<regulation prefix="Regulation" num=".04" citation="COMAR 26.11.13.04" title_num="26" subtitle_num="11" chapter_num="13" heading="Loading Operations.">
  <paragraph num="A.">
    <text>Bulk Gasoline Terminals.</text>
    <paragraph num="(1)">
      <text>Standards. The owner or operator of a bulk gasoline terminal shall:</text>
      <paragraph num="(a)">
        <text>Equip the loading system with a vapor control system designed to collect all vapors and control at least 90 percent of all vapors from the loading racks, and emissions from the loading rack may not exceed:</text>
        <paragraph num="(i)">
          <text>0.29 pound of VOC per 1,000 gallons (35 milligrams per liter) of gasoline or VOC loaded in Areas III and IV and Calvert, Cecil, Charles, and Frederick counties; or</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>0.67 pounds of VOC per 1,000 gallons (80 milligrams per liter) of gasoline or VOC loaded in Area I and Caroline, Dorchester, Kent, Queen Anne's, St. Mary's, Somerset, Talbot, Wicomico, and Worcester counties.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Design and operate the vapor control system and the gasoline loading equipment so that during loading:</text>
        <paragraph num="(i)">
          <text>The gasoline tank truck pressure does not exceed 18 inches of water, and vacuum does not exceed 6 inches of water; and</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>There are no gasoline leaks in the system when tested by the method referenced in §A(3)(a) of this regulation during loading or unloading operations.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(c)">
        <text>Equip the loading rack with a top submerged or bottom loading system.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Compliance and Record Keeping.</text>
      <paragraph num="(a)">
        <text>Testing.</text>
        <paragraph num="(i)">
          <text>Vapor control systems shall be tested for compliance with §A(1)(a) of this regulation once every 5 years, during the period between May and September 15.</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>The owner or operator shall notify the Department not less than 15 days before the scheduled test date, and notification shall contain a copy of the test protocol.</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>A copy of the test results shall be submitted to the Department not more than 60 days after the test date.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>The owner or operator shall keep a record of all maintenance and repairs performed on the vapor recovery unit for 2 years, and make these records available upon request by the Department.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Test Procedures.</text>
      <paragraph num="(a)">
        <text>Testing for leak-tight conditions, as required in §A(1)(b)(ii) of this regulation, shall be conducted as prescribed in Method 1008 of the Department’s Technical Memorandum 91-01, “Test Methods and Equipment Specifications for Stationary Sources” January 1991, as amended through Supplement 3 (October 1, 1997), which is incorporated by reference in COMAR 26.11.01.04C.</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The test procedures to determine mass emission rate compliance as required in §A(1)(a) of this regulation, shall be as prescribed in Method 1009 of the Department’s Technical Memorandum 91-01, “Test Methods and Equipment Specifications for Stationary Sources” January 1991, as amended through Supplement 3 (October 1, 1997), which is incorporated by reference in COMAR 26.11.01.04C.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Bulk Gasoline Plants.</text>
    <paragraph num="(1)">
      <text>Applicability. Section B(2) of this regulation applies to a person owning or operating a bulk gasoline plant with a daily throughput of 4,000 gallons (15,140 liters) or greater.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Equipment Standards.</text>
      <paragraph num="(a)">
        <text>The owner or operator of a bulk gasoline plant shall:</text>
        <paragraph num="(i)">
          <text>Equip the loading rack with a vapor balance system which shall be properly installed, maintained, and used;</text>
        </paragraph>
        <paragraph num="(ii)">
          <text>Equip the loading rack with a top submerged or bottom loading system; and</text>
        </paragraph>
        <paragraph num="(iii)">
          <text>Comply with the leak-tight requirements as specified in §A(1)(b) of this regulation.</text>
        </paragraph>
      </paragraph>
      <paragraph num="(b)">
        <text>Stage I Vapor Recovery. A person who owns or operates a bulk plant may not cause or permit gasoline to be unloaded from a tank truck or trailer into a stationary storage tank unless the loading system is equipped with a vapor balance line that shall be properly installed, maintained, and used.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Small Storage Tanks.</text>
    <paragraph num="(1)">
      <text>Applicability. This section applies to a person who owns or operates:</text>
      <paragraph num="(a)">
        <text>A gasoline storage tank that has a tank capacity greater than 2,000 gallons but less than 40,000 gallons; or</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A gasoline tank truck used to transfer gasoline into a storage tank that is listed in §C(1)(a) of this regulation.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>Stage I Vapor Recovery. An owner or operator of a gasoline tank truck or an owner or operator of a stationary storage tank subject to this regulation may not cause or permit gasoline to be loaded into a stationary tank unless the loading system is equipped with a vapor balance line that is properly installed, maintained, and used.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>General Standards. A person may not cause or permit gasoline or VOC having a TVP of 1.5 psia (10.3 kilonewtons/square meter) or greater to be loaded into any tank truck, railroad tank car, or other contrivance unless the:</text>
    <paragraph num="(1)">
      <text>Loading connections on the vapor lines are equipped with fittings that have no leaks and that automatically and immediately close upon disconnection to prevent release of gasoline or VOC from these fittings; and</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Equipment is maintained and operated in a manner to prevent avoidable liquid leaks during loading or unloading operations.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Alternative Compliance Procedures. In lieu of satisfying the requirements of §D(1) of this regulation, a person may instead utilize:</text>
    <paragraph num="(a)">
      <text>An overhead loading rack installation which transfers VOC other than gasoline having a TVP of 1.5 psia (10.3 kilonewtons/square meter) from railroad tank car to tank trucks, or vice versa, using drip pans and other spill control equipment to limit the release of any product during post loading disconnections and any one of the following control practices or combination thereof:</text>
      <paragraph num="(i)">
        <text>Walking the hose clear of fluids;</text>
      </paragraph>
      <paragraph num="(ii)">
        <text>Running a pump to clear the line of fluids; or</text>
      </paragraph>
      <paragraph num="(iii)">
        <text>Application of inert gas to clear the line of fluids; or</text>
      </paragraph>
    </paragraph>
    <paragraph num="(b)">
      <text>An alternative equivalent vapor containment method approved by the Department and the EPA as a revision to the Maryland State Implementation Plan.</text>
    </paragraph>
  </paragraph>
</regulation>