<regulation prefix="Regulation" num=".10" citation="COMAR 26.10.17.10" title_num="26" subtitle_num="10" chapter_num="17" heading="Corrosion Protection.">
  <paragraph num="A.">
    <text>An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST that has a capacity less than 10,000 gallons shall install an elevated AST so that the storage tank is not in direct contact with soil or another material that may allow moisture penetration or corrosion.</text>
  </paragraph>
  <paragraph num="B.">
    <text>An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST that has a capacity of 10,000 gallons or greater, is not an elevated AST, and in direct contact with soil or another material that may allow moisture penetration or corrosion shall:</text>
    <paragraph num="(1)">
      <text>Provide one of the following cathodic protection systems:</text>
      <paragraph num="(a)">
        <text>An impressed current system;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A galvanic system; or</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Subject to the approval of the Department, an alternative method of corrosion protection that is:</text>
        <paragraph num="(i)">
          <text>Designed to prevent a spill, release, or discharge of oil or a threatened spill, release, or discharge of oil in a manner determined by the Department to be not less protective of human health and the environment than the methods in §B(1)(a) and (b) of this regulation; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Approved by a corrosion expert; and</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Provide a cathodic protection system that is:</text>
      <paragraph num="(a)">
        <text>Designed by a corrosion expert;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Designed and tested, at a minimum, in accordance with the following industry standards and recommended practices:</text>
        <paragraph num="(i)">
          <text>NACE SP0169-2013 “Control of External Corrosion on Underground or Submerged Metallic Piping Systems”;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>NACE SP0193-2016 “Application of Cathodic Protection to Control External Corrosion of Carbon Steel On-Grade Storage Tank Bottoms”;</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>NACE TM0497-2018 “Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Piping Systems”; and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>API Recommended Practice 651 “Cathodic Protection of Aboveground Petroleum Storage Tanks”;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>Designed and installed to provide continuous corrosion protection to the external portion of the AST and other metal components of the AST system in contact with soil or other materials that may allow corrosion;</text>
      </paragraph>
      <paragraph num="(d)">
        <text>Installed with easily identifiable test stations, access points, or other methods to monitor the operation and functionality of the cathodic protection system; and</text>
      </paragraph>
      <paragraph num="(e)">
        <text>Continuously operated and maintained for the in-service and out-of-service life of the AST system.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Impressed Current System. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST system protected by an impressed current system shall:</text>
    <paragraph num="(1)">
      <text>Install, operate, maintain, inspect, and test the impressed current system in accordance with the requirements of this section;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Ensure the impressed current source is not de-energized at any time except to perform service work on the AST system;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Ensure the impressed current source is equipped with a continuously operating meter that displays the voltage, amperage, and operating (run) time;</text>
    </paragraph>
    <paragraph num="(4)">
      <text>At least once every 60 days:</text>
      <paragraph num="(a)">
        <text>Inspect the impressed current system to ensure the cathodic protection system is functioning properly by:</text>
        <paragraph num="(i)">
          <text>Verifying the power source to the impressed current system is on; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Recording the voltage, amperage, and operating time; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Record and maintain the inspection results in accordance with Regulation .14 of this chapter;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>At least annually:</text>
      <paragraph num="(a)">
        <text>Have a cathodic protection tester inspect and test:</text>
        <paragraph num="(i)">
          <text>The impressed current system for electrical shorts, ground connections, meter accuracy, and circuit resistance; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>The condition of the impressed current system’s isolating devices, continuity bonds, and insulators; and</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Record and maintain the results of the inspection and test in accordance with Regulation .14 of this chapter;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(6)">
      <text>Have a corrosion expert inspect the impressed current system in accordance with an industry standard or recommended practice listed in §B(2) of this regulation:</text>
      <paragraph num="(a)">
        <text>When the impressed current system is 5 years of age; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Every 5 years thereafter;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(7)">
      <text>Provide a complete report for an inspection performed pursuant to §C(6) of this regulation to the Department and maintain a copy of the report in accordance with Regulation .14 of this chapter;</text>
    </paragraph>
    <paragraph num="(8)">
      <text>Except as provided in §C(9) of this regulation, if the protection provided by an impressed current system is determined to be inadequate to properly protect the AST system:</text>
      <paragraph num="(a)">
        <text>Employ a corrosion expert to determine the cause of the inadequacy within 30 days of the discovery; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Either:</text>
        <paragraph num="(i)">
          <text>Complete repairs of the impressed current system within 60 days of the discovery or on a schedule approved by the Department; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>If repairs cannot return the impressed current system to adequate performance, replace the impressed current system within 120 days of the discovery or on a schedule approved by the Department; and</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(9)">
      <text>If an impressed current system determined to be inadequate to provide proper protection to the AST system cannot be repaired or replaced in accordance with §C(8) of this regulation:</text>
      <paragraph num="(a)">
        <text>Empty all oil in contact with the portion of the AST system inadequately protected by the impressed current system; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Place the AST system out-of-service in accordance with Regulation .13 of this chapter.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Galvanic System. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST system protected by a galvanic system shall:</text>
    <paragraph num="(1)">
      <text>Install, operate, maintain, inspect, and test the galvanic system in accordance with the requirements of this section;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Comply with the following inspection and test requirements:</text>
      <paragraph num="(a)">
        <text>A cathodic protection tester shall inspect and test the galvanic system in accordance with an industry standard or recommended practice listed in §B(2) of this regulation:</text>
        <paragraph num="(i)">
          <text>Within 6 months of installing the galvanic system; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>At least annually thereafter;</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>A cathodic protection tester conducting an annual inspection shall make and record a sufficient number of AST-to-soil and underground piping-to-soil potential measurements to determine if the AST system is completely protected in accordance with an industry standard or recommended practice listed in §B(2) of this regulation; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Maintain records of the AST-to-soil and underground piping-to-soil potential measurements in accordance with Regulation .14 of this chapter;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Except as provided under §D(4) of this regulation, if the protection provided by a galvanic system is determined to be inadequate to properly protect the AST system:</text>
      <paragraph num="(a)">
        <text>Employ a corrosion expert to determine the cause of the inadequacy within 30 days of the discovery; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Either:</text>
        <paragraph num="(i)">
          <text>Complete repairs of the galvanic system within 60 days of the discovery or on a schedule approved by the Department; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>If repairs cannot return the galvanic system to adequate performance, replace the galvanic system within 120 days of the discovery or on a schedule approved by the Department; and</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>If a galvanic system determined to be inadequate to provide proper protection to the AST system cannot be repaired or replaced in accordance with §D(3) of this regulation:</text>
      <paragraph num="(a)">
        <text>Empty all oil in contact with the portion of the AST system inadequately protected by the galvanic system; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Place the AST system out-of-service in accordance with Regulation .13 of this chapter.</text>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>