<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".07" citation="COMAR 26.11.14.07" title_num="26" subtitle_num="11" chapter_num="14" heading="Control of NO">
  <paragraph num="A.">
    <text>Applicability and NOx Emission Standards.</text>
    <paragraph num="(1)">
      <text>This regulation applies to any fuel burning equipment with a maximum design heat input capacity of greater than 250 million Btu per hour located at any Kraft pulp mill.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>The total combined NOx emissions of all fuel burning equipment at the Luke Kraft pulp mill to which this regulation applies may not exceed the following:</text>
      <paragraph num="(a)">
        <text>An emission rate of 0.70 pounds of NOx per million Btu during the period May 1 through September 30 of each year;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>An emission rate of 0.99 pounds of NOx per million Btu during the period October 1 through April 30 of each year; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>The NOx ozone season emission cap in COMAR 26.11.40.03.</text>
      </paragraph>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Demonstrating Compliance.</text>
    <paragraph num="(1)">
      <text>Compliance with the NOx emission rates in §A(2)(a) and (b) of this regulation and the NOx ozone season emission cap in COMAR 26.11.40.03 shall be demonstrated with a continuous emission monitoring system that is installed, operated, and certified in accordance with 40 CFR Part 75.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Compliance with the emission rates in §A(2)(a) and (b) of this regulation shall be demonstrated as a 30-day rolling average.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>Monitoring and Reporting Requirements.</text>
    <paragraph num="(1)">
      <text>For boilers or combustion units at a Kraft pulp mill subject to this regulation, the owner or operator of the Kraft pulp mill shall:</text>
      <paragraph num="(a)">
        <text>Continuously monitor NOx emissions with a CEM system in accordance with 40 CFR Part 75, Subpart H and 40 CFR §51.121(i)(4); and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Maintain records and submit reports in accordance with 40 CFR Part 75.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(2)">
      <text>The owner or operator of a Kraft pulp mill subject to this regulation shall include emissions data obtained from a CEM pursuant to §C(1) of this regulation in the CEM quarterly reports submitted to the Department pursuant to COMAR 26.11.01.11E(2).</text>
    </paragraph>
  </paragraph>
</regulation>