  <text>Table 1 Emission Standards and Dust Collector Performance Standards for Fuel-Burning Equipment
          
          
            Equipment Description
            Max. Rated Heat Inputin million Btu (gigajoules)per hour per furnace
            Max. Allowable Emissionsof Part. Matter—gr/scfd(mg/dscm)
          
        
        
          
            Existing and new equipmentburning residual oil
            Less than 13 (13.7)13—50 (13.7—52.8)50—250 (52.8—265)
            No Requirement (a)0.03 (69)0.020 (46)
          
          
            Existing and modifiedequipment (b) burningresidual oil
            Greater than 250 (265)
            0.020 (46)
          
          
            New equipment burningresidual oil
            Greater than 250 (265)
            0.01 (23)
          
          
            Equipment burningsolid fuel (c):Existing (b)NewNew and Existing
            Less than 250 (264)Less than 250 (264)250 (264) and Greater
            0.05 (114)0.03 (69)0.03 (69)</text>
  <paragraph num="(a)">
    <text>Construction of residual oil fired units of less than 13 million Btu (13.7 gigajoules) per hour prohibited (see Regulation .04).</text>
  </paragraph>
  <paragraph num="(b)">
    <text>Built before July 1, 1975.</text>
  </paragraph>
  <paragraph num="(c)">
    <text>Construction of new solid fuel fired units of less than 35 million Btu (37 gigajoules) per hour prohibited (see Regulation .04B).</text>
  </paragraph>
  <text>See Figures 1 &amp; 2.</text>
  <text>Notes:</text>
  <paragraph num="1.">
    <text>The construction of new residual oil fuel-burning equipment under 13 MM Btu (13.7 gigajoules) per hour is prohibited under Regulation .04.</text>
  </paragraph>
  <paragraph num="2.">
    <text>The construction of new solid fuel-burning equipment under 13 MM Btu (13.7 gigajoules) per hour is prohibited unless an exception has been approved by the Department (see Regulation .04).</text>
  </paragraph>
  <paragraph num="3.">
    <text>New fuel-burning equipment over 250 MM Btu (263.8 gigajoules) per hour are regulated by NSPS source regulations COMAR 26.11.06.12.</text>
  </paragraph>
  <paragraph num="4.">
    <text>Depending on load factor, fuel ash content, and control equipment, fuel-burning equipment which has a heat input greater than approximately 25 MM Btu (26.4 gigajoules) per hour may be subject to Prevention of Significant Deterioration Review (40 U.S.C. Part §52.21) and consequent additional control requirement.</text>
  </paragraph>