<chapter num="05" heading="UST Systems: Release Detection" title_num="26" subtitle_num="10">
  <regulation prefix="Regulation" num=".01" heading="Release Detection: General Requirements for All UST Systems.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system shall provide a method, or combination of methods, of release detection that:</text>
      <paragraph num="(1)">
        <text>Can detect a spill, release, or discharge from any portion of the UST and the connected underground piping;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Is installed and calibrated in accordance with the manufacturer’s instructions;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Is operated and maintained in accordance with:</text>
        <paragraph num="(a)">
          <text>The manufacturer’s instructions;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>A code of practice incorporated by reference under COMAR 26.10.01.03; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Requirements determined by the Department to be not less protective of human health and the environment than §A(3)(a) or (b) of this regulation;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>Meets the performance requirements in Regulations .02 and .05 of this chapter, or COMAR 26.10.12 for a UST system with a field-constructed tank or an airport hydrant system, as applicable, with performance claims verified by the manufacturer’s specifications; and</text>
      </paragraph>
      <paragraph num="(5)">
        <text>Is capable of detecting a leak at a rate or quantity specified in this chapter with a probability of detection of not less than 0.95 and a probability of false alarm of not more than 0.05.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>Beginning January 12, 2009, an owner and an operator of a UST system installing a new or replacement UST system shall monitor the UST system for a spill, release, or discharge at least monthly by interstitial monitoring in accordance with Regulation .05G of this chapter.</text>
    </paragraph>
    <paragraph num="C.">
      <text>Release Detection Operability Test. An owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Have the electronic and mechanical components of a release detection method tested for proper operation in accordance with:</text>
        <paragraph num="(a)">
          <text>The manufacturer’s instructions;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>A code of practice incorporated by reference under COMAR 26.10.01.03; or</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Requirements determined by the Department to be not less protective of human health and the environment than §C(1)(a) or (b) of this regulation;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Perform an operability test of each electronic and mechanical component of a release detection method used at a regulated substance storage facility in accordance with the following criteria:</text>
        <paragraph num="(a)">
          <text>For the automatic tank gauge and other controllers:</text>
          <paragraph num="(i)">
            <text>Test the alarm;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Verify the system configuration; and</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>Test the battery backup;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>For the probes and sensors:</text>
          <paragraph num="(i)">
            <text>Inspect the equipment for residual buildup;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Ensure the floats move freely;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>Ensure the shafts are not damaged;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>Ensure the cables are free of kinks and breaks; and</text>
          </paragraph>
          <paragraph num="(v)">
            <text>Test the alarm operability and communication with the controller;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>Test the operation of the automatic line leak detector to meet the criteria in Regulation .02D(2) of this chapter by simulating a leak;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Ensure the proper communication of the vacuum pumps and pressure gauges with the sensors and controller; and</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Ensure the proper operation of the hand-held electronic sampling equipment associated with groundwater monitoring;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Perform the operability tests required by §C(1) and (2) of this regulation at least annually; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>Maintain the following records to show compliance with §C(1)—(3) of this regulation:</text>
        <paragraph num="(a)">
          <text>A list of each component tested;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Whether each component tested meets criteria specified or needs to have action taken; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>A description of any action taken to correct an issue.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Notifications.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall notify the Department in accordance with COMAR 26.10.08.01 when a release detection method operated in accordance with one of the following performance standards indicates that a spill, release, or discharge may have occurred:</text>
        <paragraph num="(a)">
          <text>Regulation .05 of this chapter; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the UST system has a field-constructed tank or an airport hydrant system, COMAR 26.10.12.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>If an owner, an operator, and a person in charge of a UST system changes the method of release detection used, the owner, the operator, and the person in charge of the UST system shall provide the Department written notification within 30 days of the change.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>An owner and an operator of a UST system that cannot apply a method of release detection that complies with the requirements of this chapter shall close the UST system in accordance with procedures in COMAR 26.10.10.</text>
    </paragraph>
    <paragraph num="F.">
      <text>An owner and an operator of a previously deferred UST system described in COMAR 26.10.02.01A(4)—(6) and COMAR 26.10.12 shall meet the requirements of this chapter not later than October 13, 2022.</text>
    </paragraph>
    <paragraph num="G.">
      <text>A person may not tamper with, or render inaccurate, any monitoring device or method required to be maintained under this chapter.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".02" heading="Requirements for UST Systems.">
    <paragraph num="A.">
      <text>An owner and an operator of a petroleum UST system or a hazardous substance UST system, unless otherwise provided in this regulation, shall provide release detection for USTs and piping as described in this regulation.</text>
    </paragraph>
    <paragraph num="B.">
      <text>An owner and an operator of a UST system shall monitor the UST system for releases of a regulated substance by:</text>
      <paragraph num="(1)">
        <text>Conducting inventory control in accordance with Regulation .04 of this chapter; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>At least monthly, conducting one of the methods of release detection described in Regulation .05B—H of this chapter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>An owner and an operator of a UST system with a UST capacity of 550 gallons or less and that is not metered may use weekly manual tank gauging conducted in accordance with Regulation .05C of this chapter as a method of release detection.</text>
    </paragraph>
    <paragraph num="D.">
      <text>Underground Piping.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall monitor underground piping that routinely contains petroleum vapor or a regulated substance in accordance with §D(2)—(4) of this regulation.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Pressurized Piping.</text>
        <paragraph num="(a)">
          <text>An owner and an operator of a UST system with underground piping that conveys regulated substances under pressure shall equip the underground piping with an automatic line leak detector that is tested annually in accordance with Regulation .01C of this chapter, and which will:</text>
          <paragraph num="(i)">
            <text>Alert the operator to the presence of a leak or a spill, release, or discharge by restricting or shutting off the flow of a regulated substance through piping or triggering an alarm; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Detect a leak or a spill, release, or discharge of a regulated substance of at least 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>An owner and an operator of a UST system with underground piping that conveys regulated substances under pressure shall:</text>
          <paragraph num="(i)">
            <text>At least annually, perform a precision tightness test on the piping for a minimum of 1 hour that is capable of detecting a 0.1 gallon per hour release at 1.5 times the pipe operating pressure; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>At least monthly, perform one of the methods of release detection described in Regulation .05B and F—H of this chapter.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Suction Piping.</text>
        <paragraph num="(a)">
          <text>An owner and an operator of a UST system with underground piping that conveys regulated substances under suction shall:</text>
          <paragraph num="(i)">
            <text>At least every 2 years, perform a precision tightness test on the piping for a minimum of 1 hour that is capable of detecting a 0.1 gallon per hour release at a pressure between 5 and 15 pounds per square inch; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>At least monthly, monitor for a spill, release, or discharge using one of the methods of release detection described in Regulation .05B and F—H of this chapter.</text>
          </paragraph>
        </paragraph>
        <paragraph num="(b)">
          <text>An owner and an operator of a UST system with underground suction piping are not required to perform the release detection and precision tightness testing required in §D(3)(a) of this regulation on the piping when:</text>
          <paragraph num="(i)">
            <text>The piping operates at less than atmospheric pressure;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The piping is sloped so that the contents of the pipe will drain back into the UST if the suction is released;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>A single check valve is included in each suction line;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>The check valve is located directly below and as close as practicable to the suction pump; and</text>
          </paragraph>
          <paragraph num="(v)">
            <text>The owner and operator of the UST system provide a method of visual inspection to determine compliance with §D(3)(b)(ii)—(iv) of this regulation.</text>
          </paragraph>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>An owner and an operator of a UST system with secondary containment piping shall test that piping:</text>
        <paragraph num="(a)">
          <text>After completing installation of the piping but before operation of the UST system, for new, upgraded, or replaced piping;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>At least every 5 years, for piping installed on or after January 12, 2009; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>In accordance with manufacturer’s specifications or a method approved by the Department.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".03" heading="Requirements for Hazardous Substance UST Systems.">
    <paragraph num="A.">
      <text>In addition to the UST system requirements in Regulation .02 of this chapter, an owner and an operator of a hazardous substance UST system shall:</text>
      <paragraph num="(1)">
        <text>Provide containment that meets the requirements of this regulation; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Monitor the containment systems using interstitial monitoring pursuant to Regulation .05G of this chapter at least monthly.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>An owner and an operator of a hazardous substance UST system shall ensure the hazardous substance UST system meets the following requirements:</text>
      <paragraph num="(1)">
        <text>A secondary containment system is designed, constructed, and installed to:</text>
        <paragraph num="(a)">
          <text>Contain hazardous substances spilled or released from the primary containment until the spill or release is detected and removed;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Prevent the spill, release, or discharge of hazardous substances to the environment at any time during the operational life of the UST system; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Be checked for evidence of a spill, release, or discharge at least monthly;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>A double-walled UST is designed, constructed, and installed to:</text>
        <paragraph num="(a)">
          <text>Contain a release from any portion of the inner storage tank within the outer wall; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Detect the failure of the inner wall;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>An external liner, including a vault, is designed, constructed, and installed to:</text>
        <paragraph num="(a)">
          <text>Contain 100 percent of the capacity of the largest UST within its boundary;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Prevent precipitation or groundwater from entering the liner; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Surround the UST completely;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>Underground piping is equipped with secondary containment that satisfies the requirements of §B(1)—(3) of this regulation; and</text>
      </paragraph>
      <paragraph num="(5)">
        <text>Underground piping that conveys hazardous substances under pressure is equipped with an automatic line leak detector in accordance with Regulation .02D(2) of this chapter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>An owner and an operator of hazardous substance UST system may use other methods of release detection in conjunction with interstitial monitoring as required in §A(2) of this regulation if the owner and an operator of the UST system:</text>
      <paragraph num="(1)">
        <text>Demonstrates to the Department in writing that an alternate method can detect a release of the stored hazardous substance as effectively as any of the methods allowed in Regulation .05B—H of this chapter,</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Provides the Department with information regarding effective corrective action technologies, health risks, and chemical and physical properties of the stored hazardous substance, and the physical characteristics of the regulated substance storage facility; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Obtains approval from the Department to use the alternate release detection method before the installation and operation of the UST system.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".04" heading="Inventory Control.">
    <paragraph num="A.">
      <text>Inventory Variations.</text>
      <paragraph num="(1)">
        <text>An owner and an operator of a UST system shall review the reconciled inventory records required by COMAR 26.10.04.01 for the following:</text>
        <paragraph num="(a)">
          <text>Inventory variations exceeding 1 percent plus 130 gallons of the metered quantity of a regulated substance each calendar month; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Daily inventory records that show 7 consecutive days of shortage totaling 80 gallons or more.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system shall conduct a review of reconciled inventory records at the following frequencies:</text>
        <paragraph num="(a)">
          <text>Review inventory variation as required under §A(1)(a) of this regulation monthly; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Review daily inventory records as required under §A(1)(b) of this regulation daily.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(3)">
        <text>Reporting and Investigating Inventory Variations.</text>
        <paragraph num="(a)">
          <text>An operator of a UST system shall report a variation or shortage as described in §A(1) of this regulation to the owner of the UST system;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Upon discovery of an inventory variation, an owner and an operator of a UST system shall immediately investigate the cause of the variation or shortage;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>If the investigation required under §A(3)(b) of this regulation reveals no indication of a discharge or release from a UST system, an owner and an operator of a UST system shall state the cause of the inventory variation or shortage in the daily inventory records; and</text>
        </paragraph>
        <paragraph num="(d)">
          <text>If the investigation required under §A(3)(b) of this regulation reveals a discharge or release from a UST system, an owner and an operator of a UST system shall follow the procedures established under COMAR 26.10.08.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>The Department may require an owner and an operator of a UST system to perform a precision tightness test of the UST system:</text>
      <paragraph num="(1)">
        <text>If the owner and the operator fail to reconcile daily inventory records as specified in COMAR 26.10.04.01 and review the reconciled records in accordance with §A of this regulation;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If the owner and the operator fail to comply with monthly release detection requirements of Regulation .05 of this chapter; or</text>
      </paragraph>
      <paragraph num="(3)">
        <text>For any other good cause as determined by the Department.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>The Department may require an owner and an operator of a UST system to perform a precision tightness test of the UST system and install monitoring wells or conduct a site assessment if there is reason to believe there is or may have been a discharge or release of a regulated substance from the UST system.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".05" heading="Method of Release Detection.">
    <paragraph num="A.">
      <text>In addition to the inventory control requirements in Regulation .04 of this chapter, an owner and an operator of a UST system shall perform one or a combination of the methods of release detection described in §§B—H of this regulation at least monthly.</text>
    </paragraph>
    <paragraph num="B.">
      <text>Statistical Inventory Reconciliation. An owner and an operator of a UST system utilizing statistical inventory reconciliation as a monthly method of release detection:</text>
      <paragraph num="(1)">
        <text>May only use statistical inventory reconciliation if the UST system is a metered UST system;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Shall use statistical inventory reconciliation to detect a spill, release, or discharge through application of statistical principles to inventory data, or another test of equivalent performance, with a probability of detection of not less than 0.95 and a probability of false alarm of not more than 0.05;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Shall use a method of statistical inventory reconciliation that meets the following requirements:</text>
        <paragraph num="(a)">
          <text>Uses inventory volume measurements collected in accordance with COMAR 26.10.04.01;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Produces a quantitative result with a calculated leak rate;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Is capable of detecting:</text>
          <paragraph num="(i)">
            <text>A leak rate of 0.2 gallon per hour; or</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>A spill, release, or discharge of 150 gallons within a month; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(d)">
          <text>Uses a threshold that does not exceed one-half the minimum detectible leak rate; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>Shall have a Department-approved third party conduct the statistical inventory reconciliation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Manual Tank Gauging.</text>
      <paragraph num="(1)">
        <text>At least weekly, an owner and an operator of a UST system shall perform manual tank gauging using a storage tank gauging stick maintained in accordance with COMAR 26.10.04.01 as follows:</text>
        <paragraph num="(a)">
          <text>Take UST liquid level measurements at the beginning and ending of an at least 36-hour period, during which liquid may not be added to or removed from the UST;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Base the level measurements on an average of two consecutive stick readings at both the beginning and ending of the period; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Using a UST gauge chart specific to the UST gauged, convert the liquid levels to the gallons present in the UST and review for any variations between the starting and ending measurements.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system shall report a suspected spill, release, or discharge and follow the investigation and confirmation procedures in COMAR 26.10.08 if the variation between beginning and ending manual tank gauging measurements performed in accordance with §C(1) of this regulation exceeds the weekly or monthly standards in the following table:</text>
      </paragraph>
      <paragraph num="(3)">
        <text>An owner and an operator of a UST system may use manual tank gauging:</text>
        <paragraph num="(a)">
          <text>As the sole method of release detection if the nominal capacity of a UST is 550 gallons or less; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>For a UST with a nominal capacity of 551 to 2,000 gallons only in conjunction with conducting a precision tightness test, as defined in COMAR 26.10.02.02, at least every 5 years in accordance with the requirements of COMAR 26.10.03.05.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>An owner and an operator of a UST system may not use manual tank gauging to meet the requirements of this chapter for a UST that has a nominal capacity of more than 2,000 gallons.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Precision Tightness Testing. At least monthly, an owner and an operator of a UST system shall conduct a precision tightness test, as defined in COMAR 26.10.02.02, as a method of release detection in accordance with the requirements of COMAR 26.10.03.05.</text>
    </paragraph>
    <paragraph num="E.">
      <text>Automatic Tank Gauging. At least monthly, an owner and an operator of a UST system shall perform automatic tank gauging using equipment that tests for the loss of regulated substance and conducts inventory control and that meets the following requirements:</text>
      <paragraph num="(1)">
        <text>The automatic regulated substance level monitor test is capable of detecting a 0.2 gallon per hour leak rate from any portion of the UST;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>The automatic tank gauging equipment meets the inventory control, or another test of equivalent performance, requirements of COMAR 26.10.04.01, and Regulation .04 of this chapter; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>An automatic tank gauging system tests for loss of a regulated substance by operating in one of the following modes:</text>
        <paragraph num="(a)">
          <text>In-tank static testing conducted at least once monthly; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Continuous in-tank leak detection operating on an uninterrupted basis or operating within a process that allows the automatic tank gauging system to gather incremental measurements to determine the leak status of the UST at least once monthly.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="F.">
      <text>Groundwater Monitoring.</text>
      <paragraph num="(1)">
        <text>Beginning June 13, 2022, an owner and an operator of a UST system may only use groundwater monitoring as a monthly method of release detection with prior written approval from the Department.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system shall conduct groundwater monitoring in accordance with the following requirements:</text>
        <paragraph num="(a)">
          <text>Perform a site assessment 60 days before the implementation of the groundwater monitoring method;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Provide a written report of the site assessment to the Department upon request and, beginning June 13, 2022, ensure the written report is signed by a professional engineer or professional geologist, or equivalent licensed professional with experience in environmental engineering, hydrogeology, or other relevant technical discipline acceptable to the Department; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Demonstrate that the testing or monitoring to detect a regulated substance on the groundwater meets all of the following requirements:</text>
          <paragraph num="(i)">
            <text>The regulated substance stored is immiscible in water and has a specific gravity of less than one;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Groundwater is never more than 15 feet from the ground surface and the hydraulic conductivity of the soil or soils between the UST system and the monitoring wells or devices is not less than 0.01 centimeter/second, with the soil consisting of gravels, coarse to medium sands, coarse silts, or other permeable materials;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>The slotted portion of the monitoring well casing is designed to prevent migration of natural soils or filter pack into the well and to allow entry of regulated substance on the water table into the well under both high and low groundwater conditions;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>Monitoring wells are sealed from the ground surface to the top of the filter pack;</text>
          </paragraph>
          <paragraph num="(v)">
            <text>Monitoring wells or devices intercept the UST excavation zone or positioned as close to the excavation zone as is technically feasible;</text>
          </paragraph>
          <paragraph num="(vi)">
            <text>The method of measuring the contents of the well, whether automatic or manual, is capable of detecting the presence of at least 1/8 of an inch of free product on top of the groundwater in the monitoring wells;</text>
          </paragraph>
          <paragraph num="(vii)">
            <text>At least monthly, the contents of the groundwater monitoring well are measured;</text>
          </paragraph>
          <paragraph num="(viii)">
            <text>Within and immediately below the UST system excavation zone, the site is assessed to ensure compliance with the requirements in §F(2)(c)(i)—(v) of this regulation and to establish the number and positioning of monitoring wells or devices that will detect discharges or releases from any portion of the UST system;</text>
          </paragraph>
          <paragraph num="(ix)">
            <text>Monitoring wells are clearly marked and secured to avoid unauthorized access and tampering; and</text>
          </paragraph>
          <paragraph num="(x)">
            <text>A key, a lock combination number, or access tool for all monitoring wells is provided to the Department upon request and made available on the site where the UST system is located.</text>
          </paragraph>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="G.">
      <text>Interstitial Monitoring.</text>
      <paragraph num="(1)">
        <text>Beginning June 13, 2022, an owner and an operator of a UST system may only use interstitial monitoring as a monthly method of release detection between a UST system and a secondary barrier as described in §G(2)(b) of this regulation with prior written approval from the Department.</text>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system may use interstitial monitoring between the UST system and a secondary barrier immediately around or beneath the UST system as a method of release detection if the UST system is designed, constructed, and installed to detect a spill, release, or discharge from any portion of the UST system and one of the following conditions are met:</text>
        <paragraph num="(a)">
          <text>For a double-walled UST system, the owner and operator of the UST system uses a sampling or testing method that can detect a spill or release through the inner wall in any portion of the UST system;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>For a UST system with a secondary barrier within the excavation zone, the owner or operator of the UST system uses a sampling or testing method that can detect a spill, release, or discharge between the UST system and the secondary barrier, provided that:</text>
          <paragraph num="(i)">
            <text>The secondary barrier around and beneath the UST system consists of artificially constructed material that is sufficiently thick and impermeable, at least 1×10-6 centimeter/second for the regulated substance stored, to direct a spill, release, or discharge to the monitoring point and allow the detection of the regulated substance;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The barrier is compatible with the regulated substance stored so that a spill, release, or discharge from the UST system will not cause a deterioration of the barrier and allow a spill, release, or discharge to pass through the barrier undetected;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>For cathodically protected UST systems, the owner and the operator installs a secondary barrier so that it does not interfere with the proper operation of the cathodic protection system;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>The groundwater, soil moisture, or rainfall will not make the testing or sampling method used inoperative so that a spill, release, or discharge could go undetected for more than 30 consecutive days;</text>
          </paragraph>
          <paragraph num="(v)">
            <text>The site is assessed to ensure that the secondary barrier is always above the groundwater and not in a 25-year flood plain, unless the barrier and monitoring designs are for use under these conditions; and</text>
          </paragraph>
          <paragraph num="(vi)">
            <text>Monitoring wells are clearly marked and secured with bolts or a lock to avoid unauthorized access and tampering; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>For USTs with an internally fitted liner, the owner and operator of the UST uses an automated device that can detect a spill or release between the inner wall of the UST and the liner, and the liner is compatible with the regulated substance stored.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="H.">
      <text>Other Methods.</text>
      <paragraph num="(1)">
        <text>Upon the approval of the Department, an owner and an operator of a UST system may use one or combination of alternative methods of monthly release detection if:</text>
        <paragraph num="(a)">
          <text>The method can detect a 0.2 gallon per hour leak rate or a release of 150 gallons within a month with a probability of detection of not less than 0.95 and a probability of false alarm of not more than 0.05; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The owner and the operator of the UST system can demonstrate to the Department that the method can detect a spill, release, or discharge as effectively as any of the methods allowed in §§B and D—G of this regulation.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>If an alternative method of monthly release detection proposed by an owner and an operator of a UST system is approved by the Department, the owner and the operator of the UST system shall comply with any conditions imposed by the Department on the use of the method to ensure the protection of human health and the environment.</text>
      </paragraph>
    </paragraph>
    <paragraph num="I.">
      <text>Vapor Monitoring. Except as provided in §H of this regulation, an owner and an operator of a UST system may not use vapor monitoring as a monthly method of release detection after April 1, 2009.</text>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".06" heading="Release Detection Recordkeeping.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system shall maintain records demonstrating compliance with the applicable requirements of this chapter:</text>
      <paragraph num="(1)">
        <text>In accordance with COMAR 26.10.04.05;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>For at least 1 year at the regulated substance storage facility;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>For at least 5 years at a location designated by the owner of the UST system; and</text>
      </paragraph>
      <paragraph num="(4)">
        <text>That include the following information:</text>
        <paragraph num="(a)">
          <text>Written performance claims pertaining to any release detection system used, and the manner in which these claims have been justified or tested by the equipment manufacturer or installer;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The results of any sampling, testing, or monitoring including:</text>
          <paragraph num="(i)">
            <text>The results of annual operability tests required in Regulation .01C of this chapter; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The results of precision tightness testing conducted in accordance with Regulation .05D of this chapter; and</text>
          </paragraph>
        </paragraph>
        <paragraph num="(c)">
          <text>Written documentation for all calibration, maintenance, and repair of release detection equipment permanently located on-site, and any schedules of required calibration and maintenance provided by the release detection equipment manufacturer.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>An owner and an operator of a UST system shall maintain records of site assessments required under Regulation .05F of this chapter for as long as the groundwater monitoring method is used.</text>
    </paragraph>
  </regulation>
  <annotations>
    <annotation type="Authority">Environment Article, §§4-401, 4-402, 4-405, 4-407—4-411.2, 4-415.1, 4-417, 4-701 et seq., and 7-201 et seq., Annotated Code of Maryland</annotation>
    <annotation type="History" subtype="Administrative History">Effective date: February 4, 1991 (18:2 Md. R. 151)</annotation>
    <annotation type="History" subtype="Administrative History">Chapter revised effective November 4, 1996 (23:22 Md. R. 1498)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .01 amended effective February 18, 2002 (29:3 Md. R. 224)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .01A amended effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02B amended effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02C amended effective January 16, 2006 (33:1 Md. R. 39)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02D amended effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04 amended effective January 12, 2009 (36:1 Md. R. 25)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04B amended effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .04C amended effective February 18, 2002 (29:3 Md. R. 224); January 16, 2006 (33:1 Md. R. 39)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .06 amended effective January 16, 2006 (33:1 Md. R. 39)</annotation>
    <annotation type="History" subtype="Administrative History">Regulations .01—.06 repealed and new Regulations .01—.06 adopted effective June 13, 2022 (49:12 Md. R. 642)</annotation>
  </annotations>