<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".04" citation="COMAR 26.10.04.04" title_num="26" subtitle_num="10" chapter_num="04" heading="Repairs Allowed.">
  <paragraph num="A.">
    <text>An owner and an operator of a UST system shall conduct repairs that:</text>
    <paragraph num="(1)">
      <text>Prevent spills, releases, and discharges due to structural failure or corrosion for the entire period in which a UST system is used to store regulated substances;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Comply with the applicable code of practices developed by a nationally recognized association incorporated by reference under COMAR 26.10.01.03; and</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Meet all of the requirements of this chapter.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>An owner and an operator of a UST system shall have repairs to the equipment and components of the UST system performed or supervised by a UST system technician certified in accordance with COMAR 26.10.06.</text>
  </paragraph>
  <paragraph num="C.">
    <text>Repair Procedures. An owner and an operator of a UST system:</text>
    <paragraph num="(1)">
      <text>Upon approval of the Department, shall have repairs conducted on a fiberglass-reinforced plastic or steel UST:</text>
      <paragraph num="(a)">
        <text>By an authorized representative of the UST manufacturer; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>In accordance with a code of practice developed by a nationally recognized association incorporated by reference under COMAR 26.10.01.03;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>May not repair a UST by installing an internal liner;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Shall replace a metal pipe that has sections or fittings in which corrosion or other damage has resulted in:</text>
      <paragraph num="(a)">
        <text>A spill, release, or discharge of a regulated substance; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>An imminent threat of a spill, release, or discharge of a regulated substance, as determined by the Department;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>Shall repair non-corrodible pipes and fittings in accordance with the manufacturer’s specifications; and</text>
    </paragraph>
    <paragraph num="(5)">
      <text>Shall repair a containment sump with materials rated by the material manufacturer for the regulated substance stored in the UST system.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Testing of Repaired UST Systems. An owner and an operator of a repaired UST system shall:</text>
    <paragraph num="(1)">
      <text>Before placing the UST system back into service, conduct a precision tightness test in accordance with COMAR 26.10.03.05 to test the repaired UST and piping;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Before placing the UST system back into service, test secondary containment areas of the UST, piping, and containment sumps in accordance with:</text>
      <paragraph num="(a)">
        <text>The manufacturer’s instructions;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A code of practice developed by a nationally recognized association incorporated by reference under COMAR 26.10.01.03; or</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Requirements established by the Department; and</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Within 6 months of completing a repair on a cathodically protected UST system, test the cathodic protection system:</text>
      <paragraph num="(a)">
        <text>To ensure the cathodic protection system is operating properly; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>In accordance with Regulation .02B of this chapter.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Recordkeeping. In accordance with Regulation .05 of this chapter, an owner and an operator of a UST system shall maintain records of each repair conducted on the UST system until the UST system is permanently closed or undergoes a change-in-service pursuant to COMAR 26.10.10.02.</text>
  </paragraph>
</regulation>