<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".02" citation="COMAR 26.10.18.02" title_num="26" subtitle_num="10" chapter_num="18" heading="Definitions.">
  <paragraph num="A.">
    <text>In this chapter:</text>
    <paragraph num="(1)">
      <text>A term in §B of this regulation has the meaning indicated; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>A term not defined in §B of this regulation has:</text>
      <paragraph num="(a)">
        <text>The meaning given to the term in a relevant statute or COMAR 26.10.01 or 26.10.02; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>If not defined in a relevant statute or COMAR 26.10.01 or 26.10.02, the meaning attributed by common use.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Terms Defined.</text>
    <paragraph num="(1)">
      <text>“AST” has the meaning stated in COMAR 26.10.01.02B.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>“AST system” has the meaning stated in COMAR 26.10.01.02B.</text>
    </paragraph>
    <paragraph num="(3)">
      <text>“Authorized inspector” means an individual qualified and certified to inspect an AST under API Standard 653 “Tank Inspection, Repair, Alteration, and Reconstruction”.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>“Coating” means a protective material applied to or bonded to an internal or external AST surface, including paint, protective metals, adhered plastic, or polyolefin materials.</text>
    </paragraph>
    <paragraph num="(5)">
      <text>Critical High Level.</text>
      <paragraph num="(a)">
        <text>“Critical high level” means the highest level in a field-erected AST that oil can reach without detrimental impacts, such as an overflow of oil from the AST or damage to the AST.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>“Critical high level” includes the design liquid level of a field-erected AST as determined by the AST manufacturer.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(6)">
      <text>“Existing” means the installation or construction of an AST, an AST system, or a secondary containment dike was complete before June 13, 2022.</text>
    </paragraph>
    <paragraph num="(7)">
      <text>“External inspection” means a formal inspection of an AST to assess all aspects of the storage tank possible without suspending operations or requiring an AST shutdown, performed by or under the supervision of an authorized inspector in accordance with API Standard 653 “Tank Inspection, Repair, Alteration, and Reconstruction” and Regulation .11F of this chapter.</text>
    </paragraph>
    <paragraph num="(8)">
      <text>Field-erected AST.</text>
      <paragraph num="(a)">
        <text>“Field-erected AST” means an AST that is:</text>
        <paragraph num="(i)">
          <text>Welded carbon steel or stainless steel;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Erected or constructed by assembling the AST on-site at an oil storage facility; and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Erected or constructed for the purpose of storing oil.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>“Field-erected AST” includes an AST that:</text>
        <paragraph num="(i)">
          <text>Has a nameplate or other identifier that indicates it is a field-erected AST; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Is not identified as a shop-fabricated AST.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(9)">
      <text>“Formal inspection” means a documented external inspection or internal inspection of an AST conducted by or under the supervision of an authorized inspector in accordance with API Standard 653 “Tank Inspection, Repair, Alteration, and Reconstruction” and Regulation .11 of this chapter.</text>
    </paragraph>
    <paragraph num="(10)">
      <text>“High-high level” means a level in a field-erected AST established under Regulation .07 of this chapter that:</text>
      <paragraph num="(a)">
        <text>Is sufficiently below the critical high level of the AST; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Enables the termination of an oil delivery or transfer before the critical high level in the AST is reached.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(11)">
      <text>“Internal inspection” means a formal and complete inspection of an emptied and cleaned AST performed under the supervision of an authorized inspector in accordance with API Standard 653 “Tank Inspection, Repair, Alteration, and Reconstruction” and Regulation .11H of this chapter.</text>
    </paragraph>
    <paragraph num="(12)">
      <text>Maximum Working Level.</text>
      <paragraph num="(a)">
        <text>“Maximum working level” means a liquid level of a field-erected AST that should not be exceeded during normal filling procedures and is at least 3 inches below the high-high level of the AST.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>“Maximum working level” includes the normal fill level.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(13)">
      <text>“New” means the installation or construction of an AST, an AST system, or a secondary containment dike was complete on or after June 13, 2022.</text>
    </paragraph>
    <paragraph num="(14)">
      <text>Out-of-Service.</text>
      <paragraph num="(a)">
        <text>“Out-of-service” means an AST system in which the owner, the operator, and the person in charge of the AST system has:</text>
        <paragraph num="(i)">
          <text>Emptied the AST system of all oil and sludge; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Designated the AST system as out-of-service in accordance with Regulation .12 of this chapter.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>“Out-of-service” includes a change-in-service in which an AST system is emptied of all oil and sludge in order to store a non-oil product.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(15)">
      <text>“Overfill” means an occurrence when an AST is filled beyond its critical high level and may result in a spill, release, or discharge of oil.</text>
    </paragraph>
    <paragraph num="(16)">
      <text>Repair.</text>
      <paragraph num="(a)">
        <text>“Repair” means work necessary to maintain or restore an AST system to a safe operating condition using industry approved standards.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>“Repair” may include</text>
        <paragraph num="(i)">
          <text>Removing and replacing the roof, shell, or bottom material to maintain AST integrity or ancillary AST equipment;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Re-leveling of an AST’s shell, bottom, or roof;</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Adding or replacing reinforcing plates to existing shell penetrations; and</text>
        </paragraph>
        <paragraph num="(iv)">
          <text>Correcting flaws, such as tears or gouges, by grinding or gouging followed by welding.</text>
        </paragraph>
      </paragraph>
    </paragraph>
    <paragraph num="(17)">
      <text>Secondary Containment Dike.</text>
      <paragraph num="(a)">
        <text>“Secondary containment dike” means a secondary containment system that confines a spill, release, or discharge of oil from an AST or piping within the secondary containment system.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>“Secondary containment dike” includes diking and a dike.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(18)">
      <text>“Storage tank strapping record” means a current, up-to-date storage tank record for a field-erected AST that:</text>
      <paragraph num="(a)">
        <text>Is developed by an owner, an operator, and a person in charge of an AST system; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Identifies, by calculations, the following levels of concern:</text>
        <paragraph num="(i)">
          <text>Maximum working level;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>High-high level; and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Critical high level.</text>
        </paragraph>
      </paragraph>
    </paragraph>
  </paragraph>
</regulation>