<?xml version='1.0' encoding='utf-8'?>
<chapter num="10" heading="Out-of-Service UST Systems and Closure" title_num="26" subtitle_num="10">
  <regulation prefix="Regulation" num=".01" heading="Temporary Closure.">
    <paragraph num="A.">
      <text>When a UST system is temporarily closed, an owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>If a metal UST system, continue operation and maintenance of corrosion protection in accordance with COMAR 26.10.04.02;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Except as provided in §B(3) of this regulation, maintain a method of release detection in accordance with COMAR 26.10.05 and, if the UST system has a field-constructed tank or is an airport hydrant system, COMAR 26.10.12;</text>
      </paragraph>
      <paragraph num="(3)">
        <text>If a spill, release, or discharge is suspected or confirmed, comply with the reporting, investigation, and corrective action requirements in COMAR 26.10.08 and 26.10.09;</text>
      </paragraph>
      <paragraph num="(4)">
        <text>In accordance with COMAR 26.10.03.09, amend the registration for the UST system not later than 30 days following the temporary closure of the UST system; and</text>
      </paragraph>
      <paragraph num="(5)">
        <text>If a motor fuel, bulk oil storage, used oil, or hazardous substance UST system, perform the UST system inspections required in COMAR 26.10.03.10.</text>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>When a UST system is temporarily closed and the storage tank system is emptied by having all materials removed using commonly employed practices so that not more than 1 inch of residue or 0.3 percent by weight of the total capacity of the UST remain in the UST system, an owner and an operator of a UST system is not required to perform:</text>
      <paragraph num="(1)">
        <text>Operation and maintenance testing and inspections of spill and overfill prevention equipment, as required by COMAR 26.10.03.03;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Periodic operation and maintenance walkthrough inspections, as required by COMAR 26.10.04.03; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>Operation and maintenance testing and inspections of release detection equipment, as required by COMAR 26.10.05.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>When a UST system is temporarily closed for 3 months or more, an owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Leave the vent line open and functioning; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Cap and secure all other lines, pumps, manways, and ancillary equipment.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>When a UST system does not meet the performance standards for new UST systems in COMAR 26.10.03.01 or the upgrading requirements in COMAR 26.10.03.08, except for the requirements of COMAR 26.10.03.08F, and the UST system has been temporarily closed for more than 6 months, an owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Permanently close the UST system in accordance with Regulations .02—.05 of this chapter; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If the Department grants an extension, permanently close the UST system within the time period established by the Department and in accordance with Regulations .02—.05 of this chapter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>When a UST system meets the performance standards for new UST systems in COMAR 26.10.03.01 or the upgrading requirements in COMAR 26.10.03.08, and the UST system has been temporarily closed for more than 1 year, an owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Permanently close the UST system in accordance with Regulations .02—.05 of this chapter; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>If the Department grants an extension, permanently close the UST system within the time period established by the Department and in accordance with Regulations .02—.05 of this chapter.</text>
      </paragraph>
    </paragraph>
    <paragraph num="F.">
      <text>An owner and an operator of a temporarily closed UST system required to permanently close the UST system under §D or E of this regulation may apply to the Department for an extension to the required time period for completing the permanent closure by:</text>
      <paragraph num="(1)">
        <text>Completing a site assessment in accordance with the procedures in Regulation .03 of this chapter; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Submitting a written site assessment report to the Department that includes, at a minimum, the following information:</text>
        <paragraph num="(a)">
          <text>The location of the UST system on the property;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The date the site assessment was performed;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>A summary of any field test and the laboratory analytical results;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>The name of the contractors who performed the work; and</text>
        </paragraph>
        <paragraph num="(e)">
          <text>All analytical data and laboratory reports.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".02" heading="Permanent Closure and Changes-in-Service.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system, an underground farm tank, an underground residential tank, and an underground residential heating oil tank shall have a permanent closure or change-in-service of a storage tank system performed by or under the supervision of a certified UST system technician or remover.</text>
    </paragraph>
    <paragraph num="B.">
      <text>An owner, an operator, and a person in charge of a UST system shall conduct a permanent closure or change-in-service of a storage tank system in accordance with the following documents:</text>
      <paragraph num="(1)">
        <text>API Recommended Practice 1604 “Closure of Underground Petroleum Storage Tanks”; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>PEI/RP 1700 “Recommended Practices for the Closure of Underground Storage Tank and Shop-Fabricated Aboveground Storage Tank Systems”.</text>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>Notification.</text>
      <paragraph num="(1)">
        <text>Unless a permanent closure or change-in-service of a UST system is performed in response to a corrective action, an owner, an operator, and a person in charge of a UST system shall notify the Department of a planned permanent closure or change-in-service of the UST system by submitting a notification:</text>
        <paragraph num="(a)">
          <text>In writing on a form provided by the Department; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>At least 30 days before beginning the permanent closure or change-in-service, or within another reasonable time period determined by the Department.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>An owner and an operator of a UST system shall confirm a planned permanent closure of a UST system with the Department 48 hours in advance of beginning the permanent closure.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>An owner and an operator of a UST system shall perform an assessment of the excavation zone, as required under Regulation .03 of this chapter:</text>
        <paragraph num="(a)">
          <text>After notifying the Department of a planned permanent closure or change-in-service of the UST system; and</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Before completion of the permanent closure or change-in-service of the UST system.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>In accordance with COMAR 26.10.03.09, an owner, an operator, and a person in charge of a UST system that was permanently closed or underwent a change-in-service shall amend the registration for the UST system after the permanent closure or change-in-service of the UST system is complete.</text>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>Permanent Closure.</text>
      <paragraph num="(1)">
        <text>When a UST system is permanently taken out-of-service, an owner and an operator of a UST system shall permanently close the UST system by:</text>
        <paragraph num="(a)">
          <text>Removing the UST system from the ground; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If approved by the Department, abandoning the UST system in place.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(2)">
        <text>Unless otherwise directed by the Department, an owner, an operator, and a person in charge of a UST system requesting to abandon the UST system in place shall provide the Department with a report signed by a professional engineer that confirms the permanent closure of the UST system by removal would have an adverse effect on a building foundation or other important structures or utilities within the immediate vicinity of the excavation zone.</text>
      </paragraph>
      <paragraph num="(3)">
        <text>To permanently close a UST system by removal or abandonment in place, an owner, an operator, and a person in charge of a UST system shall take the following actions:</text>
        <paragraph num="(a)">
          <text>Immediately before closing the UST system, empty and clean the UST and piping by removing all flammable, combustible, and other liquids and accumulated sludge from the UST system;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Unless otherwise directed by the Department, disconnect and remove all emptied lines;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Remove all aboveground portions of vent lines and cap the remaining lines at their bases; and</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Remove all regulated substances, sludge, and soil contaminated with a regulated substance found during the UST system closure for treatment or disposal in compliance with applicable federal, State, and local laws.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(4)">
        <text>If a UST system is permanently closed by removal, an owner, an operator, and a person in charge of a UST system shall take the following actions:</text>
        <paragraph num="(a)">
          <text>Purge all explosive vapors from the UST prior to removal from the excavation zone;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Monitor the UST with an appropriate meter for vapors before and during removal of the UST from the excavation zone;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Once the UST system has been removed from the excavation zone:</text>
          <paragraph num="(i)">
            <text>Retest the UST for flammable vapors and, if necessary, purge all remaining explosive vapors; and</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>Make holes or openings in the UST to render it unfit for further use;</text>
          </paragraph>
        </paragraph>
        <paragraph num="(d)">
          <text>If the operation poses a threat to public safety, do not crush or cut up the UST on-site;</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Dispose of the UST system materials at a location acceptable to the Department; and</text>
        </paragraph>
        <paragraph num="(f)">
          <text>Fill the former UST system excavation zone to grade with an appropriate fill material.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(5)">
        <text>If a UST system is permanently closed by abandonment in place, an owner, an operator, and a person in charge of a UST system shall take the following actions:</text>
        <paragraph num="(a)">
          <text>Do not fill the UST through a fill or vent pipe;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>Provide proper openings by excavation, or other means, on the UST to facilitate cleaning and filling the UST;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>Completely fill the UST with a solid, inert, and flowable material so there are no voids in the UST;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>Dispose of any removed UST system materials at a location acceptable to the Department; and</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Fill any excavated areas to grade with an appropriate fill material.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="E.">
      <text>Change-in-Service. When an owner and an operator of a UST system chooses to store a nonregulated substance in a UST system, the owner and the operator of the UST system shall:</text>
      <paragraph num="(1)">
        <text>Notify the Department of the planned change-in-service of the UST system in accordance with §C(1) of this regulation;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Before completing the change-in-service, perform a site assessment in accordance with Regulation .03 of this chapter; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>To conduct the change-in-service, empty and clean the UST and piping by removing all flammable, combustible, and other liquids and accumulated sludge from the UST system.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".03" heading="Assessing the Site at Closure or Change-in-Service.">
    <paragraph num="A.">
      <text>Before applying for an extension for temporary closure or completing a permanent closure or change-in-service of a UST system, an owner and an operator of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Perform a site assessment to determine if there is evidence of a spill, release, or discharge where contamination would most likely be present; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>In selecting sample types, sample locations, and measurement methods consider:</text>
        <paragraph num="(a)">
          <text>The method of closure;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The nature of the stored regulated substance;</text>
        </paragraph>
        <paragraph num="(c)">
          <text>The type of backfill;</text>
        </paragraph>
        <paragraph num="(d)">
          <text>The depth to groundwater; and</text>
        </paragraph>
        <paragraph num="(e)">
          <text>Other factors appropriate for identifying the presence of a spill, release, or discharge.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="B.">
      <text>If contaminated soil, contaminated groundwater, free product, or vapor is discovered while performing the actions under §A of this regulation or by any other manner during a UST system closure or change-in-service activities, an owner, an operator, and a person in charge of a UST system shall:</text>
      <paragraph num="(1)">
        <text>Notify the Department within 2 hours of the discovery, as required in COMAR 26.10.08; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Begin performing the response and corrective actions required in COMAR 26.10.09.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <regulation prefix="Regulation" num=".04" heading="Applicability to Previously Closed UST Systems.">
    <text>When directed by the Department, an owner and an operator of a UST system that was permanently closed before December 22, 1988 shall assess the excavation zone and close the UST system in accordance with this chapter if a spill, release, or discharge from the UST system may, in the judgment of the Department, pose a current or potential threat to human health and the environment.</text>
  </regulation>
  <regulation prefix="Regulation" num=".05" heading="Closure Records.">
    <paragraph num="A.">
      <text>An owner and an operator of a UST system shall maintain records in accordance with COMAR 26.10.04.05 that demonstrate compliance with closure requirements under this chapter.</text>
    </paragraph>
    <paragraph num="B.">
      <text>The owner and the operator of a UST system that took the UST system out-of-service or the current owner and operator of a property where the UST system was taken out-of-service shall:</text>
      <paragraph num="(1)">
        <text>Maintain the closure report required in §C of this regulation and the results of the site assessment required in Regulation .03 of this chapter for at least 5 years after completion of a permanent closure or change-in-service; and</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Maintain the records specified in §B(1) of this regulation by:</text>
        <paragraph num="(a)">
          <text>Storing the records at the property; or</text>
        </paragraph>
        <paragraph num="(b)">
          <text>If the records cannot be stored at the property, submitting the records to the Department.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="C.">
      <text>UST System Closure Report. An owner and an operator of a UST system that underwent a permanent closure or change-in-service shall submit to the Department a written UST system closure report:</text>
      <paragraph num="(1)">
        <text>Signed by the certified UST system technician or remover that performed the permanent closure or change-in-service;</text>
      </paragraph>
      <paragraph num="(2)">
        <text>Within 45 days of completing the UST system closure or change-in-service; and</text>
      </paragraph>
      <paragraph num="(3)">
        <text>That includes records documenting:</text>
        <paragraph num="(a)">
          <text>The permanent closure or change-in-service of the UST system was conducted in accordance with Regulation .02 of this chapter;</text>
        </paragraph>
        <paragraph num="(b)">
          <text>The site assessment was performed in accordance with Regulation .03 of this chapter; and</text>
        </paragraph>
        <paragraph num="(c)">
          <text>At a minimum, all of the following information:</text>
          <paragraph num="(i)">
            <text>The UST size;</text>
          </paragraph>
          <paragraph num="(ii)">
            <text>The location of the UST system on the property;</text>
          </paragraph>
          <paragraph num="(iii)">
            <text>The date of the UST system closure or change-in-service;</text>
          </paragraph>
          <paragraph num="(iv)">
            <text>The method used for the UST system closure or change-in-service;</text>
          </paragraph>
          <paragraph num="(v)">
            <text>A summary of the work performed;</text>
          </paragraph>
          <paragraph num="(vi)">
            <text>A summary of any field test and the laboratory analytical results;</text>
          </paragraph>
          <paragraph num="(vii)">
            <text>The name and certification number of the certified UST system technician or remover, and name of the contractors who performed the work;</text>
          </paragraph>
          <paragraph num="(viii)">
            <text>If permanently closed by removal, a receipt documenting proper disposal of the UST system;</text>
          </paragraph>
          <paragraph num="(ix)">
            <text>A receipt documenting proper treatment or disposal of excavated oil-contaminated soils;</text>
          </paragraph>
          <paragraph num="(x)">
            <text>All analytical data and laboratory reports; and</text>
          </paragraph>
          <paragraph num="(xi)">
            <text>Photographs of each UST system taken out-of-service and each excavation zone.</text>
          </paragraph>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="D.">
      <text>An owner and an operator of an underground farm tank, an underground residential tank, and an underground residential heating oil tank that does not meet the definition of a UST shall submit a written storage tank closure report in accordance with the requirements in §C of this regulation if:</text>
      <paragraph num="(1)">
        <text>A spill, release, or discharge occurred at the property that required the owner and the operator of the underground storage tank to notify the Department in compliance with COMAR 26.10.08 and 26.10.09; or</text>
      </paragraph>
      <paragraph num="(2)">
        <text>The Department directs the owner and the operator of the underground storage tank to submit a storage tank closure report.</text>
      </paragraph>
    </paragraph>
  </regulation>
  <annotations>
    <annotation type="Authority">Environment Article, §§4-402, 4-405, 4-407, 4-408, 4-410, 4-411, 4-411.1, 4-417, and 7-201 et seq., Annotated Code of Maryland</annotation>
    <annotation type="History" subtype="Administrative History">Effective date: February 4, 1991 (18:2 Md. R. 151)</annotation>
    <annotation type="History" subtype="Administrative History">Chapter revised effective November 4, 1996 (23:22 Md. R. 1498)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .01D amended effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulation .02F amended effective June 29, 1998 (25:13 Md. R. 997)</annotation>
    <annotation type="History" subtype="Administrative History">Regulations .01—.05 repealed and new Regulations .01—.05 adopted effective June 13, 2022 (49:12 Md. R. 642)</annotation>
  </annotations>
</chapter>