replacement UST Systems.">
    <paragraph num="A.">
      <text>An owner and an operator of a new or replacement UST system shall comply with the requirements of this chapter for as long as a UST system is used to store a regulated substance to prevent a spill, release, or discharge due to structural failure, corrosion, or an overfill.</text>
    </paragraph>
    <paragraph num="B.">
      <text>UST Standards for a New or Replacement UST System.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall install a UST that is properly designed, constructed, and protected from corrosion in accordance with one of the following methods:</text>
        <paragraph num="(a)">
          <text>The UST is constructed of UL listed fiberglass-reinforced plastic;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The UST is constructed of steel, is coated with a suitable dielectric material, and has one of the following cathodic protection systems:</text>
          <paragraph num="(i)">
            <text>An impressed current system designed by a corrosion expert; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>A manufacturer-installed cathodic protection system that is UL listed or approved by STI;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>The UST is constructed of steel and clad or jacketed with a non-corrodible material that is UL listed or approved by STI; or</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Subject to the approval of the Department, the UST is constructed and protected from corrosion by an alternative installation method that is designed to prevent a spill, release, or discharge or a threatened spill, release, or discharge of a stored regulated substance in a manner determined by the Department to be as protective of public health, safety, and welfare and the environment as the USTs described in §B(1)(a)—(c) of this regulation.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system installed after January 11, 2009 shall install a UST that has secondary containment.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>An owner and an operator of a UST system with a cathodic protection system installed in accordance with §B(1)(b) of this regulation shall:</text>
        <paragraph num="(a)">
          <text>Operate and maintain the cathodic protection system in accordance with COMAR 26.10.04.02; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the UST cathodic protection system is an impressed current system, ensure the impressed current system is designed to allow for the determination of the current operating status as required in COMAR 26.10.04.02.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Notification.</text>
      <paragraph num="(1)">
        <text>In a format required by the Department, an owner, an operator, and a person in charge of a new or replacement UST system shall notify the Department in writing of the installation of the new or replacement UST system not later than 5 working days before installation begins.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>In accordance with Regulation .09 of this chapter, an owner, an operator, and a person in charge of a new or replacement UST system shall register the UST system with the Department after the installation of the UST system is complete.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Previously Installed USTs. An owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Only install a previously installed UST if:</text>
        <paragraph num="(a)">
          <text>The owner and the operator submit to the Department a written certification from the UST manufacturer that states the previously installed UST is suitable for service; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The Department has provided the owner and the operator written approval to install the previously installed UST;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Begin the installation of the previously installed UST within 60 days of the issuance of the Department’s written approval to install the UST or in accordance with another schedule required by the Department;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Ensure all UST system standards and installation requirements of COMAR 26.10 are met when installing the previously installed UST; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>Maintain the manufacturer’s written certification and the Department’s written approval in accordance with the recordkeeping requirements in COMAR 26.10.04.05.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".02" heading="Performance Standards for Piping.">
    <paragraph num="A.">
      <text>On or after January 26, 2005, an owner and an operator of a UST system shall install, upgrade, or replace piping that routinely contains petroleum vapor or a regulated substance in accordance with the following requirements:</text>
      <paragraph num="(1)">
        <text>Install piping in a UL listed or Department approved secondary containment system that:</text>
        <paragraph num="(a)">
          <text>Contains the petroleum vapor or regulated substance released from the primary piping until the petroleum vapor or regulated substance is detected and removed;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Prevents a spill, release, or discharge of petroleum vapor or a regulated substance to the environment; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>With the exception of the vent riser, beginning June 13, 2022, terminates or connects in a liquid tight containment sump with a sump sensor:</text>
          <paragraph num="(i)">
            <text>Installed within 1 inch of the lowest part of the sump bottom;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Properly secured in the sump by a fixed mounting bracket; and</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>That activates an alarm when liquid is detected;</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Connect piping to the UST in a liquid tight containment sump that is maintained clean and free of liquid;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>When a product dispenser is part of the UST system, install piping that terminates in an under-dispenser containment sump that is liquid tight and maintained clean and free of liquid; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>If an intermediate sump is used, connect piping in a liquid tight containment sump that is maintained clean and free of liquid.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Corrosion Protection Standards for Piping.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall ensure that piping in contact with the ground, including soil and backfill material, or continuous or intermittent water, is properly designed, constructed, and protected from corrosion in accordance with one of the following methods:</text>
        <paragraph num="(a)">
          <text>The piping and connectors are constructed of fiberglass-reinforced plastic or flexible piping that is UL listed as appropriate piping for the regulated substance stored and for use in a UST system;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The piping is constructed of steel, is coated with a suitable dielectric material, and has a cathodic protection system designed by a corrosion expert; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Subject to the approval of the Department, the piping is constructed and protected from corrosion by an alternative installation method that is designed to prevent a spill, release, or discharge or a threatened spill, release, or discharge of a stored regulated substance in a manner determined by the Department to be as protective of public health, safety, and welfare and the environment as the types of piping described in §B(1)(a) and (b) of this regulation.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system with steel piping equipped with a cathodic protection system installed in accordance with §B(1)(b) of this regulation shall:</text>
        <paragraph num="(a)">
          <text>Operate and maintain the piping cathodic protection system in accordance with COMAR 26.10.04.02; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the piping cathodic protection system is an impressed current system, ensure the impressed current system is designed to allow for the determination of the current operating status as required in COMAR 26.10.04.02.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>An owner and an operator of a UST system may not use a fiberglass-reinforced plastic piping system:</text>
      <paragraph num="(1)">
        <text>For direct fill lines, unless approved by the Department; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Aboveground or above grade.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>After January 1, 2009, an owner and an operator that installs a new, upgraded, or replacement UST system may not use a flexible piping system for:</text>
      <paragraph num="(1)">
        <text>Direct fill lines;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Vent lines; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Stage II vapor recovery lines.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>An owner and an operator of a UST system that replaces 40 percent or more of piping connected to a single UST, including each independent piping run connected to a UST with multiple piping runs, shall replace the remaining single-walled piping connected to the UST with a piping system that meets the requirements of this regulation.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".03" heading="Spill and Overfill Prevention Equipment.">
    <paragraph num="A.">
      <text>Except as provided under §C of this regulation, an owner and an operator of a UST system shall use spill and overfill prevention equipment that complies with the requirements of this section.</text>
      <paragraph num="(1)">
        <text>Spill Prevention Equipment. An owner and an operator of a UST system shall install and test spill prevention equipment that will prevent a spill, release, or discharge of a regulated substance into the environment when the transfer hose of a truck tank or transport is detached from the fill pipe or Stage I vapor recovery connection of a UST in accordance with the following requirements:</text>
        <paragraph num="(a)">
          <text>Install a spill catchment basin with a minimum capacity of 5 gallons at the fill pipe of a new, replacement, or upgraded UST;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Beginning November 4, 1996, install a spill catchment basin with a minimum capacity of 5 gallons at the fill pipe of a new, replacement, or upgraded UST system that receives used oil;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Beginning July 1, 1998, install a spill catchment basin with a minimum capacity of 5 gallons at the Stage I vapor recovery connection on a new or replacement UST system that utilizes Stage I vapor recovery; and</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Test spill prevention equipment for tightness using a method approved by the Department at the following frequency:</text>
          <paragraph num="(i)">
            <text>If the spill prevention equipment was installed before January 26, 2005, within 180 days of that date;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>If the spill prevention equipment is installed on or after January 26, 2005, within 30 days of installing the spill prevention equipment;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>Upon repair of the spill prevention equipment; and</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>At least annually after the most recent test was conducted.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Overfill Prevention Equipment. An owner and an operator of a UST system:</text>
        <paragraph num="(a)">
          <text>Shall ensure overfill prevention equipment:</text>
          <paragraph num="(i)">
            <text>Automatically shuts off flow into a UST when the UST is 95 percent full; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Alerts the transfer operator when a UST is 90 percent full by restricting the flow of a regulated substance into the UST or triggering a high level alarm;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>May not install or replace a flow restrictor in a vent line to comply with §A(2)(a) of this regulation after June 13, 2022;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Shall have a UST system inspector or technician certified under COMAR 26.10.06 or a precision tightness tester certified by a test method recognized by the Department conduct an inspection and functional test of overfill prevention equipment as follows:</text>
          <paragraph num="(i)">
            <text>Inspect overfill prevention equipment using a method approved by the Department to ensure the overfill prevention equipment is set to activate at the correct level specified in §A(2)(a) of this regulation when a regulated substance reaches that level in a UST; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Conduct a functional test of the overfill prevention equipment using a method approved by the Department to ensure the overfill prevention equipment will activate when a regulated substance reaches the correct level specified in §A(2)(a) of this regulation; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(d)">
          <text>Shall conduct inspections and functional tests of overfill prevention equipment in accordance with the procedures in §A(2)(c) of this regulation at the following frequency:</text>
          <paragraph num="(i)">
            <text>Unless an inspection and functional test was conducted before June 13, 2022, within 1 year of June 13, 2022;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Upon the installation or repair of overfill prevention equipment; and</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>At least every 3 years after the most recent inspection and functional test was conducted.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Containment Sumps. An owner and an operator of a UST system shall:</text>
        <paragraph num="(a)">
          <text>Ensure a containment sump prevents the release of a regulated substance into the environment;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Use a containment sump for all connections of piping to or from a UST and to or from a dispenser; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Test a containment sump for tightness using a method approved by the Department at the following frequency:</text>
          <paragraph num="(i)">
            <text>If the containment sump was installed before January 26, 2005, within 1 year of that date;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>If the containment sump is installed on or after January 26, 2005, within 30 days of installing the containment sump;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>Upon repair of the containment sump;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>If the most recent test conducted on the containment sump occurred before June 13, 2022, within 5 years of the most recent test; and</text>
          </paragraph>
          <paragraph num="(v)">
            <text>At least every 3 years after the most recent test was conducted.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>When a test for tightness conducted on spill prevention equipment or a containment sump results in a failed test result, the owner and the operator of the UST system and the person conducting the test shall report the failed test result to the Department within 2 hours in accordance with COMAR 26.10.08.01.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Dispenser System Requirements.</text>
      <paragraph num="(1)">
        <text>When installing a new dispenser system, an owner and an operator of a UST system shall equip the dispenser system with under-dispenser containment.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>A dispenser system is considered new when both the dispenser and the equipment needed to connect the dispenser to a UST system are installed at a regulated substance storage facility.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>An owner and an operator of a UST system are not required to use the spill and overfill prevention equipment required under §A of this regulation if:</text>
      <paragraph num="(1)">
        <text>The Department determines alternative equipment or methods used for spill and overfill prevention are as protective of public health, safety, and welfare and the environment as the equipment or methods required under §A of this regulation;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Not more than 25 gallons of a regulated substance is transferred at one time to the UST system; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>The UST system stores heating oil only for consumptive use and the UST system was installed before November 4, 1996.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Reporting and Recordkeeping.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall maintain records demonstrating compliance with the requirements for installing and operating spill and overfill prevention equipment and containment sumps for as long as the UST system is used to store a regulated substance.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If an owner, an operator, and a person in charge of a UST system changes the method of spill or overfill prevention used, the owner, the operator, and the person in charge of the UST system shall provide the Department written notification within 30 days of the change.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>For each inspection and test conducted in compliance with §A(1)(d), (2)(d), and (3)(c) of this regulation, the owner and the operator of the UST system shall:</text>
        <paragraph num="(a)">
          <text>Maintain test records that include at least the following information:</text>
          <paragraph num="(i)">
            <text>The name of the testing company;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The name of the individual conducting the test;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>The date of the test;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>The data accumulated by the test; and</text>
          </paragraph>
          <paragraph num="(v)">
            <text>The results of the test.</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>Keep the test records on file at the regulated substance storage facility or at a location designated by and under the control of the owner and the operator of the UST system for as long as the UST system is used to store a regulated substance; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Make the records available to the Department upon request.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".04" heading="UST System Installation Standards.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system shall properly install the UST system in accordance with:</text>
      <paragraph num="(1)">
        <text>The requirements of this regulation;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>The applicable technical codes and standards incorporated by reference under COMAR 26.10.01.03;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>The manufacturer’s instructions;</text>
      </paragraph>
      <paragraph num="(4)">
        <text>The requirement to have a certified UST system technician perform or supervise the installation in accordance with COMAR 26.10.02.03D; and</text>
      </paragraph>
      <paragraph num="(5)">
        <text>Any alternative installation methods approved by the Department under Regulations .01B(1)(d), .02B(1)(c), and .03C(1) of this chapter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Monitoring Pipes. An owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Install two permanent monitoring pipes or, if a UST system is constructed in a high risk groundwater use area or well head protection area as defined in COMAR 26.10.07.02B, four permanent monitoring pipes:</text>
        <paragraph num="(a)">
          <text>Vertically and in opposing corners of a new or replacement UST system excavation zone;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>That extend to a minimum depth of 2 feet below the bottom of the UST in the excavation zone;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Constructed of schedule 40 polyvinyl chloride (PVC);</text>
        </paragraph>
        <paragraph num="(d)">
          <text>That are a minimum of 4 inches in diameter;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Constructed with PVC screened pipe from the bottom to within 2 feet of the top of a monitoring pipe, with the remaining 2 feet being constructed of solid PVC; and</text>
        </paragraph>
        <paragraph num="(f)">
          <text>That have a minimum slot size of 0.020 inches and maximum slot size of 0.025 inches with not less than 30 slots per foot; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Complete the installation of the monitoring pipes required under §B(1) of this regulation by:</text>
        <paragraph num="(a)">
          <text>Backfilling around the outside of the monitoring pipes with fine pea gravel or wrapping the monitoring pipes in an appropriate filter cloth to prevent clogging;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Sealing around the top 8 inches to ground surface with a bentonite clay and concrete mixture or by other means to prevent the entrance of surface water runoff;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Capping the monitoring pipes with a liquid-tight threaded cap or removable liquid-tight plug;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Protecting the monitoring pipes from traffic with a manhole and cover;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Locking or bolting closed the monitoring pipes;</text>
        </paragraph>
        <paragraph num="(f)">
          <text>Identifying the monitoring pipes to avoid confusion with product fill lines; and</text>
        </paragraph>
        <paragraph num="(g)">
          <text>Having a key or locking tool for the monitoring pipes kept at the regulated substance storage facility.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Excavations. An owner and an operator of a UST system shall perform an excavation for the UST system that is:</text>
      <paragraph num="(1)">
        <text>A minimum distance of 5 feet from the base of adjacent structures or property lines;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If installing a steel UST, a minimum 12-inch distance between other USTs and a minimum 12-inch clearance between a UST and all sides of the excavation zone; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>If installing a fiberglass-reinforced plastic UST, a minimum 18-inch distance between other USTs and a minimum 18-inch clearance between a UST and all sides of the excavation zone.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>An owner and an operator of a UST system shall place a UST upon a minimum 12-inch bedding made of backfill material.</text>
    </paragraph>
    <paragraph num="E.">
      <text>Backfill Material. An owner and an operator of a UST system:</text>
      <paragraph num="(1)">
        <text>Shall use backfill material composed of:</text>
        <paragraph num="(a)">
          <text>Pea gravel not larger than 3/4 of an inch; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Crushed stone not larger than 1/2 of an inch;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>May use clean sand as backfill material for protected steel and steel-clad USTs;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Shall use the same material for backfilling operations that is used for bedding; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>May not use backfill material with debris, foreign matter, or frozen matter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="F.">
      <text>Except where there is, at a minimum, 48 inches of clearance between a UST and shoring, an owner and an operator of a UST system shall remove shoring from the UST system excavation zone when the installation of the UST system is complete.</text>
    </paragraph>
    <paragraph num="G.">
      <text>In an area of high groundwater or where UST movement is possible, an owner and an operator of a UST system shall safeguard a UST against movement from high groundwater or a flood by:</text>
      <paragraph num="(1)">
        <text>Anchoring the UST in compliance with the UST manufacturer’s instructions; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Other means acceptable to the Department.</text>
      </paragraph>
    </paragraph>
    <paragraph num="H.">
      <text>When using a hold-down pad or anchors made of concrete to prevent the movement of a UST, an owner and an operator of a UST system shall allow the concrete to cure for a minimum of 48 hours before:</text>
      <paragraph num="(1)">
        <text>Placing a new UST and associated backfill on freshly poured concrete; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Anchoring a UST to the hold-down devices.</text>
      </paragraph>
    </paragraph>
    <paragraph num="I.">
      <text>An owner and an operator of a UST system may not install a groundwater drain system in the UST system excavation zone without prior written approval by the Department.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".05" heading="Precision Tightness Testing.">
    <paragraph num="A.">
      <text>After completing the installation or replacement, repair, or upgrade of a UST system, an owner and an operator of a UST system shall test the UST system for tightness using a precision tightness test as defined in COMAR 26.10.02.02B before operation of the UST system.</text>
    </paragraph>
    <paragraph num="B.">
      <text>An owner and an operator of a UST system shall only conduct a precision tightness test approved by the Department.</text>
    </paragraph>
    <paragraph num="C.">
      <text>For each precision tightness test conducted on a UST system, the owner and the operator of the UST system shall:</text>
      <paragraph num="(1)">
        <text>Maintain and make available for inspection by the Department upon request, records regarding a precision tightness test;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Keep the records on file at the regulated substance storage facility or at a location designated by and the under control of the owner and the operator of the UST system for as long as the UST system is used to store a regulated substance; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Include in the records all of the following information:</text>
        <paragraph num="(a)">
          <text>The commercial name of the test equipment;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The name of the testing company;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>The name of the individual conducting the test;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>The date of the test;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>The data accumulated by the test; and</text>
        </paragraph>
        <paragraph num="(f)">
          <text>The results of the precision tightness test.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Inconclusive Precision Tightness Test Results.</text>
      <paragraph num="(1)">
        <text>When a precision tightness test conducted on a UST system results in an inconclusive test result, the owner and the operator of the UST system shall retest the UST system not later than 2 working days after the inconclusive test result.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If a subsequent precision tightness test conducted on a UST system also results in an inconclusive test result, the owner and the operator of the UST system and the person conducting the precision tightness test shall report the test result as a failure to the Department within 2 hours in accordance with COMAR 26.10.08.01.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>When a precision tightness test conducted on a UST system results in a failed test result, the owner and the operator of the UST system and the person conducting the precision tightness test shall report the failed test result to the Department within 2 hours in accordance with COMAR 26.10.08.01.</text>
    </paragraph>
    <paragraph num="F.">
      <text>Consumptive Use UST Systems.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a consumptive use UST system shall comply with the requirements of §§A—E of this regulation.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Unless otherwise required by the Department, an owner and an operator of a consumptive use UST system are not required to conduct precision tightness tests on the consumptive use UST system at the frequency required under §F(3)(a) if the following conditions are met:</text>
        <paragraph num="(a)">
          <text>The UST system is protected against corrosion in accordance with the requirements of this chapter;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The UST system is installed in accordance with the requirements of this chapter; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>The owner and the operator of the UST system conduct monthly release detection monitoring of the UST system in accordance with COMAR 26.10.05.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>If the conditions in §F(2) of this regulation are not met, an owner and an operator of a consumptive use UST system shall:</text>
        <paragraph num="(a)">
          <text>Conduct a precision tightness test on the UST system:</text>
          <paragraph num="(i)">
            <text>15 years after the installation date for the UST system or, if the installation date cannot be determined, immediately; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>At least every 5 years after the most recent precision tightness test; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>Conduct a precision tightness test on the UST system immediately upon receipt of a notice from the Department to conduct a precision tightness test.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".06" heading="Piping Installation.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system shall comply with the installation requirements of this regulation.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Install piping in accordance with the requirements of this regulation.</text>
    </paragraph>
    <paragraph num="C.">
      <text>Place underground piping on a 6-inch bedding of appropriate backfill material as described in Regulation .04 of this chapter.</text>
    </paragraph>
    <paragraph num="D.">
      <text>Maintain the following clearances when installing piping:</text>
      <paragraph num="(1)">
        <text>Twice the nominal diameter of the pipe but at least 4 inches between all piping;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>At least 6 inches between piping and electrical conduits related to the UST system;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>At least 6 inches between piping and excavation zone sidewalls; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>At least 18 inches between piping and the surface of the ground.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Unless otherwise approved by the Department, ensure piping rises 1/8 of an inch for each lateral foot from the UST to the piping endpoint.</text>
    </paragraph>
    <paragraph num="F.">
      <text>Follow the manufacturer specifications and installation requirements when installing piping.</text>
    </paragraph>
    <paragraph num="G.">
      <text>In accordance with manufacturer specifications, use a UL listed flexible connector to connect piping as follows:</text>
      <paragraph num="(1)">
        <text>Except for a direct fill line, to connect a pipe carrying a regulated substance to a UST at the end of a piping run; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>To connect a pipe carrying a regulated substance to a dispenser system.</text>
      </paragraph>
    </paragraph>
    <paragraph num="H.">
      <text>Unless otherwise approved by the Department, an owner and an operator of a UST system may not use a flexible connector to connect piping carrying petroleum vapor or a regulated substance at any other point in the piping system not listed in §G of this regulation.</text>
    </paragraph>
    <paragraph num="I.">
      <text>Place a UL listed shear valve on pressurized product piping dispensing motor fuel, and properly anchor the shear valve at the dispenser.</text>
    </paragraph>
    <paragraph num="J.">
      <text>Install appurtenances such as water or air piping in a separate piping trench;</text>
    </paragraph>
    <paragraph num="K.">
      <text>Ensure vent lines above the ground surface are:</text>
      <paragraph num="(1)">
        <text>Constructed with at least schedule 40 steel;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Protected from traffic;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Properly anchored; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>Protected from weather and debris.</text>
      </paragraph>
    </paragraph>
    <paragraph num="L.">
      <text>Ensure the vents of a UST system storing a flammable or combustible liquid meet the following conditions:</text>
      <paragraph num="(1)">
        <text>If the UST system stores a flammable liquid, the vents terminate 12 feet above the ground surface and 2 feet above an attached building; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If the UST system stores a combustible liquid, the vents terminate at least 3 feet above the ground surface.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".07" heading="Compatibility.">
    <text>An owner and an operator of a UST system shall:</text>
    <paragraph num="A.">
      <text>Use a UST system made of or lined with a material compatible with the regulated substance stored in the UST system;</text>
    </paragraph>
    <paragraph num="B.">
      <text>If the UST system stores an ethanol blend, comply with API Recommend Practice 1626 “Storing and Handling Ethanol and Gasoline-ethanol Blends at Distribution Terminals and Filling Stations”;</text>
    </paragraph>
    <paragraph num="C.">
      <text>Provide notification to the Department regarding a change in the regulated substance stored in the UST system as follows:</text>
      <paragraph num="(1)">
        <text>In a format required by the Department, notify the Department in writing at least 30 days before switching to a regulated substance that contains:</text>
        <paragraph num="(a)">
          <text>Greater than 10 percent ethanol;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Greater than 20 percent biodiesel; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Any other regulated substance identified by the Department; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>In accordance with Regulation .09 of this chapter, amend the registration for the UST system after the switch to a regulated substance listed in §C(1) of this regulation is complete;</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>If a UST system stores one of the regulated substances identified in §C of this regulation, demonstrate the compatibility of the UST system with the regulated substance, including the UST, piping, containment sumps, pumping equipment, release detection equipment, spill prevention equipment, and overfill prevention equipment, by using one of the following options:</text>
      <paragraph num="(1)">
        <text>Use equipment or components certified or listed by a nationally recognized association for use with the stored regulated substance;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Use equipment or components with written approval from the manufacturer that affirmatively states the equipment or components are compatible with a specified range of biofuel blends, including the stored regulated substance; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Use equipment or components determined by the Department to be not less protective of public health, safety, and welfare and the environment as the equipment or components specified in §D(1) and (2) of this regulation; and</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Maintain records documenting compliance with the compatibility requirements under §D of this regulation for as long as the UST system is used to store the regulated substance.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".08" heading="Upgrading Existing UST Systems.">
    <paragraph num="A.">
      <text>This regulation does not apply to an owner and an operator of:</text>
      <paragraph num="(1)">
        <text>A UST system containing heating oil for consumptive use; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>A UST system with a field-constructed tank or an airport hydrant fuel distribution system.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Closure of an Existing UST System.</text>
      <paragraph num="(1)">
        <text>Except as provided in §B(2) of this regulation, an owner and an operator of an existing UST system shall permanently close the UST system in accordance with:</text>
        <paragraph num="(a)">
          <text>The closure requirements under COMAR 26.10.10; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The reporting and corrective action requirements under COMAR 26.10.08 and 26.10.09.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of an existing UST system are not required under §B(1) of this regulation to permanently close the existing UST system if the following conditions are met:</text>
        <paragraph num="(a)">
          <text>Upon installation, the existing UST system was installed in accordance with the performance standards under Regulations .01B, .02B, .03A(1)(a) and (2)(a), and .07A of this chapter; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The existing UST system was upgraded on or before December 22, 1998 in accordance with the requirements under §§D—F of this regulation.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Unless an existing UST system meets the conditions in §B(2) of this regulation, an owner and an operator of an existing UST system may not allow delivery of a regulated substance to, or dispensing of a regulated substance from, the existing UST system.</text>
    </paragraph>
    <paragraph num="D.">
      <text>Upgrade Requirements.</text>
      <paragraph num="(1)">
        <text>Not later than December 22, 1998, an owner and an operator of an existing UST system with a steel UST shall implement of one the following corrosion protection methods under §D(2) or (3) of this regulation.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Cathodic Protection System. Not later than December 22, 1998, an owner and an operator of an existing UST system with a steel UST shall upgrade the UST by installing a cathodic protection system meeting the performance standards in Regulation .01B(1)(b)(i) and (3) of this chapter, and ensuring the integrity of the UST through one of the following methods:</text>
        <paragraph num="(a)">
          <text>Internally inspect and assess the UST to ensure the storage tank is structurally sound and free of corrosion holes;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Demonstrate the UST was not installed before December 22, 1988, and the UST has been monitored monthly for releases in accordance with COMAR 26.10.05.05E—H;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Demonstrate the UST was not installed before December 22, 1988, and the UST has been assessed by conducting two precision tightness tests meeting requirements of Regulation .05A—C of this chapter and the following testing schedule:</text>
          <paragraph num="(i)">
            <text>The first precision tightness test was conducted before installing the cathodic protection system; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The second precision tightness test was conducted between 3 and 6 months following the first operation of the cathodic protection system; or</text>
          </paragraph>
        </paragraph>
        <paragraph num="(d)">
          <text>Demonstrate that the UST was assessed for corrosion holes using a method determined by the Department to prevent spills, releases, and discharges in a manner that is not less protective of public health, safety, and welfare and the environment than the methods specified under §D(2)(a)—(c) of this regulation.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Internal Lining Combined with Cathodic Protection. Not later than December 22, 1998, an owner and an operator of an existing UST system with a steel UST that meets the requirements of API Standard 1631 “Interior Lining and Periodic Inspection of Underground Storage Tanks” shall upgrade the steel UST with an internal lining and a cathodic protection system as follows:</text>
        <paragraph num="(a)">
          <text>Before applying the interior lining, determine if there is evidence of a spill, release, or discharge from the UST system where a spill, release, or discharge is most likely to be present;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Apply the interior lining:</text>
          <paragraph num="(i)">
            <text>In compliance with the repair standards in COMAR 26.10.04.04; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>In accordance with the requirements in API Standard 1631 “Interior Lining and Periodic Inspection of Underground Storage Tanks”;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>Install a cathodic protection system that meets the performance standards for cathodic protection under Regulation .01B(1)(b)(i) and (3);</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Conduct a precision tightness test on the UST system in accordance with Regulation .05A—C of this chapter before placing the UST system back into service;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Maintain, and make available for inspection by the Department upon request, a written certification from the contractors that performed the work required under §D(3)(a)—(d) of this regulation that states all work was performed in accordance with the requirements of this regulation; and</text>
        </paragraph>
        <paragraph num="(f)">
          <text>Internally inspect the lined UST within the first 10 years after applying the lining and at least every 5 years thereafter, with the results of each inspection finding that the lining is structurally sound and performing in accordance with the original design specifications.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>After December 22, 1998, if the internal lining of an existing UST system upgraded using the method in §D(3) of this regulation no longer performs in accordance with original design specifications, the owner and the operator of the existing UST system shall permanently close the UST system in accordance with procedures in COMAR 26.10.10.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Piping Upgrade Requirements. Not later than December 22, 1998, an owner and an operator of an existing UST system shall upgrade metal piping in contact with the ground by installing a cathodic protection system that meets the performance standards for cathodic protection under Regulation .02B(1)(b) and (2) of this chapter.</text>
    </paragraph>
    <paragraph num="F.">
      <text>Spill and Overfill Prevention Equipment Requirements. Not later than December 22, 1998, an owner and an operator of an existing UST system shall upgrade the UST system to meet the performance standards under Regulation .03A(1)(a) and (2)(a) of this chapter.</text>
    </paragraph>
    <paragraph num="G.">
      <text>In accordance with Regulation .09 of this chapter, an owner, an operator, and a person in charge of an existing UST system shall amend the registration for the existing UST system after an upgrade performed in compliance with this regulation is complete.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".09" heading="UST System Registration Requirements.">
    <paragraph num="A.">
      <text>An owner, an operator, and a person in charge of one or more UST systems shall:</text>
      <paragraph num="(1)">
        <text>Register each UST system with the Department and maintain up-to-date registration for each UST system with the Department;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Submit to the Department a completed registration form for a UST system to the Department not later than 30 days following the:</text>
        <paragraph num="(a)">
          <text>Installation of a new or replacement UST system; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Acquisition of a new or replacement UST system;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Amend the registration for a registered UST system by submitting to the Department a registration form not later than 30 days following:</text>
        <paragraph num="(a)">
          <text>The return of a temporarily closed UST system to in-service status;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>A change in the regulated substance stored;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>A change-in-service to store a non-regulated substance in a UST system;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>An upgrade of an existing UST system;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>The temporary closure or permanent closure of a UST system; or</text>
        </paragraph>
        <paragraph num="(f)">
          <text>If applicable, an owner of UST system being released from the requirement to maintain financial responsibility or obtaining coverage under an alternate mechanism of financial responsibility; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>Include on a submitted registration form all of the information requested on the form, including:</text>
        <paragraph num="(a)">
          <text>If amending the registration for a registered UST system, information remaining unchanged since the last registration form was submitted for the UST system;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>A certification of the UST system owner’s compliance with the:</text>
          <paragraph num="(i)">
            <text>Installation of a UST and piping requirements under this chapter;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Installation of spill and overfill prevention equipment requirements under this chapter;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>Cathodic protection of steel USTs and piping requirements under Regulations .01 and .02 of this chapter;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>Financial responsibility requirements under COMAR 26.10.11; and</text>
          </paragraph>
          <paragraph num="(v)">
            <text>Release detection requirements under COMAR 26.10.05 and, if a UST system with a field-constructed tank or an airport hydrant system, 26.10.12;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>If the UST system is used in the operation of a commercial or business entity, certification and proof that:</text>
          <paragraph num="(i)">
            <text>The owner has registered the commercial or business entity with the Maryland Department of Assessments and Taxation; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The commercial or business entity is in good standing with the State at the time of the UST system initial or amended registration; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(d)">
          <text>A certification from a certified UST system technician that the methods used to install the UST system comply with the requirements in COMAR 26.10.02—26.10.12 and 26.10.16.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>An owner, an operator, and a person in charge of a UST system required to register or amend the registration for a UST system under §A of this regulation:</text>
      <paragraph num="(1)">
        <text>May register or amend the registration for one or more UST systems located at one place of operation using one registration form; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Shall register or amend the registration for UST systems located at separate places of operation using separate registration forms for each place of operation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>A person who sells a UST system shall inform the purchaser of the registration obligation under §A of this regulation and provide the purchaser with a copy of the Department’s registration form.</text>
    </paragraph>
    <paragraph num="D.">
      <text>An owner, an operator, and person in charge of a UST system that is not registered with the Department may not sell, receive, or dispense oil or any other regulated substance to or from the UST system, with the exception of the minimum amount of a regulated substance necessary to conduct an initial precision tightness test for a new or replacement UST system.</text>
    </paragraph>
    <paragraph num="E.">
      <text>An owner, an operator, and a person in charge of a registered UST system shall:</text>
      <paragraph num="(1)">
        <text>Display the UST system registration certificate issued by the Department at the regulated substance storage facility; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Produce the UST system registration certificate immediately upon the request of the Department.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".10" heading="UST System Inspection Requirements.">
    <paragraph num="A.">
      <text>An owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system shall have a certified inspection completed for the UST system:</text>
      <paragraph num="(1)">
        <text>By a UST system inspector certified by the Department under COMAR 26.10.06;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>To verify the owner’s and the operator’s compliance with the UST system requirements established under this chapter and COMAR 26.10.02, 26.10.04, 26.10.05, 26.10.07—26.10.12 and 26.10.16; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>In accordance with the schedule established under §B of this regulation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Inspection Schedule. An owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system shall complete:</text>
      <paragraph num="(1)">
        <text>An initial inspection of the UST system:</text>
        <paragraph num="(a)">
          <text>If the UST system was installed before January 16, 2006, within 30 days of receiving a notification from the Department to complete an inspection; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the UST system was installed on or after January 16, 2006, within 6 months of the UST system installation;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>A subsequent inspection of the UST system:</text>
        <paragraph num="(a)">
          <text>At least once every 3 years following the most recent inspection;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Within 30 days of receiving a notification from the Department to complete an inspection; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>If the ownership of the UST system changes, within 3 months of the change in ownership.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Additional Inspections.</text>
      <paragraph num="(1)">
        <text>If required by the Department, an owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system shall complete an inspection in addition to an inspection required under §B of this regulation to verify compliance with the UST system requirements under this chapter and COMAR 26.10.02, 26.10.04, 26.10.05, 26.10.07—26.10.12 and 26.10.16.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system may not substitute an inspection required by the Department under §C(1) of this regulation for an inspection required under §B of this regulation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>After conducting an inspection required under §B or C of this regulation, an owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system shall:</text>
      <paragraph num="(1)">
        <text>Submit to the Department an inspection report on forms provided by the Department:</text>
        <paragraph num="(a)">
          <text>Within 30 days of the deadline to complete an inspection established under §B or C of this regulation;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Completed by a certified UST system inspector;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Signed by the certified UST system inspector that conducted the inspection; and</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Signed by the owner, the operator, and the person in charge of the UST system; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Unless the Department determines immediate corrective action by the owner is required to protect public health, safety, and welfare and the environment, within 30 days of receiving a Notice to Correct Deficiencies issued by the Department:</text>
        <paragraph num="(a)">
          <text>Correct all of the deficiencies identified during the inspection in accordance with the UST system requirements under this chapter and COMAR 26.10.02, 26.10.04, 26.10.05, 26.10.07—26.10.12 and 26.10.16; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Submit to the Department proof of corrective actions performed to correct the deficiencies.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Recordkeeping. For a minimum of 5 years, an owner of a motor fuel, bulk oil storage, used oil, or a hazardous substance UST system shall maintain records of completed inspections at a location designated by the owner and make the records available to the Department upon request.</text>
    </paragraph>
  </regulation>
  <annotations>
    <annotation type="Authority">Environment Article, §§4-401, 4-402, 4-405, 4-407—4-411.2, 4-415.1, 4-417, 4-701 et seq., and 7-201 et seq., Annotated Code of Maryland</annotation>
    <annotation type="History" subtype="Administrative History">Effective date: February 4, 1991 (18:2 Md. R. 151)</annotation>
    <annotation type="History" subtype="Administrative History">Chapter revised effective November 4, 1996 (23:22 Md. R. 1498)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .01 amended effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .01B amended effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02 amended as an emergency provision effective January 26, 2005 (32:4 Md. R. 406); emergency provision extended at 32:15 Md. R. 1315</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02 amended effective January 16, 2006 (33:1 Md. R. 38); January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .03A amended effective February 18, 2002 (29:3 Md. R. 224)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .03A amended as an emergency provision effective January 26, 2005 (32:4 Md. R. 406); emergency provision extended at 32:15 Md. R. 1315</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .03A amended effective January 16, 2006 (33:1 Md. R. 38)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .03D adopted effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04B amended effective January 16, 2006 (33:1 Md. R. 38)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04H adopted effective February 18, 2002 (29:3 Md. R. 224)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04I adopted effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .05A amended effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .07E amended effective February 18, 2002 (29:3 Md. R. 224)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .08 amended effective June 29, 1998 (25:13 Md. R. 997); February 18, 2002 (29:3 Md. R. 224); January 16, 2006 (33:1 Md. R. 38)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .09 amended effective January 16, 2006 (33:1 Md. R. 38)</annotation>