<regulation prefix="Regulation" num=".03" citation="COMAR 26.10.12.03" title_num="26" subtitle_num="10" chapter_num="12" heading="Upgrade Requirements.">
  <paragraph num="A.">
    <text>Not later than October 13, 2022, an owner and an operator of a UST system with a field-constructed tank or an airport hydrant system installed on or before June 13, 2022 shall comply with the upgrade requirements of this section.</text>
    <paragraph num="(1)">
      <text>Corrosion Protection. The owner and the operator of the UST system shall ensure the UST system components in contact with the ground:</text>
      <paragraph num="(a)">
        <text>Except as provided in Regulation .02 of this chapter, meet the new and replacement UST system performance standards for USTs in COMAR 26.10.03.01 and piping in COMAR 26.10.03.02; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Are constructed of metal and cathodically protected according to a NACE code of practice incorporated by reference under COMAR 26.10.01.03 and meet the following cathodic protection conditions:</text>
        <paragraph num="(i)">
          <text>The cathodic protection meets the requirements of COMAR 26.10.03.01B(1)(b) and (3) for USTs and COMAR 26.10.03.02B(1)(b) and (2) for piping; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>A UST greater than 10 years old without cathodic protection is assessed to ensure the UST is structurally sound and free of corrosion holes prior to adding cathodic protection through an internal inspection or another method determined by the Department.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Spill and Overfill Prevention Equipment. To prevent a spill, release, or discharge or an overfill associated with product transfer to a UST system, the owner and the operator of the UST system shall ensure the UST system meets the new UST system spill and overfill prevention equipment requirements specified in COMAR 26.10.03.03.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>An owner and an operator of a UST system with a field-constructed tank or an airport hydrant system not in compliance with §A of this regulation shall:</text>
    <paragraph num="(1)">
      <text>Immediately place the UST system in temporary closure in accordance with COMAR 26.10.10.01; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Permanently close the UST system in accordance with COMAR 26.10.10.02—.05 not later than April 13, 2023, or another time period established by the Department.</text>
    </paragraph>
  </paragraph>
</regulation>