<?xml version='1.0' encoding='utf-8'?>
<regulation prefix="Regulation" num=".10" citation="COMAR 26.13.05.10" title_num="26" subtitle_num="13" chapter_num="05" heading="General Requirements for Hazardous Waste Management in Tank Systems.">
  <paragraph num="A.">
    <text>Applicability.</text>
    <paragraph num="(1)">
      <text>Owners and operators of facilities that use tank systems to treat or store hazardous waste shall comply with the requirements of this regulation and Regulations .10-1—.10-7 of this chapter, except as otherwise provided in §A(2), (3), and (5) of this regulation or in Regulation .01 of this chapter.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Tank systems that are used to store or treat hazardous waste which contains no free liquids and are situated inside a building with an impermeable floor are exempted from the requirements of Regulation .10-4 of this chapter. To determine whether a waste contains free liquids, a person shall use EPA Method 9095 (Paint Filter Liquids Test) as described in “Test Methods for Evaluating Solid Wastes, Physical/Chemical Methods” (EPA Publication SW-846), which is incorporated by reference in COMAR 26.13.01.05A(4).</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Tank systems, including sumps as defined in COMAR 26.13.01.03B, that serve as part of a secondary containment system to collect or contain releases of hazardous wastes, are exempted from the requirements of Regulation .10-4A of this chapter.</text>
    </paragraph>
    <paragraph num="(4)">
      <text>For the purposes of classifying a tank system as either new or existing, installation of the tank system is considered to have begun if the following criteria are met:</text>
      <paragraph num="(a)">
        <text>The owner or operator has obtained all federal, State, and local approvals or permits necessary to begin physical construction of the site or installation of the tank system; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>A continuous on-site physical construction or installation program has begun, or the owner or operator has entered into contractual obligations, which cannot be canceled or modified without substantial loss, for either completion of physical construction of the site or installation of the tank system within a reasonable time.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>Tanks, sumps, and other collection devices or systems used in conjunction with drip pads as defined in COMAR 26.13.01.03B and regulated under Regulations .17-1—.17-4 of this chapter are subject to the requirements of this regulation and Regulations .10-1—.10-7 of this chapter.</text>
    </paragraph>
  </paragraph>
  <paragraph num="B.">
    <text>Waste Analysis and Trial Tests. In addition to the waste analysis required by Regulation .02D of this chapter, whenever a tank is to be used to chemically treat or store a hazardous waste which is substantially different from waste previously treated or stored in that tank, or chemically treat hazardous waste with a substantially different process than any previously used in that tank, the owner or operator shall, before treating or storing the different waste or using the different process:</text>
    <paragraph num="(1)">
      <text>Conduct waste analysis and trial treatment or storage tests, such as bench scale or pilot plant scale tests; or</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Obtain written, documented information on similar storage or treatment of similar waste under similar operating conditions, to show that this proposed treatment or storage will meet the requirements of §C(1) of this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="C.">
    <text>General Operating Requirements.</text>
    <paragraph num="(1)">
      <text>A person may not place hazardous wastes or treatment reagents in a tank system if they could cause the tank, its ancillary equipment, or the containment system to rupture, corrode, leak, or otherwise fail.</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Overfilling. The owner or operator shall use appropriate controls and practices to prevent spills and overflows from tank or containment systems, and, at a minimum, shall employ the following controls and practices to comply with this requirement:</text>
      <paragraph num="(a)">
        <text>Controls to prevent overfilling, such as level sensing devices, high level alarms, automatic feed cutoff, or by-pass to a standby tank;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>For uncovered tanks, maintenance of sufficient freeboard to prevent overtopping by wave or wind action or by precipitation; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Spill prevention controls, such as check valves or dry disconnect couplings.</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>The owner or operator shall comply with the requirements of Regulation .10-6 of this chapter if a leak or spill occurs in the tank system.</text>
    </paragraph>
  </paragraph>
  <paragraph num="D.">
    <text>Inspections. The owner or operator shall:</text>
    <paragraph num="(1)">
      <text>Develop and follow a schedule and procedure for inspecting overfill controls;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Inspect at least once each operating day:</text>
      <paragraph num="(a)">
        <text>Data gathered from monitoring and leak detection equipment, such as pressure and temperature gauges and monitoring wells, to ensure that the tank system is being operated according to its design;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>For uncovered tanks, the level of waste in the tank to ensure compliance with §C(2)(b) of this regulation;</text>
      </paragraph>
      <paragraph num="(c)">
        <text>Above-ground portions of the tank system to detect corrosion or releases of waste; and</text>
      </paragraph>
      <paragraph num="(d)">
        <text>The construction materials of, and the area immediately surrounding the externally accessible portion of the tank system, including the secondary containment system, to detect erosion or signs of releases of hazardous wastes, such as wet spots or dead vegetation;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(3)">
      <text>Inspect cathodic protection systems, if present, according to, at a minimum, the following schedule to ensure that they are functioning properly:</text>
      <paragraph num="(a)">
        <text>Confirm proper operation of the cathodic protection system within 6 months after initial installation and annually after that; and</text>
      </paragraph>
      <paragraph num="(b)">
        <text>Inspect or test, or both, as appropriate, all sources of impressed current at least every 2 months;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(4)">
      <text>Develop, as part of the inspection schedule required in Regulation .02F of this chapter, and in addition to the specific requirements of §D(1)—(3) of this regulation, a schedule and procedures for assessing the condition of the tank which meet the following requirements:</text>
      <paragraph num="(a)">
        <text>The schedule and procedures shall be adequate to detect cracks, leaks, corrosion, or erosion which may prevent compliance with §C(1) of this regulation;</text>
      </paragraph>
      <paragraph num="(b)">
        <text>The inspection procedure shall include procedures for emptying a tank to allow entry and inspection of the interior when tank entry is necessary to detect corrosion or erosion of the tank sides and bottom; and</text>
      </paragraph>
      <paragraph num="(c)">
        <text>The scheduled frequency of assessments shall be based on the material of construction of the tank, type of corrosion or erosion protection used, rate of corrosion or erosion observed during the previous inspections, and the characteristics of the waste being treated or stored;</text>
      </paragraph>
    </paragraph>
    <paragraph num="(5)">
      <text>Document, in the operating record of the facility, inspections of the items required to be made in §D(1)—(4) of this regulation.</text>
    </paragraph>
  </paragraph>
  <paragraph num="E.">
    <text>Air Emissions. The owner or operator shall provide all tanks with the treatment process controls, emission controls, and safety or emergency procedures that are necessary to protect human health and the environment from toxic or otherwise harmful fumes, mists, or gases resulting from:</text>
    <paragraph num="(1)">
      <text>Volatilization of wastes stored or treated in the tank;</text>
    </paragraph>
    <paragraph num="(2)">
      <text>Chemical reactions in the tank, either routine or resulting from process upsets; or</text>
    </paragraph>
    <paragraph num="(3)">
      <text>Physical agitation or other forms of treatment conducted in the tank.</text>
    </paragraph>
  </paragraph>
</regulation>