<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".02" citation="COMAR 26.10.04.02" title_num="26" subtitle_num="10" chapter_num="04" heading="Operation and Maintenance of Corrosion Protection.">
  <paragraph num="A.">
    <text>An owner and an operator of a metal UST system with corrosion protection shall:</text>
    <paragraph num="(1)">
      <text>Comply with the requirements of this regulation to prevent a spill, release, or discharge due to corrosion until the UST system is permanently closed or undergoes a change-in-service pursuant to COMAR 26.10.10.02;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Operate and maintain a corrosion protection system to continuously provide corrosion protection to the metal components of the UST system in contact with the ground, including soil and backfill material, or continuous or intermittent water; and</text>
    </paragraph>
    <paragraph num="(3)">
      <text>If the UST system is protected by an impressed current system, design the UST system so that the impressed current source cannot be de-energized at any time, except to perform service work on the UST system or the impressed current system.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Inspections. An owner and an operator of a UST system equipped with a cathodic protection system shall comply with all of the following inspection requirements:</text>
    <paragraph num="(1)">
      <text>Determine if the cathodic protection system is adequate and complies with the requirements of this regulation by using criteria established in a NACE or STI code of practice incorporated by reference under COMAR 26.10.01.03;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Inspect the UST system for proper operation by having a qualified cathodic protection tester:</text>
      <paragraph num="(a)">
        <text>Test a field-installed cathodic protection system within 6 months of installation, and at least annually thereafter; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Test a factory-installed cathodic protection system within 6 months of installation, and at least once every 3 years thereafter;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>If a qualified cathodic protection tester determines the cathodic protection system is inadequate per a NACE or STI code of practice:</text>
      <paragraph num="(a)">
        <text>Notify the Department of the failed test in compliance with the suspected spill, release, or discharge reporting requirements in COMAR 26.10.08.01; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Repair the cathodic protection system in accordance with a NACE or STI code of practice within 60 days of the failed test; and</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>If the UST system is designed with an impressed current system:</text>
      <paragraph num="(a)">
        <text>Inspect the UST system at least every 60 days to ensure that the impressed current system is functioning properly; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Have a complete assessment of the impressed current system performed by a corrosion expert:</text>
        <paragraph num="(i)">
          <text>When the impressed current system reaches 5 years of age, and at least every 5 years after the most recent assessment; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>In accordance with the guidance as established under a NACE code of practice.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>An owner and an operator of a UST system equipped with a cathodic protection system shall:</text>
    <paragraph num="(1)">
      <text>In accordance with Regulation .05C of this chapter, maintain and upon request by the Department provide records of the operation and maintenance of the cathodic protection system that demonstrate compliance with performance standards of this regulation; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Include in the records required to be maintained under §C(1) of this regulation the following information:</text>
      <paragraph num="(a)">
        <text>The results of the last three inspections and the last assessment of an impressed current system conducted in accordance with §B(4) of this regulation; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The results of testing from the last two inspections of a cathodic protection system conducted in accordance with §B(2) of this regulation.</text>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>