<regulation prefix="Regulation" num=".13" citation="COMAR 26.10.17.13" title_num="26" subtitle_num="10" chapter_num="17" heading="Out-of-Service and Permanent Closure.">
  <paragraph num="A.">
    <text>The requirements of this regulation apply to an owner, an operator, and a person in charge of an AST system with a shop-fabricated AST required under COMAR 26.10.01.10 to register the AST system with the Department.</text>
  </paragraph>
  <paragraph num="B.">
    <text>Out-of-Service. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall complete each of the following steps to place the AST system out-of-service:</text>
    <paragraph num="(1)">
      <text>Remove all oil from the AST system;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Isolate all piping connected to the AST;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Remove all waste materials from the AST system, including storage tank-bottom sludge, and dispose of these materials in compliance with applicable federal, State, and local laws;</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Purge all petroleum vapors and maintain the AST system vapor free;</text>
    </paragraph>
    <paragraph num="(5)">
      <text>Secure the AST system to prevent unauthorized entrance or tampering;</text>
    </paragraph>
    <paragraph num="(6)">
      <text>Protect the AST system from flotation;</text>
    </paragraph>
    <paragraph num="(7)">
      <text>Continue the operation and maintenance of corrosion protection on the AST system in accordance with Regulation .10 of this chapter;</text>
    </paragraph>
    <paragraph num="(8)">
      <text>Lock the fill port;</text>
    </paragraph>
    <paragraph num="(9)">
      <text>Label the AST using lettering at least 3 inches high, in a readily visible location on the AST, with the following information:</text>
      <paragraph num="(a)">
        <text>Date the AST was placed out-of-service;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Name of product last stored; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>The words “OUT-OF-SERVICE” or “EMPTY”; and</text>
      </paragraph>
    </paragraph>
    <paragraph num="(10)">
      <text>Notify the Department in writing 30 days before placing the AST system out-of-service.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Return to In-Service. An owner, an operator, and a person in charge of an out-of-service AST system with a shop-fabricated AST shall complete each of the following steps prior to placing the AST system in-service:</text>
    <paragraph num="(1)">
      <text>If a formal inspection and leak test was due to occur while the AST system was out-of-service, conduct a formal inspection and leak test of the AST system in accordance with Regulation .12 of this chapter;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Test all connected piping and appurtenances to ensure a spill, release, or discharge will not occur;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Maintain a copy of all corrosion protection system and formal inspection and testing reports, including the findings of inspections and tests and repairs performed, and provide a copy to the Department upon request; and</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Notify the Department in writing 30 days before placing the AST system in-service.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Permanent Closure. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall permanently close the AST system in accordance with the following requirements:</text>
    <paragraph num="(1)">
      <text>At least 30 days before beginning the permanent closure of the AST system:</text>
      <paragraph num="(a)">
        <text>Notify the Department in writing of the planned AST system permanent closure; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Submit to the Department for approval a proposed sampling plan for a site assessment to determine if there is evidence of a spill, release, or discharge where contamination is most likely to be present, which includes the sampling of, at a minimum, the following areas of the AST site:</text>
        <paragraph num="(i)">
          <text>Within and immediately outside of the secondary containment dike, if present;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Within the footprint of the removed AST; and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Beneath underground piping associated with the removed AST;</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Place the AST system out-of-service in accordance with §B of this regulation;</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Comply with PEI RP 1700 “Recommended Practices for the Closure of Underground Storage Tank and Shop-Fabricated Aboveground Storage Tank Systems”;</text>
    </paragraph>
    <paragraph num="(4)">
      <text>Disconnect and remove all aboveground piping associated with the AST system;</text>
    </paragraph>
    <paragraph num="(5)">
      <text>Disconnect and remove all underground piping associated with the AST system:</text>
      <paragraph num="(a)">
        <text>Under the continuous on-site presence and direction of a certified UST system technician or remover; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>In accordance with the UST system permanent closure procedures in COMAR 26.10.10.02D;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(6)">
      <text>Remove the AST and associated piping from the site; and</text>
    </paragraph>
    <paragraph num="(7)">
      <text>Within 45 days of completing the permanent closure and approved site assessment, submit a closure report to the Department detailing:</text>
      <paragraph num="(a)">
        <text>The AST closure activities; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The results of the sampling event, including a map identifying sample locations, laboratory results, summary of findings, and conclusions.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Change-in-Service. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST placing the AST system out-of-service in order to store a non-oil product in the AST system shall:</text>
    <paragraph num="(1)">
      <text>Notify the Department in writing at least 30 days before placing the AST system out-of-service; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Place the AST system out-of-service in accordance with the requirements of the Department.</text>
    </paragraph>
  </paragraph>
  <paragraph num="F.">
    <text>Upon completing an out-of-service activity specified §§B—E of this regulation, an owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall:</text>
    <paragraph num="(1)">
      <text>Within 30 days, amend the AST system registration with the Department in accordance with COMAR 26.10.01.10; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>If the oil storage facility or oil handling facility is required under COMAR 26.10.01.09 to be operated under an Individual Oil Operation Permit, submit a request to modify the Individual Oil Operations Permit in accordance with COMAR 26.10.01.12.</text>
    </paragraph>
  </paragraph>